AB CIP Driver
In-process native-protocol driver that exposes Allen-Bradley CIP / EtherNet-IP
controllers as OPC UA nodes. It runs inside the OtOpcUa server's .NET 10 AnyCPU
process and talks to the PLC through the libplctag.NET wrapper — no gateway, no
sidecar. One driver instance can serve many devices; per-device routing is keyed
on the canonical ab://gateway[:port]/cip-path host-address string.
Supported families: ControlLogix, CompactLogix, Micro800, and
GuardLogix. CIP has no native push model, so subscriptions are a polling
overlay on top of IReadable.
For the driver spec (capability surface, config shape, type mapping), see docs/v2/driver-specs.md §3. For the manual test client, see Driver.AbCip.Cli.md. For the integration fixture coverage map, see AbServer-Test-Fixture.md.
Project Layout
| Project | Role |
|---|---|
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbCip/ |
The driver — AbCipDriver, the libplctag runtime/enumerator/template-reader wrappers, the UDT read planner + template decoders, the host-address parser, and the ALMD alarm projection. |
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Ab.LibplctagShared/ |
Project-less shared source (LibplctagOrphanRelease.cs, #578/#580) compiled into both Driver.AbCip and Driver.AbLegacy. The AbStatus → OPC UA table is shared in Driver.Ab.Transport (AbOpcUaStatusMap). |
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Contracts/ |
AbCipDriverOptions, AbCipDeviceOptions, AbCipTagDefinition / AbCipStructureMember, and the AbCipDataType / AbCipPlcFamily enums bound from the driver's DriverConfig JSON. |
Per family the AbCipPlcFamilyProfile (PlcFamilies/AbCipPlcFamilyProfile.cs)
supplies the libplctag plc attribute, default CIP path, ConnectionSize, and
request-packing / connected-messaging quirks — ControlLogix is the baseline and
each other family is a delta (Micro800 is unconnected-only with no backplane
routing; GuardLogix shares the ControlLogix wire protocol with a tag-level safety
partition).
Capability Surface
AbCipDriver : IDriver, IReadable, IWritable, ITagDiscovery, ISubscribable, IHostConnectivityProbe, IPerCallHostResolver, IAlarmSource, IDisposable, IAsyncDisposable
(Driver.AbCip/AbCipDriver.cs). It adds IAlarmSource over the Modbus /
AB Legacy surface.
| Capability | Implementation entry point | Notes |
|---|---|---|
ITagDiscovery |
DiscoverAsync |
Emits pre-declared tags under per-device folders; UDT tags with declared Members fan out into a sub-folder + one variable per member. With EnableControllerBrowse the @tags symbol table — plus each Program:<name>.@tags listing — is walked into a Discovered/ folder (system/module/routine tags filtered out). |
IReadable |
ReadAsync → ReadGroupAsync / ReadSingleAsync |
Per-tag reads; opt-in whole-UDT grouping (EnableDeclarationOnlyUdtGrouping) collapses N member reads into one. |
IWritable |
WriteAsync |
BOOL-within-DINT writes do a per-parent read-modify-write under a lock; SafetyTag and non-writable tags return BadNotWritable. |
ISubscribable |
SubscribeAsync driven by the shared PollGroupEngine |
CIP has no push model — subscriptions become polling groups. |
IHostConnectivityProbe |
ProbeLoopAsync + GetHostStatuses |
One probe loop per device reading Probe.ProbeTagPath; no path configured ⇒ a warning is logged and the device stays Unknown. |
IPerCallHostResolver |
ResolveHost |
Routes each call to the tag's DeviceHostAddress, the breaker key for the resilience pipeline so one dead PLC trips only its own breaker. |
IAlarmSource |
AbCipAlarmProjection (ALMD) |
Opt-in via EnableAlarmProjection; off by default the subscribe path is a no-op so capability negotiation still works. |
Addressing Model
Per-device host addresses are the canonical ab://gateway[:port]/cip-path form
parsed by AbCipHostAddress.TryParse (AbCipHostAddress.cs). The parsed
CipPath is handed to libplctag verbatim, so no wire-layer translation is
needed:
| Form | Meaning |
|---|---|
ab://10.0.0.5/1,0 |
Single-chassis ControlLogix, CPU in slot 0 |
ab://10.0.0.5/1,2,2,192.168.50.20,1,0 |
Bridged ControlLogix (routed path) |
ab://10.0.0.5/ |
Micro800 / no-backplane device (empty path) |
ab://10.0.0.5:44818/1,0 |
Explicit EIP port (default 44818) |
Tags carry a Logix symbolic TagPath (controller or program scope). UDT-typed
tags are declared as AbCipDataType.Structure with a Members list; discovery
fans each member out as {tag.Name}.{member.Name}, and the read planner can
collapse a batch of members into one whole-UDT read when
EnableDeclarationOnlyUdtGrouping is set. The whole-UDT fast path is opt-in
because Studio 5000 may reorder members vs declaration order; decoding at
declaration-order offsets against a reordered layout yields silently-plausible
wrong numbers.
Configuration
AbCipDriverOptions (Driver.AbCip.Contracts/AbCipDriverOptions.cs) binds from
the driver's DriverConfig JSON. Key fields:
Devices— oneAbCipDeviceOptionsper PLC (HostAddress,PlcFamily, optionalDeviceName, per-deviceAllowPacking/ConnectionSizeoverrides).Tags— pre-declaredAbCipTagDefinitionlist;Membersfor UDT fan-out,SafetyTagfor GuardLogix safety-partition tags.Probe— connectivity-probeEnabled/Interval/Timeout/ProbeTagPath. A driver created from the AdminUI starts with the probe off (an enabled probe with no tag path only logs a warning); an absentprobekey in a stored config still means enabled to the driver.- AdminUI driver forms (AbCip/AbLegacy) overlay only the keys they edit onto the stored JSON, so unmodelled keys survive a save (#576). They also write durations as the integer-millisecond keys the factory binds (
timeoutMs,alarmPollIntervalMs,probe.intervalMs,probe.timeoutMs); a legacy TimeSpan-string key (timeout: "00:00:05") is loaded and migrated on save. Transport— absent (default ⇒Native),Native, orLibplctag(fallback); see Transport.- Discovery —
EnableControllerBrowse(@tagswalk),EnableDeclarationOnlyUdtGrouping(whole-UDT read fast path) andbrowsePageDelayMs(native browse pacing, see Native browse). - Alarms —
EnableAlarmProjection+AlarmPollIntervalfor the ALMD projection.
Full per-field descriptions live in AbCipDriverOptions.cs. The JSON skeleton is
reproduced in docs/v2/driver-specs.md §3.
Transport (transport option)
The driver has two interchangeable wire transports, selected by one DriverConfig key:
| Key | Values | Default | Serialization |
|---|---|---|---|
transport |
absent | Native | Libplctag |
absent ⇒ the node's Drivers:AbCip:DefaultTransport (itself default Native) |
string, case-insensitive on read, written as "Libplctag" / "Native"; "use the default" is encoded by OMITTING the key |
Native(the default since Task 22) is a managed in-process EtherNet/IP + CIP client (Driver.Ab.Transport).Libplctag(fallback) drives the libplctag native library, as before.- An absent key means "use the default". It is resolved in one place,
AbCipTransportResolver, which the driver, the Test Connect probe and the CLI all go through. Precedence: an explicit per-driver key → the node-level appsettingDrivers:AbCip:DefaultTransport(Native|Libplctag, envDrivers__AbCip__DefaultTransport; a bad value fails host start; see Configuration.md) → compiledNative. The Test Connect probe uses the same node value, so it probes the stack the driver would run. The CLI has no node config and uses compiledNative. - A bad value fails like a bad
PlcFamily; the Test Connect probe reports "Config JSON is invalid". - A change takes effect when the driver instance is constructed: on every process start (so the upgrade
restart moves no-key drivers to Native — see the release note) and when a deploy that changes
DriverConfigdoes this (DriverHostActorrespawns the child, #516).ReinitializeAsyncalone keeps the transport it was constructed with. - AdminUI: the Transport dropdown in the advanced section of the AbCip driver form ("Default (node setting; Native unless pinned)" / "Native (managed)" / "libplctag (fallback)"). Default omits the key on save, so a defaulted driver stays defaulted; saving another field preserves an explicit value and preserves absence.
- The driver logs
transport=<effective> (default|configured)at Information on every init, e.g.transport=Native (default)ortransport=Libplctag (node default), including reconnect re-inits. AbCip drivers now receive the host logger (they previously ran on a null logger, so none of their warnings reached the node log); expect previously invisible warnings, e.g. a probe enabled with no probe tag path. - CLI:
--transport default|native|libplctag(defaultdefault, which goes through the same resolver). - libplctag is confined to
Libplctag*.csadapters, enforced by a source-scan guard (LibplctagConfinementGuardTests), so removing it later is mechanical.
Release note — native is the default (Task 22)
- The native managed transport is now the default. A driver config with no
transportkey runsNative; libplctag remains available as the fallback. - ⚠️ Client-visible: native reports
BadTypeMismatchfor a mis-authored same-width type (for example a tag authoredDINTwhere the controller holds aREAL), where libplctag returned Good garbage. Correct the authored type; see Native transport behaviour. It does not degrade driver health or churn the connection; one Warning per tag names it. - To fall back one driver, set
"transport": "Libplctag"in its driver config (or pick "libplctag (fallback)" in the AdminUI dropdown). To fall back a whole node, setDrivers:AbCip:DefaultTransporttoLibplctag(below). - ⚠️ When it takes effect: the upgrade restart itself. Every process start constructs the drivers
(including boot-from-cache on a driver-only node), so every driver with no
transportkey moves to the node default —Nativeunless pinned — the moment the upgraded node starts; no deploy is needed. After the upgrade, a per-driver transport change takes effect when a deploy recreates the driver (not onReinitializeAsync). - To stay on libplctag across the upgrade (pin before upgrading): set the node-level key on each node
you upgrade, in the same change that installs the new build —
appsettings.json"Drivers": { "AbCip": { "DefaultTransport": "Libplctag" } }, or the environment variableDrivers__AbCip__DefaultTransport=Libplctagon the service. Older builds ignore the section, so it can be staged ahead of the binaries. Every AbCip driver with notransportkey then starts on libplctag; the init log showstransport=Libplctag (node default). Move to Native later per driver (explicit"transport": "Native"in the new AdminUI) or for the node (remove the key / setNative, then restart). ⚠️ Do not rely on adding"transport": "Libplctag"to driver configs through the old AdminUI before upgrading: its typed AbCip form has no Transport field and drops unknown keys on save (#576), and on a fusedadmin,drivernode the AdminUI and drivers upgrade together, so there is no window. The node key works on every node shape, including fused nodes and driver-only nodes booting from cache. - Evidence, and its limits: AbCip reads (plus browse and templates) were proven on a production
CompactLogix 5069-L320ERS2 (Z-35162, read-only, 2026-10-08; see
gate results §Real press). AbCip writes are
simulator-proven only (
ab_server). - AbLegacy is different: its default stays libplctag and Native is opt-in per driver; the native PCCC
path has wire evidence (on
ab_server) only for N-file reads/writes and one F8 read (see AbLegacy.md §Transport).
Native transport behaviour
- One CIP connection and one request scheduler per device (
DeviceSessionPool), shared by reads, writes, browse and template reads. The Multiple Service Packet scheduler coalesces requests with one request in flight; large reads (listing pages, Read Template) are sent unpacked and exclusive. Packing budgets the expected reply as well as the request (#582): each queued request declares an upper bound on its reply (expectedReplyBytes; reads: elements x element width, STRING = 88 bytes per element, BOOL counted as 4) and a batch is closed when the summed MSP reply (6 + 2n + sum) would exceed the connection size. A read whose size cannot be bounded (structure / unknown authored type) is sent alone; writes and status-only replies count their 4-byte header. Pinned byRequestSchedulerTests.Mixed_scalar_string_and_array_replies_are_packed_within_the_reply_budget. ⚠️ RESIDUAL: mixed STRING/array packing has not been exercised against a real controller (the real-press gate predates the budget); the budget is unit-tested against the scheduler and fake channel only. - Fragmented-read integrity (#567):
Read Tag Fragmentedreplies are compared against the first reply; a changed type code or structure handle mid-read fails the read withBadReplyrather than stitching two types into one value. - Forward Open throttle: at most one attempt in flight, at least 1 s between starts, bounded by the open budget.
- A target-closed CIP connection is recycled at once (#566). When a connected reply says the controller
no longer holds the class-3 connection while TCP stays up — general status
0x01with extended0x0107(target connection not found) or0x0203(connection timed out), e.g. after a controller restart or a connection timeout — the session is closed (UnRegisterSession; no Forward Close, there is nothing to close) and the next request reopens through the throttle. The request that got the reply failsBadCommunicationError(transportBadConnection); a keep-alive that gets it recycles the connection before any request fails. Every other status — tag-level errors, other0x01extended codes — is left to the request. ⚠️ RESIDUAL: which of the two codes a real Logix controller returns for a forgotten connection (and whether it answers at all rather than dropping TCP) is unobserved; the check is correct whichever it does — a silent target still faults the session through the exchange timeout. ConnectionSize/Timeout/AllowPackingare honoured per pooled connection, and the first driver/device to open a given device key wins — including a Test Connect probe on a fusedadmin,drivernode (its connection carries the probe timeout). A later opener with different options is ignored and logged once as a Warning (DeviceSessionPool). ⚠️ The device key compares the host string, so the same controller addressed by DNS name in one driver and by IP in another gets two connections and two Forward Open throttles (up to two opens per second); address a controller the same way everywhere. ControlLogix, GuardLogix and (since T21) CompactLogix default to 4002, a Large Forward Open (0x5B), the same as libplctag. A target that refuses Large gets one regular open at min(size, 504) inside the same throttled attempt. An explicitConnectionSizein the options or on the device overrides the family default.- Routing: Micro800 is connected with an empty route regardless of
UseConnectedMessaging. SLC500/MicroLogix/PLC-5 over this driver are direct.logixpcccuses UnconnectedSend; its SLC framing is unverified. - ⚠️ Type check (client-visible change). The native path compares the type code the controller returns
with the authored
DataTypeand reportsBadTypeMismatchon disagreement. libplctag never checks it, so a same-width mis-authored tag read as Good garbage: authoring a tag asDINTwhile the controller holds aREALreturns the REAL's bits as an integer with a Good status under libplctag, andBadTypeMismatchnatively. That is the fix working, but a consumer will see Bad quality on tags that previously looked healthy: correct the authored type. Same-width signed/unsigned pairs are exempt, and writes are gated on a mismatch too. A mismatch is a deterministic configuration refusal, handled like an Unsupported refusal (final review I4): the tag's handle is kept (no re-create, no reconnect), driver health is unchanged (noDegraded, nothing fed to the comms-loss watchdog), and the Warning is logged once per tag per driver instance, not every poll. The same applies to the libplctag-path width check. The same holds when the controller refuses the existence read itself with a type error (CIP0xFF/0x2107): initialization completes with the status instead of throwing, so the runtime is not disposed and re-created (nor, for a sole lease holder, re-Forward-Opened) on every poll, and the device's connect backoff is not opened (#570). Micro800BYTE/WORD/LWORD(0xD1/0xD2/0xD4) are checked as integers of their width: aREAL/LREALor a narrower integer authored over anLWORDisBadTypeMismatch, not decoded garbage (#570). - A malformed tag name is a per-tag configuration error (#570). A
TagPaththat does not parse, or a name the CIP symbolic encoder refuses (non-ASCII, an empty member such asA..B, a member longer than 255 characters, an unterminated or non-numeric subscript), reads and writesBadConfigurationErrorwith one Warning per tag. Nothing reaches the device, so it never opens the device's connect backoff and never degrades driver health — healthy tags on the same device keep reading. (libplctag still reports its ownErrorBadParamfor a name it rejects.) A malformed probe tag does not feed the backoff either. - STRING capacity: the built-in Logix
STRINGis 88 bytes on the wire —LEN+DATA[82]+ 2 bytes of alignment padding — so a write holds at most 82 characters (it used to allow 84) and a read never returns the padding as characters. The write still sends the whole 88-byte structure, padding zeroed, as libplctag does. A user string type of any other size keeps the buffer-derived capacity (size − 4): the read alone cannot tell itsDATAlength from up to 3 bytes of padding, so a write may accept up to 3 characters more than the type holds (#570). - Releasing a tag never blocks (#579). Disposing a native tag runtime — the driver does it under the
tag's lock on an evict, a reinitialize or a shutdown — releases its connection lease in the background
(
ConnectionLease.ReleaseInBackground, the same shape the native AbLegacy runtime uses). It used to wait up to 2 s for the last lease's Forward Close. Nothing is lost by not waiting: the pool records the close synchronously, so a re-create the next instant still does not open a second session until that Forward Close + UnRegisterSession have finished, and the close is bounded by the connection's own budgets (the open budget for an open still in flight, 1 s for the Forward Close), so a connection is always released. Offline soak:NativeAbCipLeaseReleaseTests(25 create/release cycles, no leaked connection); a soak againstab_serverhas not been run. - A refused operation is not a comms fault. Any operation a runtime refuses as Unsupported (in AbCip, e.g.
a native write whose type cannot be determined) reaches the client as
BadNotSupported, keeps the tag handle, and leaves driver health unchanged; only real transport failures evict and degrade.
Known gaps
- ⚠️ Native writes are verified against
ab_serveronly (simulator-only), never a real controller. The real-press gate (Task 21) was read-only: it proved native reads, browse and templates on Z-35162 (2026-10-08) and nothing else. Results: native-ab-transport-gate-results. - libplctag cannot be deleted until a bench controller allows write verification.
- ⚠️ RESIDUAL (#567): wide-struct fragmented writes (8-byte alignment) are unit-tested only. Production presses are read-only and there is no bench controller, so this cannot be proven; it stays open until a bench controller exists.
- Native browse (#572, resolved in code): listing paging no longer assumes ascending instance order, pages
are paced, and a browse's template reads share one lease. One residual: whether a real controller ever
lists a page out of order is unobserved — the reader is now correct either way.
browsePageDelayMsis an AdminUI driver-form field ("Browse page delay (ms)", #596); keys the form does not model are preserved on save (#576). - Micro800, routed and
logixpcccpaths are covered byab_serveronly. The Micro800 profile passes natively. The AbLegacy default excludeslogixpccc(and PLC-5). - Follow-up issues for this workstream: #564 to #577.
- Fixed along the way (pre-existing on master):
ab://host:44818/with an empty CIP path (Micro800, unrouted MicroLogix) failed on libplctag withErrorBadDatabecause the adapter sentPath=""; it now sends no path.
Alarm Projection
IAlarmSource is served by AbCipAlarmProjection, which polls each subscribed
ALMD UDT's InFaulted + Severity members at AlarmPollInterval and fires
OnAlarmEvent on raise/clear transitions. It is ALMD-only in this pass (ALMA
analog alarms are a follow-up) and disabled by default — shops running FT
Alarm & Events should keep it off and take alarms through the native route, since
the projection semantics don't exactly mirror Rockwell FT A&E.
Testing
- Unit tests —
tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests/cover the driver, host-address parser, UDT planner, and alarm projection via fake tag runtimes. - Integration tests —
tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbCip.IntegrationTests/run against theab_serverDocker fixture. See AbServer-Test-Fixture.md for the coverage map and theAB_SERVER_ENDPOINTwiring. - Manual client — Driver.AbCip.Cli.md.
1-D array support
An AB CIP tag becomes a 1-D OPC UA array node when its TagConfig JSON carries
"isArray": true and "arrayLength": N (N ≥ 1). The canonical rule:
isArray: true + arrayLength >= 1 → array; isArray: false (any length) → scalar.
Read mechanism — the driver delegates to libplctag's native array read. The tag's
TagPath is passed to libplctag as a [N]-subscripted symbol (or the tag is created with
an element count of N so libplctag fetches the full block in one EIP/CIP request). Both
atomic types (DINT[N], REAL[N], …) and UDT member arrays are supported.
Unit test coverage — tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests/ covers
array reads via the fake tag runtime for atomic and UDT member cases. The ab_server
integration fixture is down during normal dev (Docker host fixture currently offline).
Live-verify — integration-fixture-gated (requires ab_server Docker fixture on 10.100.0.35:44818).
Deferrals — array writes, multi-dimensional arrays, per-element historization. Safety-partition array tags (SafetyTag: true) are excluded (GuardLogix write constraints extend to array writes).
See Uns.md §Array tags for the cross-driver coverage matrix and the UI authoring flow.
Native browse: paging, pacing and template leases
Native symbol browse (transport = Native; libplctag pages inside its own library and is unaffected):
- Paging continues past the highest instance seen, not the last entry of a page. The Symbol Object
listing is requested from
start; the next request starts atmax(instance in the reply) + 1, so the order a controller lists a page in does not matter. A "more" reply whose highest instance is still below itsstart(or equalsuint.MaxValue) made no progress and fails withBadReply("made no progress") rather than looping against the controller. - Pages are paced.
browsePageDelayMs(driver config, default 5,0= back-to-back, negative =0) pauses before every page after the first. 5 ms is small against a page's own round-trip, so a 50k-symbol browse gains a few seconds, but it breaks the back-to-back burst (one request in flight, roughly a Studio 5000 online browse) into slices the controller's message processing can interleave with. Raise it for a controller that is tight on CPU; the pause applies per listing (the controller listing and each program listing). - Template reads in a browse share one lease.
DiscoverAsyncreads the UDT templates (and nested templates) of a device through a single batch reader (IAbCipTemplateReaderFactory.CreateBatch); the native batch reader holds one device lease from its first read until the browse of that device ends, instead of leasing per template.FetchUdtShapeAsyncoutside a discovery run is unchanged: one self-contained lease per call.
Controller-discovered UDT member variables
When EnableControllerBrowse is set, the driver walks the controller's @tags symbol table and
surfaces each UDT-typed tag's atomic member leaves as individually addressable OPC UA
Variables — in addition to the UDT container tag itself.
What is discovered
-
Top-level UDT members — the Template Object for each controller-browse UDT is fetched via its template instance ID; each atomic member (BOOL, SINT, INT, DINT, REAL, …) becomes a separate Variable node under the UDT's
Discovered/sub-folder, addressable by its member path (e.g.MyUdt.Temperature,MyUdt.Flags). Top-level atomic member discovery is functional in production. -
Nested struct members — shipped (commits
3d8ce4e8/d203f31c). When a UDT member is itself a struct, the Template Object member block carries the nested UDT's template instance ID in the low 12 bits of the memberinfofield (struct flag0x8000set). The driver captures this asAbCipUdtMember.NestedTemplateIdand threads it into a secondFetchUdtShapeAsynccall (@udt/{id}) so the nested struct's atomic leaves are expanded into dot-joined addressable paths (e.g.Motor1.Status.Code,Motor1.Status.Running). Recursion is bounded by a depth cap of 8 levels; members at or beyond the cap are dropped rather than emitted. Nested struct leaves that resolve to no emittable atomic leaf produce no sub-folder (lazy materialisation).ab_server(the default Docker simulator) does not implement the CIP Template Object service (class 0x6C), so the fixture cannot exercise it; seetests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbCip.IntegrationTests/Emulate/AbCipEmulateNestedUdtTests.csfor the skip-gated Emulate smoke (backlog #6). -
STRING tags and members — a controller reports every STRING (built-in, or a user string type such as
STR0016) as aLENDINT +DATASINT[n] struct. Discovery recognises that shape and emits one String variable, top-level or nested, instead of a LEN/DATA folder. -
Hidden members are skipped — the
ZZZZZZZZZZ…hosts Logix packs BOOL members into and__…AOI backing members are not browsed (a user name can never start with__). -
Arrays — the Symbol Object's dimension bits populate
IsArray/ElementCount(multi-dim flattened). An array of a UDT is emitted as one variable, not fanned out (Tag.Membernames no element); an array of STRING is a String array. -
Program scope —
@tagslists each program (Program:Main) but none of its tags; the enumerator reads everyProgram:<name>.@tagslisting too, so program-scoped tags appear asProgram:<name>.<tag>. One unreadable program listing is skipped, not fatal.
Real-controller verification (2026-10-07)
Run read-only against production CompactLogix 5069-L320ERS2 rev 34.11 presses (and a second
CompactLogix) from the Mac over VPN. Before the fixes above, every real @udt/<id> buffer
decoded to null (the decoder assumed a layout no controller sends — the test builders shared
the assumption, the #468 trap), program-scoped tags were absent, and arrays browsed as scalars.
After them, one browse of a press took ~30 s and produced 23,412 variables covering all 80
tags the Ignition project reads on it, with matching types. The template and symbol layouts are
pinned by bytes captured off those controllers: CipTemplateObjectWireCaptureTests,
CipSymbolObjectRealControllerCaptureTests, AbCipProgramScopeEnumerationTests.
Bare-container reads
Reading the UDT container tag itself (without a member suffix) returns
BadNotSupported — address the atomic member leaves instead.
Member writes
UDT member writes discovered via controller browse are deferred in this release.
Pre-declared Members with Writable: true retain full read/write support as before.
Configuration
No new configuration keys are required. Set EnableControllerBrowse: true in the
AbCipDriverOptions JSON to enable the @tags walk; UDT member expansion is automatic for all
UDT-typed tags found in the walk.
Operational Notes
- Native heap is invisible to the GC. libplctag's native
Tagheap does not show up in CLR allocation figures. Watch whole-process RSS, and useReinitializeAsync(tears down + re-creates every device's libplctag handles) as the remediation for native-heap growth. (There is no per-driver footprint number to consult:IDriver.GetMemoryFootprint()was deleted as unconsumed in Gitea #525.) - Handle eviction on failure — a non-zero libplctag status or a transport exception evicts the cached tag runtime so the next read/write re-creates a fresh handle, mirroring the probe loop's recreate-on-failure behaviour.
- Read statuses carry the libplctag cause — a tag the controller does not have reads
BadNodeIdUnknown(notBadCommunicationError), and it does not open the device's connect-backoff window (the controller answered; before this, one typo throttled every sibling tag on the device). A genuine connection failure still opens it. - Width check on scalar reads — libplctag never checks the CIP type the controller returns. A scalar atomic read whose buffer is not the authored type's width (e.g. a REAL authored as INT — the legacy Kepware export does exactly this for some press tags) reads
BadTypeMismatchinstead of Good garbage. Same-width mistakes (DINT vs REAL) are undetectable under libplctag; theNativetransport reports them asBadTypeMismatch(see Native transport behaviour). The width-mismatch refusal is pinned byAbCipTypeMismatchTests.A_width_mismatched_read_keeps_the_handle_leaves_health_alone_and_warns_once:BadTypeMismatch, handle kept, noDegraded, one Warning per tag. Benign edge (#585): a driver leftDegradedby an earlier outage whose only remaining tags are mis-typed gets one extra comms-loss-watchdog reconnect ~90 s later before settling, because a type refusal deliberately writes no health and so never clears the staleDegraded. - Module-defined I/O tags —
Local:1:I.Data,ABB_OmniCore:I.ConnectionFaultedand similar colon-bearing base names are valid tag paths (controller scope only). - User string arrays —
STR0016[N]and similar arrays stride by the actual element size (read buffer ÷ count); libplctag.NET 1.5.2 leavesElementSizeunset after a read. - Declaration-only UDT grouping is a footgun unless verified — only enable
EnableDeclarationOnlyUdtGroupingwhen every UDT's member declaration order has been hand-verified against the controller's compiled layout.