Joseph Doherty 95c7e0b490 Task #222 partial — unblock AB Legacy PCCC via cip-path workaround (5/5 stages)
Replaced the "ab_server PCCC upstream-broken" skip gate with the actual
root cause: libplctag's ab_server rejects empty CIP routing paths at the
unconnected-send layer before the PCCC dispatcher runs. Real SLC/
MicroLogix/PLC-5 hardware accepts empty paths (no backplane); ab_server
does not. With `/1,0` in place, N (Int16), F (Float32), and L (Int32)
file reads + writes round-trip cleanly across all three compose profiles.

## Fixture changes

- `AbLegacyServerFixture.cs`:
  - Drop `AB_LEGACY_TRUST_WIRE` env var + the reachable-but-untrusted
    skip branch. Fixture now only skips on TCP unreachability.
  - Add `AB_LEGACY_CIP_PATH` env var (default `1,0`) + expose `CipPath`
    property. Set `AB_LEGACY_CIP_PATH=` (empty) against real hardware.
  - Shorter skip messages on the `[AbLegacyFact]` / `[AbLegacyTheory]`
    attributes — one reason: endpoint not reachable.

- `AbLegacyReadSmokeTests.cs`:
  - Device URI built from `sim.CipPath` instead of hardcoded empty path.
  - New `AB_LEGACY_COMPOSE_PROFILE` env var filters the parametric
    theory to the running container's family. Only one container binds
    `:44818` at a time, so cross-family params would otherwise fail.
  - `Slc500_write_then_read_round_trip` skips cleanly when the running
    profile isn't `slc500`.

## E2E + seed + docs

- `scripts/e2e/test-ablegacy.ps1` — drop the `AB_LEGACY_TRUST_WIRE`
  skip gate; synopsis calls out the `/1,0` vs empty cip-path split
  between the Docker fixture and real hardware.
- `scripts/e2e/e2e-config.sample.json` — sample gateway flipped from
  the hardware placeholder (`192.168.1.10`) to the Docker fixture
  (`127.0.0.1/1,0`); comment rewritten.
- `scripts/e2e/README.md` — AB Legacy expected-matrix row goes from
  SKIP to PASS.
- `scripts/smoke/seed-ablegacy-smoke.sql` — default HostAddress points
  at the Docker fixture + header / footer text reflect the new state.
- `tests/.../Docker/README.md` — "Known limitations" section rewritten
  to describe the cip-path gate (not a dispatcher gap); env-var table
  picks up `AB_LEGACY_CIP_PATH` + `AB_LEGACY_COMPOSE_PROFILE`.
- `docs/drivers/AbLegacy-Test-Fixture.md` + `docs/drivers/README.md`
  + `docs/DriverClis.md` — flip status from blocked to functional;
  residual bit-file-write gap (B3:0/5 → 0x803D0000) documented.

## Residual gap

Bit-file writes (`B3:0/5` style) surface `0x803D0000` against
`ab_server --plc=SLC500`; bit reads work. Non-blocking for smoke
coverage — N/F/L round-trip is enough. Real hardware / RSEmulate 500
for bit-write fidelity. Documented in `Docker/README.md` §"Known
limitations" + the `AbLegacy-Test-Fixture.md` follow-ups list.

## Verified

- Full-solution build: 0 errors, 334 pre-existing warnings.
- Integration suite passes per-profile with
  `AB_LEGACY_COMPOSE_PROFILE=<slc500|micrologix|plc5>` + matching
  compose container up.
- All four non-hardware e2e scripts (Modbus / AB CIP / AB Legacy / S7)
  now 5/5 against the respective docker-compose fixtures.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-21 12:38:43 -04:00

60 lines
2.7 KiB
JSON

{
"$comment": "Copy this file to e2e-config.json and replace the NodeIds with the ones your Config DB publishes. Fields named `opcUaUrl` override the -OpcUaUrl parameter on test-all.ps1 per-driver. Omit a top-level key to skip that driver.",
"modbus": {
"$comment": "Port 5020 matches tests/.../Modbus.IntegrationTests/Docker/docker-compose.yml — `docker compose --profile standard up -d`.",
"endpoint": "127.0.0.1:5020",
"bridgeNodeId": "ns=2;s=Modbus/HR200",
"opcUaUrl": "opc.tcp://localhost:4840"
},
"abcip": {
"$comment": "ab_server listens on port 44818 (default CIP/EIP). `docker compose --profile controllogix up -d`.",
"gateway": "ab://127.0.0.1:44818/1,0",
"family": "ControlLogix",
"tagPath": "TestDINT",
"bridgeNodeId": "ns=2;s=AbCip/TestDINT"
},
"ablegacy": {
"$comment": "Works against ab_server --profile slc500 (Docker fixture) or real SLC/MicroLogix/PLC-5 hardware. `/1,0` cip-path is required for the Docker fixture; real hardware accepts an empty path — e.g. `ab://10.0.1.50:44818/`.",
"gateway": "ab://127.0.0.1/1,0",
"plcType": "Slc500",
"address": "N7:5",
"bridgeNodeId": "ns=2;s=AbLegacy/N7_5"
},
"s7": {
"$comment": "Port 1102 matches tests/.../S7.IntegrationTests/Docker/docker-compose.yml (python-snap7 needs non-priv port). `docker compose --profile s7_1500 up -d`. Real S7 PLCs listen on 102.",
"endpoint": "127.0.0.1:1102",
"cpu": "S71500",
"slot": 0,
"address": "DB1.DBW0",
"bridgeNodeId": "ns=2;s=S7/DB1_DBW0"
},
"focas": {
"$comment": "Gated behind FOCAS_TRUST_WIRE=1 — no public simulator. Point at a real CNC + ensure Fwlib32.dll is on PATH.",
"host": "192.168.1.20",
"port": 8193,
"address": "R100",
"bridgeNodeId": "ns=2;s=Focas/R100"
},
"twincat": {
"$comment": "Gated behind TWINCAT_TRUST_WIRE=1 — needs XAR or standalone TwinCAT Router NuGet reachable at -AmsNetId.",
"amsNetId": "127.0.0.1.1.1",
"amsPort": 851,
"symbolPath": "MAIN.iCounter",
"bridgeNodeId": "ns=2;s=TwinCAT/MAIN_iCounter"
},
"phase7": {
"$comment": "Virtual tags + scripted alarms. The VirtualNodeId must resolve to a server-side virtual tag whose script reads the modbus InputNodeId and writes VT = input * 2. The AlarmNodeId is the ConditionId of a scripted alarm that fires when VT > 100.",
"modbusEndpoint": "127.0.0.1:5502",
"inputNodeId": "ns=2;s=Modbus/HR100",
"virtualNodeId": "ns=2;s=Virtual/VT_DoubledHR100",
"alarmNodeId": "ns=2;s=Alarm/HR100_High"
}
}