Joseph Doherty c14624f012 Phase 2 PR 14 — alarm subsystem wire-up. Per IsAlarm=true attribute (PR 9 added the discovery flag), GalaxyAlarmTracker in Backend/Alarms/ advises the four Galaxy alarm-state attributes: .InAlarm (boolean alarm active), .Priority (int severity), .DescAttrName (human-readable description), .Acked (boolean acknowledged). Runs the OPC UA Part 9 alarm lifecycle state machine simplified for the Galaxy AlarmExtension model and raises AlarmTransition events on transitions operators must react to — Active (InAlarm false→true, default Unacknowledged), Acknowledged (Acked false→true while InAlarm still true), Inactive (InAlarm true→false). MxAccessGalaxyBackend instantiates the tracker in its constructor with delegate-based subscribe/unsubscribe/write pointers to MxAccessClient, hooks TransitionRaised to forward each transition through the existing OnAlarmEvent IPC event that PR 4 ConnectionSink wires into MessageKind.AlarmEvent frames — no new contract messages required since GalaxyAlarmEvent already exists in Shared.Contracts. Field mapping: EventId = fresh Guid.ToString('N') per transition, ObjectTagName = alarm attribute full reference, AlarmName = alarm attribute full reference, Severity = tracked Priority, StateTransition = 'Active'|'Acknowledged'|'Inactive', Message = DescAttrName or tag fallback, UtcUnixMs = transition time. DiscoverAsync caches every IsAlarm=true attribute's full reference (tag.attribute) into _discoveredAlarmTags (ConcurrentBag cleared-then-filled on every re-Discover to track Galaxy redeploys). SubscribeAlarmsAsync iterates the cache and advises each via GalaxyAlarmTracker.TrackAsync; best-effort per-alarm — a subscribe failure on one alarm doesn't abort the whole call since operators prefer partial alarm coverage to none. Tracker is internally idempotent on repeat Track calls (second invocation for same alarm tag is a no-op; already-subscribed check short-circuits before the 4 MXAccess sub calls). Subscribe-failure rollback inside TrackAsync removes the alarm state + unadvises any of the 4 that did succeed so a partial advise can't leak a phantom tracking entry. AcknowledgeAlarmAsync routes to tracker.AcknowledgeAsync which writes the operator comment to <tag>.AckMsg via MxAccessClient.WriteAsync — writes use the existing MXAccess OnWriteComplete TCS-by-handle path (PR 4 Medium 4) so a runtime-refused ack bubbles up as Success=false rather than false-positive. State-machine quirks preserved from v1: (1) initial Acked=true on subscribe does NOT fire Acknowledged (alarm at rest, pre-acknowledged — default state is Acked=true so the first subscribe callback is a no-op transition), (2) Acked false→true only fires Acknowledged when InAlarm is currently true (acking a latched-inactive alarm is not a user-visible transition), (3) Active transition clears the Acked flag in-state so the next Acked callback correctly fires Acknowledged (v1 had this buried in the ConditionState logic; we track it on the AlarmState struct directly). Priority value handled as int/short/long via type pattern match with int.MaxValue guard — Galaxy attribute category returns varying CLR types (Int32 is canonical but some older templates use Int16), and a long overflow cast to int would silently corrupt the severity. Dispose cascade in MxAccessGalaxyBackend.Dispose: alarm-tracker unsubscribe→dispose, probe-manager unsubscribe→dispose, mx.ConnectionStateChanged detach, historian dispose — same discipline PR 6 / PR 8 / PR 13 established so dangling invocation-list refs don't survive a backend recycle. #pragma warning disable CS0067 around OnAlarmEvent removed since the event is now raised. Tests (9 new, GalaxyAlarmTrackerTests): four-attribute subscribe per alarm, idempotent repeat-track, InAlarm false→true fires Active with Priority + Desc, InAlarm true→false fires Inactive, Acked false→true while InAlarm fires Acknowledged, Acked transition while InAlarm=false does not fire, AckMsg write path carries the comment, snapshot reports latest four fields, foreign probe callback for a non-tracked tag is silently dropped. Full Galaxy.Host.Tests Unit suite 84 pass / 0 fail (9 new alarm + 12 PR 13 probe + 21 PR 12 quality + 42 pre-existing). Galaxy.Host builds clean (0/0). Branches off phase-2-pr13-runtime-probe so the MxAccessGalaxyBackend constructor/Dispose chain gets the probe-manager + alarm-tracker wire-up in a coherent order; fast-forwards if PR 13 merges first.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-18 07:34:13 -04:00
..
Phase 2 PR 14 — alarm subsystem wire-up. Per IsAlarm=true attribute (PR 9 added the discovery flag), GalaxyAlarmTracker in Backend/Alarms/ advises the four Galaxy alarm-state attributes: .InAlarm (boolean alarm active), .Priority (int severity), .DescAttrName (human-readable description), .Acked (boolean acknowledged). Runs the OPC UA Part 9 alarm lifecycle state machine simplified for the Galaxy AlarmExtension model and raises AlarmTransition events on transitions operators must react to — Active (InAlarm false→true, default Unacknowledged), Acknowledged (Acked false→true while InAlarm still true), Inactive (InAlarm true→false). MxAccessGalaxyBackend instantiates the tracker in its constructor with delegate-based subscribe/unsubscribe/write pointers to MxAccessClient, hooks TransitionRaised to forward each transition through the existing OnAlarmEvent IPC event that PR 4 ConnectionSink wires into MessageKind.AlarmEvent frames — no new contract messages required since GalaxyAlarmEvent already exists in Shared.Contracts. Field mapping: EventId = fresh Guid.ToString('N') per transition, ObjectTagName = alarm attribute full reference, AlarmName = alarm attribute full reference, Severity = tracked Priority, StateTransition = 'Active'|'Acknowledged'|'Inactive', Message = DescAttrName or tag fallback, UtcUnixMs = transition time. DiscoverAsync caches every IsAlarm=true attribute's full reference (tag.attribute) into _discoveredAlarmTags (ConcurrentBag cleared-then-filled on every re-Discover to track Galaxy redeploys). SubscribeAlarmsAsync iterates the cache and advises each via GalaxyAlarmTracker.TrackAsync; best-effort per-alarm — a subscribe failure on one alarm doesn't abort the whole call since operators prefer partial alarm coverage to none. Tracker is internally idempotent on repeat Track calls (second invocation for same alarm tag is a no-op; already-subscribed check short-circuits before the 4 MXAccess sub calls). Subscribe-failure rollback inside TrackAsync removes the alarm state + unadvises any of the 4 that did succeed so a partial advise can't leak a phantom tracking entry. AcknowledgeAlarmAsync routes to tracker.AcknowledgeAsync which writes the operator comment to <tag>.AckMsg via MxAccessClient.WriteAsync — writes use the existing MXAccess OnWriteComplete TCS-by-handle path (PR 4 Medium 4) so a runtime-refused ack bubbles up as Success=false rather than false-positive. State-machine quirks preserved from v1: (1) initial Acked=true on subscribe does NOT fire Acknowledged (alarm at rest, pre-acknowledged — default state is Acked=true so the first subscribe callback is a no-op transition), (2) Acked false→true only fires Acknowledged when InAlarm is currently true (acking a latched-inactive alarm is not a user-visible transition), (3) Active transition clears the Acked flag in-state so the next Acked callback correctly fires Acknowledged (v1 had this buried in the ConditionState logic; we track it on the AlarmState struct directly). Priority value handled as int/short/long via type pattern match with int.MaxValue guard — Galaxy attribute category returns varying CLR types (Int32 is canonical but some older templates use Int16), and a long overflow cast to int would silently corrupt the severity. Dispose cascade in MxAccessGalaxyBackend.Dispose: alarm-tracker unsubscribe→dispose, probe-manager unsubscribe→dispose, mx.ConnectionStateChanged detach, historian dispose — same discipline PR 6 / PR 8 / PR 13 established so dangling invocation-list refs don't survive a backend recycle. #pragma warning disable CS0067 around OnAlarmEvent removed since the event is now raised. Tests (9 new, GalaxyAlarmTrackerTests): four-attribute subscribe per alarm, idempotent repeat-track, InAlarm false→true fires Active with Priority + Desc, InAlarm true→false fires Inactive, Acked false→true while InAlarm fires Acknowledged, Acked transition while InAlarm=false does not fire, AckMsg write path carries the comment, snapshot reports latest four fields, foreign probe callback for a non-tracked tag is silently dropped. Full Galaxy.Host.Tests Unit suite 84 pass / 0 fail (9 new alarm + 12 PR 13 probe + 21 PR 12 quality + 42 pre-existing). Galaxy.Host builds clean (0/0). Branches off phase-2-pr13-runtime-probe so the MxAccessGalaxyBackend constructor/Dispose chain gets the probe-manager + alarm-tracker wire-up in a coherent order; fast-forwards if PR 13 merges first.
2026-04-18 07:34:13 -04:00
Phase 2 — port GalaxyRepository to Galaxy.Host + DbBackedGalaxyBackend, smoke-tested against live ZB. Real Galaxy gobject hierarchy + dynamic attributes now flow through the IPC contract end-to-end without any MXAccess code involvement, so the OPC UA address-space build (Stream C.4 acceptance) becomes parity-testable today even before the COM client port lands. Backend/Galaxy/GalaxyRepository.cs is a byte-for-byte port of v1 GalaxyRepositoryService's HierarchySql + AttributesSql (the two SQL bodies, both ~50 lines of recursive CTE template-chain + deployed_package_chain logic, are identical to v1 so the row set is verifiably the same — extended-attributes + scope-filter queries from v1 are intentionally not ported yet, they're refinements not on the Phase 2 critical path); plus TestConnectionAsync (SELECT 1) and GetLastDeployTimeAsync (SELECT time_of_last_deploy FROM galaxy) for the ChangeDetection deploy-watermark path. Backend/Galaxy/GalaxyRepositoryOptions defaults to localhost ZB Integrated Security; runtime override comes from DriverConfig.Database section per plan.md §"Galaxy DriverConfig". Backend/Galaxy/GalaxyHierarchyRow + GalaxyAttributeRow are the row-shape DTOs (no required modifier — net48 lacks RequiredMemberAttribute and we'd need a polyfill shim like the existing IsExternalInit one; default-string init is simpler). System.Data.SqlClient 4.9.0 added (the same package the v1 Host uses; net48-compatible). Backend/DbBackedGalaxyBackend wraps the repository: DiscoverAsync builds a real DiscoverHierarchyResponse (groups attributes by gobject, resolves parent-by-tagname, maps category_id → human-readable template-category name mirroring v1 AlarmObjectFilter); ReadValuesAsync/WriteValuesAsync/HistoryReadAsync still surface "MXAccess code lift pending (Phase 2 Task B.1)" because runtime data values genuinely need the COM client; OpenSession/CloseSession/Subscribe/Unsubscribe/AlarmSubscribe/AlarmAck/Recycle return success without backend work (subscription ID is a synthetic counter for now). Live smoke tests (GalaxyRepositoryLiveSmokeTests) skip when localhost ZB is unreachable; when present they verify (1) TestConnection returns true, (2) GetHierarchy returns at least one deployed gobject with a non-empty TagName, (3) GetAttributes returns rows with FullTagReference matching the "tag.attribute" shape, (4) GetLastDeployTime returns a value, (5) DbBackedBackend.DiscoverAsync returns at least one gobject with attributes and a populated TemplateCategory. All 5 pass against the local Galaxy. Full solution 957 pass / 1 pre-existing Phase 0 baseline; the 494 v1 IntegrationTests + 6 v1 IntegrationTests-net48 tests still pass — legacy OtOpcUa.Host untouched. Remaining for the Phase 2 exit gate is the MXAccess COM client port itself (the v1 MxAccessClient partials + IMxProxy abstraction + StaPump-based Connect/Subscribe/Read/Write semantics) — Discover is now solved in DB-backed form, so the lift can focus exclusively on the runtime data-plane.
2026-04-17 23:14:09 -04:00
Phase 2 PR 12 — richer historian quality mapping. Replace MxAccessGalaxyBackend's inline MapHistorianQualityToOpcUa category-only helper (192+→Good, 64-191→Uncertain, 0-63→Bad) with a new public HistorianQualityMapper.Map utility that preserves specific OPC DA subcodes — BadNotConnected(8)→0x808A0000u instead of generic Bad(0x80000000u), UncertainSubNormal(88)→0x40950000u instead of generic Uncertain, Good_LocalOverride(216)→0x00D80000u instead of generic Good, etc. Mirrors v1 QualityMapper.MapToOpcUaStatusCode byte-for-byte without pulling in OPC UA types — the function returns uint32 literals that are the canonical OPC UA StatusCode wire encoding, surfaced directly as DataValueSnapshot.StatusCode on the Proxy side with no additional translation. Unknown subcodes fall back to the family category (255→Good, 150→Uncertain, 50→Bad) so a future SDK change that adds a quality code we don't map yet still gets a sensible bucket. GalaxyDataValue wire shape unchanged (StatusCode stays uint) — this is a pure fidelity upgrade on the Host side. Downstream callers (Admin UI status dashboard, OPC UA clients receiving historian samples) can now distinguish e.g. a transport outage (BadNotConnected) from a sensor fault (BadSensorFailure) from a warm-up delay (BadWaitingForInitialData) without a second round-trip or dashboard heuristic. 21 new tests (HistorianQualityMapperTests): theory with 15 rows covering every specific mapping from the v1 QualityMapper table, plus 6 fallback tests verifying unknown-subcode codes in each family (Good/Uncertain/Bad) collapse to the family default. Galaxy.Host.Tests Unit suite 56/0 (21 new + 35 existing). Galaxy.Host builds clean (0/0). Branches off v2.
2026-04-18 07:11:02 -04:00
Phase 2 PR 13 — port GalaxyRuntimeProbeManager state machine + wire per-platform ScanState probing. PR 8 gave operators the gateway-level transport signal (MxAccessClient.ConnectionStateChanged → OnHostStatusChanged tagged with the Wonderware client identity) — enough to detect when the entire MXAccess COM proxy dies, but silent when a specific or goes down while the gateway stays alive. This PR closes that gap: a pure-logic GalaxyRuntimeProbeManager (ported from v1's 472-LOC GalaxyRuntimeProbeManager.cs, distilled to ~240 LOC of state machine without the OPC UA node-manager entanglement) lives in Backend/Stability/, advises <TagName>.ScanState per WinPlatform + AppEngine gobject discovered during DiscoverAsync, runs the Unknown → Running → Stopped state machine with v1's documented semantics preserved verbatim, and raises a StateChanged event on transitions operators should react to. MxAccessGalaxyBackend instantiates the probe manager in the constructor with SubscribeAsync/UnsubscribeAsync delegate pointers into MxAccessClient, hooks StateChanged to forward each transition through the same OnHostStatusChanged IPC event the gateway signal uses (HostName = platform/engine TagName, RuntimeStatus = 'Running'|'Stopped'|'Unknown', LastObservedUtcUnixMs from the state-change timestamp), so Admin UI gets per-host signals flowing through the existing PR 8 wire with no additional IPC plumbing. State machine rules ported from v1 runtimestatus.md: (a) ScanState is on-change-only — a stably-Running host may go hours without a callback, so Running → Stopped is driven only by explicit ScanState=false, never by starvation; (b) Unknown → Running is a startup transition and does NOT fire StateChanged (would paint every host as 'just recovered' at startup, which is noise and can clear Bad quality set by a concurrently-stopping sibling); (c) Stopped → Running fires StateChanged for the real recovery case; (d) Running → Stopped fires StateChanged; (e) Unknown → Stopped fires StateChanged because that's the first-known-bad signal operators need when a host is down at our startup time. MxAccessGalaxyBackend.DiscoverAsync calls _probeManager.SyncAsync with the runtime-host subset of the hierarchy (CategoryId == 1 WinPlatform or 3 AppEngine) as a best-effort step after building the Discover response — probe failures are swallowed so Discover still returns the hierarchy even if a per-host advise fails; the gateway signal covers the critical rung. SyncAsync is idempotent (second call with the same set is a no-op) and handles the diff on re-Discover for tag rename / host add / host remove. Subscribe failure rolls back the host's state entry under the lock so a later probe callback for a never-advised tag can't transition a phantom state from Unknown to Stopped and fan out a false host-down signal (the same protection v1's GalaxyRuntimeProbeManager had at line 237-243 of v1 with a captured-probe-string comparison under the lock). MxAccessGalaxyBackend.Dispose unsubscribes the StateChanged handler before disposing the probe manager to prevent dangling invocation-list references across reconnects, same discipline as PR 8's ConnectionStateChanged and PR 6's SubscriptionReplayFailed. Tests (12 new GalaxyRuntimeProbeManagerTests): Sync_subscribes_to_ScanState_per_host verifies tag.ScanState subscriptions are advised per Platform/Engine; Sync_is_idempotent_on_repeat_call_with_same_set verifies no duplicate subscribes; Sync_unadvises_removed_hosts verifies the diff unadvises gone hosts; Subscribe_failure_rolls_back_host_entry_so_later_transitions_do_not_fire_stale_events covers the rollback-on-subscribe-fail guard; Unknown_to_Running_does_not_fire_StateChanged preserves the startup-noise rule; Running_to_Stopped_fires_StateChanged_with_both_states asserts OldState and NewState are both captured in the transition record; Stopped_to_Running_fires_StateChanged_for_recovery verifies the recovery case; Unknown_to_Stopped_fires_StateChanged_for_first_known_bad_signal preserves the first-bad rule; Repeated_Good_Running_callbacks_do_not_fire_duplicate_events verifies the state-tracking de-dup; Unknown_callback_for_non_tracked_probe_is_dropped asserts a foreign callback is silently ignored; Snapshot_reports_current_state_for_every_tracked_host covers the dashboard query hook; IsRuntimeHost_recognizes_WinPlatform_and_AppEngine_category_ids asserts the CategoryId filter. Galaxy.Host.Tests Unit suite 75 pass / 0 fail (12 new probe + 63 pre-existing). Galaxy.Host builds clean (0 errors / 0 warnings). Branches off v2.
2026-04-18 07:27:56 -04:00
Phase 2 PR 11 — HistoryReadEvents IPC (alarm history). New Shared.Contracts messages HistoryReadEventsRequest/Response + GalaxyHistoricalEvent DTO (MessageKind 0x66/0x67). IGalaxyBackend gains HistoryReadEventsAsync, Stub/DbBacked return canonical pending error, MxAccessGalaxyBackend delegates to _historian.ReadEventsAsync (ported in PR 5) and maps HistorianEventDto → GalaxyHistoricalEvent — Guid.ToString() for EventId wire shape, DateTime → Unix ms for both EventTime (when the event fired in the process) and ReceivedTime (when the Historian persisted it), DisplayText + Severity pass through. SourceName is string? — null means 'all sources' (passed straight through to HistorianDataSource.ReadEventsAsync which adds the AddEventFilter('Source', Equal, ...) only when non-null). Distinct from the live GalaxyAlarmEvent type because historical rows carry both timestamps and lack StateTransition (Historian logs instantaneous events, not the OPC UA Part 9 alarm lifecycle; translating to OPC UA event lifecycle is the alarm-subsystem's job). Guards: null historian → Historian-disabled error; SDK exception → Success=false with message chained. Tests (3 new): disabled-error when historian null, maps HistorianEventDto with full field set (Id/Source/EventTime/ReceivedTime/DisplayText/Severity=900) to GalaxyHistoricalEvent, null SourceName passes through unchanged (verifies the 'all sources' contract). Galaxy.Host.Tests Unit suite 34 pass / 0 fail. Galaxy.Host builds clean. Branches off phase-2-pr10-history-attime since both extend the MessageKind enum; fast-forwards if PR 10 merges first.
2026-04-18 07:08:16 -04:00
Phase 2 PR 11 — HistoryReadEvents IPC (alarm history). New Shared.Contracts messages HistoryReadEventsRequest/Response + GalaxyHistoricalEvent DTO (MessageKind 0x66/0x67). IGalaxyBackend gains HistoryReadEventsAsync, Stub/DbBacked return canonical pending error, MxAccessGalaxyBackend delegates to _historian.ReadEventsAsync (ported in PR 5) and maps HistorianEventDto → GalaxyHistoricalEvent — Guid.ToString() for EventId wire shape, DateTime → Unix ms for both EventTime (when the event fired in the process) and ReceivedTime (when the Historian persisted it), DisplayText + Severity pass through. SourceName is string? — null means 'all sources' (passed straight through to HistorianDataSource.ReadEventsAsync which adds the AddEventFilter('Source', Equal, ...) only when non-null). Distinct from the live GalaxyAlarmEvent type because historical rows carry both timestamps and lack StateTransition (Historian logs instantaneous events, not the OPC UA Part 9 alarm lifecycle; translating to OPC UA event lifecycle is the alarm-subsystem's job). Guards: null historian → Historian-disabled error; SDK exception → Success=false with message chained. Tests (3 new): disabled-error when historian null, maps HistorianEventDto with full field set (Id/Source/EventTime/ReceivedTime/DisplayText/Severity=900) to GalaxyHistoricalEvent, null SourceName passes through unchanged (verifies the 'all sources' contract). Galaxy.Host.Tests Unit suite 34 pass / 0 fail. Galaxy.Host builds clean. Branches off phase-2-pr10-history-attime since both extend the MessageKind enum; fast-forwards if PR 10 merges first.
2026-04-18 07:08:16 -04:00
Phase 2 PR 14 — alarm subsystem wire-up. Per IsAlarm=true attribute (PR 9 added the discovery flag), GalaxyAlarmTracker in Backend/Alarms/ advises the four Galaxy alarm-state attributes: .InAlarm (boolean alarm active), .Priority (int severity), .DescAttrName (human-readable description), .Acked (boolean acknowledged). Runs the OPC UA Part 9 alarm lifecycle state machine simplified for the Galaxy AlarmExtension model and raises AlarmTransition events on transitions operators must react to — Active (InAlarm false→true, default Unacknowledged), Acknowledged (Acked false→true while InAlarm still true), Inactive (InAlarm true→false). MxAccessGalaxyBackend instantiates the tracker in its constructor with delegate-based subscribe/unsubscribe/write pointers to MxAccessClient, hooks TransitionRaised to forward each transition through the existing OnAlarmEvent IPC event that PR 4 ConnectionSink wires into MessageKind.AlarmEvent frames — no new contract messages required since GalaxyAlarmEvent already exists in Shared.Contracts. Field mapping: EventId = fresh Guid.ToString('N') per transition, ObjectTagName = alarm attribute full reference, AlarmName = alarm attribute full reference, Severity = tracked Priority, StateTransition = 'Active'|'Acknowledged'|'Inactive', Message = DescAttrName or tag fallback, UtcUnixMs = transition time. DiscoverAsync caches every IsAlarm=true attribute's full reference (tag.attribute) into _discoveredAlarmTags (ConcurrentBag cleared-then-filled on every re-Discover to track Galaxy redeploys). SubscribeAlarmsAsync iterates the cache and advises each via GalaxyAlarmTracker.TrackAsync; best-effort per-alarm — a subscribe failure on one alarm doesn't abort the whole call since operators prefer partial alarm coverage to none. Tracker is internally idempotent on repeat Track calls (second invocation for same alarm tag is a no-op; already-subscribed check short-circuits before the 4 MXAccess sub calls). Subscribe-failure rollback inside TrackAsync removes the alarm state + unadvises any of the 4 that did succeed so a partial advise can't leak a phantom tracking entry. AcknowledgeAlarmAsync routes to tracker.AcknowledgeAsync which writes the operator comment to <tag>.AckMsg via MxAccessClient.WriteAsync — writes use the existing MXAccess OnWriteComplete TCS-by-handle path (PR 4 Medium 4) so a runtime-refused ack bubbles up as Success=false rather than false-positive. State-machine quirks preserved from v1: (1) initial Acked=true on subscribe does NOT fire Acknowledged (alarm at rest, pre-acknowledged — default state is Acked=true so the first subscribe callback is a no-op transition), (2) Acked false→true only fires Acknowledged when InAlarm is currently true (acking a latched-inactive alarm is not a user-visible transition), (3) Active transition clears the Acked flag in-state so the next Acked callback correctly fires Acknowledged (v1 had this buried in the ConditionState logic; we track it on the AlarmState struct directly). Priority value handled as int/short/long via type pattern match with int.MaxValue guard — Galaxy attribute category returns varying CLR types (Int32 is canonical but some older templates use Int16), and a long overflow cast to int would silently corrupt the severity. Dispose cascade in MxAccessGalaxyBackend.Dispose: alarm-tracker unsubscribe→dispose, probe-manager unsubscribe→dispose, mx.ConnectionStateChanged detach, historian dispose — same discipline PR 6 / PR 8 / PR 13 established so dangling invocation-list refs don't survive a backend recycle. #pragma warning disable CS0067 around OnAlarmEvent removed since the event is now raised. Tests (9 new, GalaxyAlarmTrackerTests): four-attribute subscribe per alarm, idempotent repeat-track, InAlarm false→true fires Active with Priority + Desc, InAlarm true→false fires Inactive, Acked false→true while InAlarm fires Acknowledged, Acked transition while InAlarm=false does not fire, AckMsg write path carries the comment, snapshot reports latest four fields, foreign probe callback for a non-tracked tag is silently dropped. Full Galaxy.Host.Tests Unit suite 84 pass / 0 fail (9 new alarm + 12 PR 13 probe + 21 PR 12 quality + 42 pre-existing). Galaxy.Host builds clean (0/0). Branches off phase-2-pr13-runtime-probe so the MxAccessGalaxyBackend constructor/Dispose chain gets the probe-manager + alarm-tracker wire-up in a coherent order; fast-forwards if PR 13 merges first.
2026-04-18 07:34:13 -04:00
Phase 2 PR 11 — HistoryReadEvents IPC (alarm history). New Shared.Contracts messages HistoryReadEventsRequest/Response + GalaxyHistoricalEvent DTO (MessageKind 0x66/0x67). IGalaxyBackend gains HistoryReadEventsAsync, Stub/DbBacked return canonical pending error, MxAccessGalaxyBackend delegates to _historian.ReadEventsAsync (ported in PR 5) and maps HistorianEventDto → GalaxyHistoricalEvent — Guid.ToString() for EventId wire shape, DateTime → Unix ms for both EventTime (when the event fired in the process) and ReceivedTime (when the Historian persisted it), DisplayText + Severity pass through. SourceName is string? — null means 'all sources' (passed straight through to HistorianDataSource.ReadEventsAsync which adds the AddEventFilter('Source', Equal, ...) only when non-null). Distinct from the live GalaxyAlarmEvent type because historical rows carry both timestamps and lack StateTransition (Historian logs instantaneous events, not the OPC UA Part 9 alarm lifecycle; translating to OPC UA event lifecycle is the alarm-subsystem's job). Guards: null historian → Historian-disabled error; SDK exception → Success=false with message chained. Tests (3 new): disabled-error when historian null, maps HistorianEventDto with full field set (Id/Source/EventTime/ReceivedTime/DisplayText/Severity=900) to GalaxyHistoricalEvent, null SourceName passes through unchanged (verifies the 'all sources' contract). Galaxy.Host.Tests Unit suite 34 pass / 0 fail. Galaxy.Host builds clean. Branches off phase-2-pr10-history-attime since both extend the MessageKind enum; fast-forwards if PR 10 merges first.
2026-04-18 07:08:16 -04:00