Joseph Doherty f3850f8914 Phase 6.1 Stream A.5/A.6 — WriteIdempotent flag on DriverAttributeInfo + Modbus/S7 tag records + FlakeyDriver integration tests
Per-tag opt-in for write-retry per docs/v2/plan.md decisions #44, #45, #143.
Default is false — writes never auto-retry unless the driver author has marked
the tag as safe to replay.

Core.Abstractions:
- DriverAttributeInfo gains `bool WriteIdempotent = false` at the end of the
  positional record (back-compatible; every existing call site uses the default).

Driver.Modbus:
- ModbusTagDefinition gains `bool WriteIdempotent = false`. Safe candidates
  documented in the param XML: holding-register set-points, configuration
  registers. Unsafe: edge-triggered coils, counter-increment addresses.
- ModbusDriver.DiscoverAsync propagates t.WriteIdempotent into
  DriverAttributeInfo.WriteIdempotent.

Driver.S7:
- S7TagDefinition gains `bool WriteIdempotent = false`. Safe candidates:
  DB word/dword set-points, configuration DBs. Unsafe: M/Q bits that drive
  edge-triggered program routines.
- S7Driver.DiscoverAsync propagates the flag.

Stream A.5 integration tests (FlakeyDriverIntegrationTests, 4 new) exercise
the invoker + flaky-driver contract the plan enumerates:
- Read with 5 transient failures succeeds on the 6th attempt (RetryCount=10).
- Non-idempotent write with RetryCount=5 configured still fails on the first
  failure — no replay (decision #44 guard at the ExecuteWriteAsync surface).
- Idempotent write with 2 transient failures succeeds on the 3rd attempt.
- Two hosts on the same driver have independent breakers — dead-host trips
  its breaker but live-host's first call still succeeds.

Propagation tests:
- ModbusDriverTests: SetPoint WriteIdempotent=true flows into
  DriverAttributeInfo; PulseCoil default=false.
- S7DiscoveryAndSubscribeTests: same pattern for DBx SetPoint vs M-bit.

Full solution dotnet test: 947 passing (baseline 906, +41 net across Stream A
so far). Pre-existing Client.CLI Subscribe flake unchanged.

Stream A's remaining work (wiring CapabilityInvoker into DriverNodeManager's
OnReadValue / OnWriteValue / History / Subscribe dispatch paths) is the
server-side integration piece + needs DI wiring for the pipeline builder —
lands in the next PR on this branch.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-19 07:16:21 -04:00

171 lines
8.6 KiB
C#

using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus;
/// <summary>
/// Modbus TCP driver configuration. Bound from the driver's <c>DriverConfig</c> JSON at
/// <c>DriverHost.RegisterAsync</c>. Every register the driver exposes appears in
/// <see cref="Tags"/>; names become the OPC UA browse name + full reference.
/// </summary>
public sealed class ModbusDriverOptions
{
public string Host { get; init; } = "127.0.0.1";
public int Port { get; init; } = 502;
public byte UnitId { get; init; } = 1;
public TimeSpan Timeout { get; init; } = TimeSpan.FromSeconds(2);
/// <summary>Pre-declared tag map. Modbus has no discovery protocol — the driver returns exactly these.</summary>
public IReadOnlyList<ModbusTagDefinition> Tags { get; init; } = [];
/// <summary>
/// Background connectivity-probe settings. When <see cref="ModbusProbeOptions.Enabled"/>
/// is true the driver runs a tick loop that issues a cheap FC03 at register 0 every
/// <see cref="ModbusProbeOptions.Interval"/> and raises <c>OnHostStatusChanged</c> on
/// Running ↔ Stopped transitions. The Admin UI / OPC UA clients see the state through
/// <see cref="IHostConnectivityProbe"/>.
/// </summary>
public ModbusProbeOptions Probe { get; init; } = new();
/// <summary>
/// Maximum registers per FC03 (Read Holding Registers) / FC04 (Read Input Registers)
/// transaction. Modbus-TCP spec allows 125; many device families impose lower caps:
/// AutomationDirect DL205/DL260 cap at <c>128</c>, Mitsubishi Q/FX3U cap at <c>64</c>,
/// Omron CJ/CS cap at <c>125</c>. Set to the lowest cap across the devices this driver
/// instance talks to; the driver auto-chunks larger reads into consecutive requests.
/// Default <c>125</c> — the spec maximum, safe against any conforming server. Setting
/// to <c>0</c> disables the cap (discouraged — the spec upper bound still applies).
/// </summary>
public ushort MaxRegistersPerRead { get; init; } = 125;
/// <summary>
/// Maximum registers per FC16 (Write Multiple Registers) transaction. Spec maximum is
/// <c>123</c>; DL205/DL260 cap at <c>100</c>. Matching caller-vs-device semantics:
/// exceeding the cap currently throws (writes aren't auto-chunked because a partial
/// write across two FC16 calls is no longer atomic — caller must explicitly opt in
/// by shortening the tag's <c>StringLength</c> or splitting it into multiple tags).
/// </summary>
public ushort MaxRegistersPerWrite { get; init; } = 123;
/// <summary>
/// When <c>true</c> (default) the built-in <see cref="ModbusTcpTransport"/> detects
/// mid-transaction socket failures (<see cref="System.IO.EndOfStreamException"/>,
/// <see cref="System.Net.Sockets.SocketException"/>) and transparently reconnects +
/// retries the PDU exactly once. Required for DL205/DL260 because the H2-ECOM100
/// does not send TCP keepalives — intermediate NAT / firewall devices silently close
/// idle sockets and the first send after the drop would otherwise surface as a
/// connection error to the caller even though the PLC is up.
/// </summary>
public bool AutoReconnect { get; init; } = true;
}
public sealed class ModbusProbeOptions
{
public bool Enabled { get; init; } = true;
public TimeSpan Interval { get; init; } = TimeSpan.FromSeconds(5);
public TimeSpan Timeout { get; init; } = TimeSpan.FromSeconds(2);
/// <summary>Register to read for the probe. Zero is usually safe; override for PLCs that lock register 0.</summary>
public ushort ProbeAddress { get; init; } = 0;
}
/// <summary>
/// One Modbus-backed OPC UA variable. Address is zero-based (Modbus spec numbering, not
/// the documentation's 1-based coil/register conventions). Multi-register types
/// (Int32/UInt32/Float32 = 2 regs; Int64/UInt64/Float64 = 4 regs) respect the
/// <see cref="ByteOrder"/> field — real-world PLCs disagree on word ordering.
/// </summary>
/// <param name="Name">
/// Tag name, used for both the OPC UA browse name and the driver's full reference. Must be
/// unique within the driver.
/// </param>
/// <param name="Region">Coils / DiscreteInputs / InputRegisters / HoldingRegisters.</param>
/// <param name="Address">Zero-based address within the region.</param>
/// <param name="DataType">
/// Logical data type. See <see cref="ModbusDataType"/> for the register count each encodes.
/// </param>
/// <param name="Writable">When true and Region supports writes (Coils / HoldingRegisters), IWritable routes writes here.</param>
/// <param name="ByteOrder">Word ordering for multi-register types. Ignored for Bool / Int16 / UInt16 / BitInRegister / String.</param>
/// <param name="BitIndex">For <c>DataType = BitInRegister</c>: which bit of the holding register (0-15, LSB-first).</param>
/// <param name="StringLength">For <c>DataType = String</c>: number of ASCII characters (2 per register, rounded up).</param>
/// <param name="StringByteOrder">
/// Per-register byte order for <c>DataType = String</c>. Standard Modbus packs the first
/// character in the high byte (<see cref="ModbusStringByteOrder.HighByteFirst"/>).
/// AutomationDirect DirectLOGIC (DL205/DL260) and a few legacy families pack the first
/// character in the low byte instead — see <c>docs/v2/dl205.md</c> §strings.
/// </param>
/// <param name="WriteIdempotent">
/// Per <c>docs/v2/plan.md</c> decisions #44, #45, #143 — flag a tag as safe to replay on
/// write timeout / failure. Default <c>false</c>; writes do not auto-retry. Safe candidates:
/// holding-register set-points for analog values and configuration registers where the same
/// value can be written again without side-effects. Unsafe: coils that drive edge-triggered
/// actions (pulse outputs), counter-increment addresses on PLCs that treat writes as deltas,
/// any BCD / counter register where repeat-writes advance state.
/// </param>
public sealed record ModbusTagDefinition(
string Name,
ModbusRegion Region,
ushort Address,
ModbusDataType DataType,
bool Writable = true,
ModbusByteOrder ByteOrder = ModbusByteOrder.BigEndian,
byte BitIndex = 0,
ushort StringLength = 0,
ModbusStringByteOrder StringByteOrder = ModbusStringByteOrder.HighByteFirst,
bool WriteIdempotent = false);
public enum ModbusRegion { Coils, DiscreteInputs, InputRegisters, HoldingRegisters }
public enum ModbusDataType
{
Bool,
Int16,
UInt16,
Int32,
UInt32,
Int64,
UInt64,
Float32,
Float64,
/// <summary>Single bit within a holding register. <see cref="ModbusTagDefinition.BitIndex"/> selects 0-15 LSB-first.</summary>
BitInRegister,
/// <summary>ASCII string packed 2 chars per register, <see cref="ModbusTagDefinition.StringLength"/> characters long.</summary>
String,
/// <summary>
/// 16-bit binary-coded decimal. Each nibble encodes one decimal digit (0-9). Register
/// value <c>0x1234</c> decodes as decimal <c>1234</c> — NOT binary <c>0x04D2 = 4660</c>.
/// DL205/DL260 and several Mitsubishi / Omron families store timers, counters, and
/// operator-facing numerics as BCD by default.
/// </summary>
Bcd16,
/// <summary>
/// 32-bit (two-register) BCD. Decodes 8 decimal digits. Word ordering follows
/// <see cref="ModbusTagDefinition.ByteOrder"/> the same way <see cref="Int32"/> does.
/// </summary>
Bcd32,
}
/// <summary>
/// Word ordering for multi-register types. Modbus TCP standard is <see cref="BigEndian"/>
/// (ABCD for 32-bit: high word at the lower address). Many PLCs — Siemens S7, several
/// Allen-Bradley series, some Modicon families — use <see cref="WordSwap"/> (CDAB), which
/// keeps bytes big-endian within each register but reverses the word pair(s).
/// </summary>
public enum ModbusByteOrder
{
BigEndian,
WordSwap,
}
/// <summary>
/// Per-register byte order for ASCII strings packed 2 chars per register. Standard Modbus
/// convention is <see cref="HighByteFirst"/> — the first character of each pair occupies
/// the high byte of the register. AutomationDirect DirectLOGIC (DL205, DL260, DL350) and a
/// handful of legacy controllers pack <see cref="LowByteFirst"/>, which inverts that within
/// each register. Word ordering across multiple registers is always ascending address for
/// strings — only the byte order inside each register flips.
/// </summary>
public enum ModbusStringByteOrder
{
HighByteFirst,
LowByteFirst,
}