Files
lmxopcua/tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Ab.Transport.Tests/Captures/logix-forward-close.hex
T
Joseph Doherty 1201d5fcfb test(ab-transport): golden libplctag<->ab_server frame captures for Logix, Micro800 and PCCC
17 .hex fixtures captured from libplctag 1.5.2 (native 2.6.0) against
otopcua-ab-server:libplctag-release, plus the CaptureFile loader, its
length/alternation tests, and the re-runnable scripts/ab-capture/capture.sh.

Observed and recorded in Captures/README.md "Routing observed":
- Micro800 is NOT UCMM under libplctag 2.6.0: it opens a Large Forward Open
  (path 20 02 24 01) and reads connected; use_connected_msg=0 is ignored.
- SLC500/MicroLogix/PLC-5 send Execute PCCC 0x4B unconnected and unwrapped;
  a configured path=1,0 never reaches the wire.
- Only Large FO 0x5B was observed; no 0x54 fallback occurred.
- LogixPccc is unreachable against ab_server (CIP 0x08); no fixture committed.
2026-10-07 15:50:00 -04:00

10 lines
792 B
Plaintext

# logix-forward-close.hex
# client : libplctag 1.5.2 (libplctag.NET wrapper; libplctag.NativeImport 1.0.41, native core 2.6.0)
# server : otopcua-ab-server:libplctag-release (ab_server from libplctag v2.7.0 + patches 0001/0002)
# profile: controllogix
# tag : protocol=ab_eip&gateway=10.100.0.35:44818&path=1,0&plc=controllogix&name=TestDINT
# session: logix-read-dint (captured 2026-10-07, scripts/ab-capture/capture.sh)
# frames : Forward Close 0x4E request/reply (last two frames of the logix-read-dint session). No UnregisterSession followed.
> 6F002800F3A5081A00000000F0B223110000000000000000000000000100020000000000B20018004E02200624010A05B1723DF3454350210300010020022401
< 6F001E00F3A5081A00000000000000000000000000000000000000000100020000000000B2000E00CE000000B1723DF3454350210000