fix(s7): bound async wire ops with a wall-clock deadline (R2-01 read leg)
The R2-01 live gate (S7_1500ConnectTimeoutOutageTests, docker-pause blackhole)
surfaced a real gap the offline fakes couldn't: S7.Net's ReadTimeout/WriteTimeout
map to the TcpClient's ReceiveTimeout/SendTimeout, which govern only SYNCHRONOUS
socket calls — the async read/write paths S7.Net uses ignore them. On an
established-but-frozen peer (frozen PLC / firewall DROP / cable pulled mid-flow,
TCP session still open) a read blocked until the OS TCP stack gave up (minutes),
silently wedging the poll loop: no Bad tick, no reconnect. STAB-14 fixed only the
CONNECT leg (EnsureConnectedAsync CancelAfter); this is its READ-leg sibling.

- New S7OperationDeadline: bounds every data-plane wire op with a wall-clock
  ceiling (= _options.Timeout), surfacing an overrun as TimeoutException. Applied
  in S7PlcAdapter to Read/ReadBytes/Write/WriteBytes/ReadStatus. OpenAsync is left
  to EnsureConnectedAsync's own CancelAfter (not double-bounded).
- IsS7ConnectionFatal now classifies TimeoutException fatal → handle marked dead →
  next EnsureConnectedAsync reopens (connect-timeout fix takes over from there).
- Tests: 5 S7OperationDeadline unit tests (deadline / token-honouring / caller-
  cancel-passthrough / resultless), 1 driver-reaction test (read TimeoutException
  → reopen). Driver.S7.Tests 260/260.
- Live gate S7_1500ConnectTimeoutOutageTests now GREEN against the real snap7 sim
  (8s: baseline Good -> pause blackhole -> Bad tick -> unpause -> recovered Good).
2026-07-15 07:11:42 -04:00
..