b61f3e0560
v2-ci / unit-tests (push) Has been cancelled
GalaxyAlarmPriority, the one table live Galaxy alarms (MxAccessSeverityMapper) and AVEVA A&E history (EventMapper, #886) map the AVEVA priority through, ranked a higher number as more severe. AVEVA ranks priority 1 as the most urgent, so a priority-1 alarm read 250 and a priority-999 system event 1000. It now uses AVEVA's default priority ranges, most urgent first: AVEVA priority AVEVA severity bucket OPC UA Severity 1-250 1 Critical Critical 1000 251-500 2 High High 750 501-750 3 Medium Medium 500 751-999 4 Low Low 250 (history only) 0 not an alarm - 1 Out-of-range priorities clamp (<= 0 Critical, > 999 Low). Evidence, vd03 Runtime.dbo.Events read-only: priority 1/100 alarms carry AVEVA severity 1, 400/500 severity 2, 600/700 severity 3, and every priority-999 System.* / User.* row severity 0 with IsAlarm 0. - Live and history now use the same number. GalaxyDriver passes the table's exact value as AlarmEventArgs.OpcUaSeverity. Before, it passed only the bucket, which NativeAlarmProjector re-mapped through its generic 200/500/700/900 ladder, so live and history disagreed even before the direction fix. - History: a row whose AVEVA severity is 0 (System.Start/Stop/Deploy, User.Write...) is not an alarm and reads Severity 1, below every alarm band. For alarms AVEVA's 1-4 severity is still never the value: the live feed carries only the priority, so it cannot use it, and history must agree. - Docs: docs/Historian.md gains "Galaxy alarm priority -> Severity (lmxopcua#887)"; docs/AlarmTracking.md updated. - Live re-run of the #801/#886 harness against vd03 HistorianGateway ea9f21c (read-only, network-only): 224 of 233 cases identical to the #886 run, the 9 others differ only in Severity (priority-700 alarm rows 750 -> 500, 19 system/user events 1000 -> 1). Record: aveva-history-801.md "#887 re-run", report aveva-gate-sdk2-887.json.gz. Client-visible: every OPC UA client that ranks or filters Galaxy alarms by Severity sees the order reversed (live and HistoryReadEvents). ScadaBridge has no code that depends on the old values; its own mixed severity directions are ScadaBridge#129. Tests updated because they pinned the inverted table: - Driver.Galaxy.Tests MxAccessSeverityMapperTests (rewritten: edges 1/250/251/ 500/501/750/751/999, 0/-100/int.MinValue/1000/int.MaxValue clamps, monotonic-decreasing sweep, equals GalaxyAlarmPriority for -2..1001) - Driver.Galaxy.Tests GatewayGalaxyAlarmFeedTests (750 and 600 -> Medium) - Driver.Historian.Gateway.Tests EventMapperTests (band table, priority 999 -> 250, 1 -> 1000; system events -> 1) - OpcUaServer.IntegrationTests GalaxyEquipmentEventHistoryWireTests (700 -> 500, 100 -> 1000, System.Stop -> 1; the fake now stores AVEVA's real 0-4 severity) New tests: - Runtime.Tests NativeAlarmRestatementEndToEndTests .Galaxy_live_condition_severity_is_the_AVEVA_priority_band (8 rows: the real feed -> real GalaxyDriver -> host -> projector; the same rows EventMapperTests pins on the history path) - EventMapperTests.Aveva_severity_zero_marks_an_event_that_is_not_an_alarm (5 rows, incl. the priority-999 alarm positive control) - GalaxyDriverAlarmSourceTests: OpcUaSeverity passes through Mutation check, 8 mutants, all killed: the pre-#887 inverted table; the driver dropping OpcUaSeverity; no not-an-alarm rule; each of the three band edges off by one; history ignoring priority; a missing AVEVA severity read as 0. Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi