Files
lmxopcua/docs/featuregaps.md
2026-04-26 11:22:40 -04:00

2.0 KiB

Feature gaps — driver-side limitations and decisions

Cross-driver registry of known capability gaps, the workaround we ship, and whether the gap is on the roadmap. Each row links to the driver-specific deep-dive document. Closed entries stay in the table for traceability — they are not deleted, only marked.

# Driver Gap Status Workaround / decision Roadmap Reference
1 S7 Optimized DB / S7Plus — S7netplus speaks classic S7comm only and cannot read S7-1200 / S7-1500 DBs that have "Optimized block access" checked (the TIA Portal V14+ default). Absolute-offset reads against an Optimized DB return BadDeviceFailure. Decided — Track 1 + Track 3 (closed by #304) Track 1 (docs): operators uncheck "Optimized block access" in TIA Portal on every DB the driver reads, recompile, and download. Track 3 (bridge): for shops that won't or can't disable Optimized access, run an OpcUaClient driver instance against the S7-1500 V2.5+ CPU's onboard OPC UA server (Siemens runtime OPC UA license required). Track 2 (custom S7Plus library) is out of scope unless a customer funds the ≥4-week initial implementation plus ongoing protocol-revision maintenance. Sharp7 / Snap7Net don't help — they are also classic-S7comm-only. docs/v2/s7.md § Optimized DB constraint · docs/drivers/OpcUaClient.md

How to read this table

  • Status is one of Open (work pending), Decided (architectural decision made; docs reflect it; no code change planned), or Closed (delivered).
  • Roadmap captures whether the gap is funded for the next phase. A blank cell means "no roadmap; doc-only outcome."
  • The numeric # is stable — new rows append at the bottom and keep their number across deletions/edits so cross-references survive.