Joseph Doherty 5ed26d2ec6 docs: alarms-over-gateway plan banner — record A.2 dev-rig finding
Replaces the "ships as a follow-up gated on dev-rig validation"
banner with the actual finding from the dev-rig inspection: the
MXAccess COM Toolkit on this AVEVA install does not expose any
alarm-event family, and the AVEVA alarm-subscription managed
assemblies (aaAlarmManagedClient, ArchestrAAlarmsAndEvents.SDK)
are x64-only and incompatible with the worker's x86 bitness.

Two operator-facing paths forward documented inline:

1. Stay on the value-driven sub-attribute path (current production
   behaviour). Operator-comment fidelity is the only v1 regression.

2. Add an x64 alarm-helper sub-process alongside the worker that
   loads aaAlarmManagedClient and forwards transitions over a
   named-pipe IPC. Recovers full v1 fidelity but adds operational
   complexity.

The full architectural notes live in the mxaccessgw repo at
src/MxGateway.Worker/MxAccess/MxAccessAlarmEventSink.cs.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-30 21:29:16 -04:00
..