Files
lmxopcua/tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Tests/ModbusProtocolOptionsTests.cs
T
Joseph Doherty 64e3fbe035
v2-ci / build (push) Failing after 1m43s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (push) Has been skipped
docs: backfill XML documentation across 756 files
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
2026-05-28 08:10:17 -04:00

152 lines
7.1 KiB
C#

using Shouldly;
using Xunit;
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.Tests;
/// <summary>
/// #140 protocol-behavior knobs: MaxCoilsPerRead, UseFC15ForSingleCoilWrites,
/// UseFC16ForSingleRegisterWrites, DisableFC23. Coverage focuses on default behaviour
/// (no change from pre-#140) and the wire-FC selection when the knobs are flipped.
/// </summary>
[Trait("Category", "Unit")]
public sealed class ModbusProtocolOptionsTests
{
private sealed class CapturingTransport : IModbusTransport
{
public readonly List<byte[]> Sent = new();
/// <summary>Asynchronously connects the transport.</summary>
/// <param name="ct">The cancellation token.</param>
/// <returns>A completed task.</returns>
public Task ConnectAsync(CancellationToken ct) => Task.CompletedTask;
/// <summary>Asynchronously sends a Modbus PDU and returns a response.</summary>
/// <param name="unitId">The Modbus unit ID.</param>
/// <param name="pdu">The protocol data unit to send.</param>
/// <param name="ct">The cancellation token.</param>
/// <returns>A task that returns the response bytes.</returns>
public Task<byte[]> SendAsync(byte unitId, byte[] pdu, CancellationToken ct)
{
Sent.Add(pdu);
// Return a minimal valid response per FC. We zero-fill the data slot but size it
// correctly so the driver's bitmap walker doesn't IndexOutOfRange on chunked reads.
switch (pdu[0])
{
case 0x05: case 0x06: case 0x0F: case 0x10:
return Task.FromResult(pdu); // echo
case 0x01: case 0x02:
{
var qty = (ushort)((pdu[3] << 8) | pdu[4]);
var byteCount = (byte)((qty + 7) / 8);
var resp = new byte[2 + byteCount];
resp[0] = pdu[0]; resp[1] = byteCount;
return Task.FromResult(resp);
}
case 0x03: case 0x04:
{
var qty = (ushort)((pdu[3] << 8) | pdu[4]);
var byteCount = (byte)(qty * 2);
var resp = new byte[2 + byteCount];
resp[0] = pdu[0]; resp[1] = byteCount;
return Task.FromResult(resp);
}
default:
return Task.FromResult(new byte[] { pdu[0], 0, 0 });
}
}
/// <summary>Asynchronously disposes the transport.</summary>
/// <returns>A completed task.</returns>
public ValueTask DisposeAsync() => ValueTask.CompletedTask;
}
/// <summary>Verifies that defaults match historical behavior.</summary>
[Fact]
public void Defaults_Match_Historical_Behaviour()
{
var opts = new ModbusDriverOptions();
opts.MaxCoilsPerRead.ShouldBe((ushort)2000);
opts.UseFC15ForSingleCoilWrites.ShouldBeFalse();
opts.UseFC16ForSingleRegisterWrites.ShouldBeFalse();
opts.DisableFC23.ShouldBeFalse();
}
/// <summary>Verifies that single coil write uses FC05 by default.</summary>
[Fact]
public async Task Single_Coil_Write_Uses_FC05_By_Default()
{
var fake = new CapturingTransport();
var tag = new ModbusTagDefinition("Run", ModbusRegion.Coils, 0, ModbusDataType.Bool);
var drv = new ModbusDriver(new ModbusDriverOptions { Host = "f", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } }, "m1", _ => fake);
await drv.InitializeAsync("{}", CancellationToken.None);
await drv.WriteAsync([new WriteRequest("Run", true)], CancellationToken.None);
fake.Sent.Last()[0].ShouldBe((byte)0x05); // FC05 Write Single Coil
}
/// <summary>Verifies that single coil write uses FC15 when forced.</summary>
[Fact]
public async Task Single_Coil_Write_Uses_FC15_When_Forced()
{
var fake = new CapturingTransport();
var tag = new ModbusTagDefinition("Run", ModbusRegion.Coils, 0, ModbusDataType.Bool);
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], UseFC15ForSingleCoilWrites = true, Probe = new ModbusProbeOptions { Enabled = false } };
var drv = new ModbusDriver(opts, "m1", _ => fake);
await drv.InitializeAsync("{}", CancellationToken.None);
await drv.WriteAsync([new WriteRequest("Run", true)], CancellationToken.None);
fake.Sent.Last()[0].ShouldBe((byte)0x0F); // FC15 Write Multiple Coils
}
/// <summary>Verifies that single register write uses FC06 by default.</summary>
[Fact]
public async Task Single_Register_Write_Uses_FC06_By_Default()
{
var fake = new CapturingTransport();
var tag = new ModbusTagDefinition("Sp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
var drv = new ModbusDriver(new ModbusDriverOptions { Host = "f", Tags = [tag], Probe = new ModbusProbeOptions { Enabled = false } }, "m1", _ => fake);
await drv.InitializeAsync("{}", CancellationToken.None);
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
fake.Sent.Last()[0].ShouldBe((byte)0x06); // FC06 Write Single Register
}
/// <summary>Verifies that single register write uses FC16 when forced.</summary>
[Fact]
public async Task Single_Register_Write_Uses_FC16_When_Forced()
{
var fake = new CapturingTransport();
var tag = new ModbusTagDefinition("Sp", ModbusRegion.HoldingRegisters, 0, ModbusDataType.Int16);
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], UseFC16ForSingleRegisterWrites = true, Probe = new ModbusProbeOptions { Enabled = false } };
var drv = new ModbusDriver(opts, "m1", _ => fake);
await drv.InitializeAsync("{}", CancellationToken.None);
await drv.WriteAsync([new WriteRequest("Sp", (short)42)], CancellationToken.None);
fake.Sent.Last()[0].ShouldBe((byte)0x10); // FC16 Write Multiple Registers
}
/// <summary>Verifies that coil array read automatically chunks at MaxCoilsPerRead.</summary>
[Fact]
public async Task Coil_Array_Read_Auto_Chunks_At_MaxCoilsPerRead()
{
var fake = new CapturingTransport();
// 2500 coils with cap 2000 → 2 reads (2000 + 500).
var tag = new ModbusTagDefinition("Big", ModbusRegion.Coils, 0, ModbusDataType.Bool, ArrayCount: 2500);
var opts = new ModbusDriverOptions { Host = "f", Tags = [tag], MaxCoilsPerRead = 2000, Probe = new ModbusProbeOptions { Enabled = false } };
var drv = new ModbusDriver(opts, "m1", _ => fake);
await drv.InitializeAsync("{}", CancellationToken.None);
await drv.ReadAsync(["Big"], CancellationToken.None);
// Ignore the probe FC03 from InitializeAsync; count only FC01 reads.
var fc01s = fake.Sent.Where(p => p[0] == 0x01).ToList();
fc01s.Count.ShouldBe(2);
// First chunk asks for 2000.
((ushort)((fc01s[0][3] << 8) | fc01s[0][4])).ShouldBe((ushort)2000);
// Second chunk asks for 500.
((ushort)((fc01s[1][3] << 8) | fc01s[1][4])).ShouldBe((ushort)500);
}
}