otopcua-twincat-cli — Beckhoff TwinCAT test client
Ad-hoc probe / read / write / subscribe tool for Beckhoff TwinCAT 2 / TwinCAT 3
runtimes via ADS. Uses the same TwinCATDriver the OtOpcUa server does
(Beckhoff.TwinCAT.Ads package). Native ADS notifications by default;
--poll-only falls back to the shared PollGroupEngine.
Fifth (final) of the driver test-client CLIs.
Build + run
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT.Cli -- --help
Prerequisite: AMS router
The Beckhoff.TwinCAT.Ads library needs a reachable AMS router to open ADS
sessions. Pick one:
- Local TwinCAT XAR — install the free TwinCAT 3 XAR Engineering install on the machine running the CLI; it ships the router.
- Beckhoff.TwinCAT.Ads.TcpRouter — standalone NuGet router. Run in a sidecar process when no XAR is installed.
- Remote AMS route — any Windows box with TwinCAT installed, with an AMS route authorised to the CLI host.
The CLI compiles + runs without a router, but every wire call fails with a transport error until one is reachable.
Common flags
| Flag | Default | Purpose |
|---|---|---|
-n / --ams-net-id |
required | AMS Net ID (e.g. 192.168.1.40.1.1) |
-p / --ams-port |
851 |
AMS port (TwinCAT 3 PLC = 851, TwinCAT 2 = 801) |
--timeout-ms |
5000 |
Per-operation timeout |
--poll-only |
off | Disable native ADS notifications, use PollGroupEngine instead |
--verbose |
off | Serilog debug output |
Data types
TwinCAT exposes the IEC 61131-3 atomic set: Bool, SInt, USInt, Int,
UInt, DInt, UDInt, LInt, ULInt, Real, LReal, String, WString,
Time, Date, DateTime, TimeOfDay. The four IEC time/date variants
marshal as UDINT on the wire — CLI takes a numeric raw value and lets the
caller interpret semantics.
Commands
probe
# Local TwinCAT 3, probe a canonical global
otopcua-twincat-cli probe -n 127.0.0.1.1.1 -s "TwinCAT_SystemInfoVarList._AppInfo.OnlineChangeCnt"
# Remote, probe a project variable
otopcua-twincat-cli probe -n 192.168.1.40.1.1 -s MAIN.bRunning --type Bool
read
# Bool symbol
otopcua-twincat-cli read -n 192.168.1.40.1.1 -s MAIN.bStart -t Bool
# Counter
otopcua-twincat-cli read -n 192.168.1.40.1.1 -s GVL.Counter -t DInt
# Nested UDT member
otopcua-twincat-cli read -n 192.168.1.40.1.1 -s Motor1.Status.Running -t Bool
# Array element
otopcua-twincat-cli read -n 192.168.1.40.1.1 -s "Recipe[3]" -t Real
# WString
otopcua-twincat-cli read -n 192.168.1.40.1.1 -s GVL.sMessage -t WString
ADS variable handles for read / write symbols are cached transparently
inside the CLI's underlying AdsTwinCATClient. The first read of a symbol
resolves a handle; repeats reuse the cached handle for smaller AMS payloads
and skipped name resolution. The cache wipes on reconnect, on
DeviceSymbolVersionInvalid (with a one-shot retry), and on CLI exit. See
docs/drivers/TwinCAT-Test-Fixture.md §Handle caching for the full story
including the staleness caveat after an online change.
write
otopcua-twincat-cli write -n 192.168.1.40.1.1 -s MAIN.bStart -t Bool -v true
otopcua-twincat-cli write -n 192.168.1.40.1.1 -s GVL.Counter -t DInt -v 42
otopcua-twincat-cli write -n 192.168.1.40.1.1 -s GVL.sMessage -t WString -v "running"
Structure writes refused — drop to driver config JSON for those.
subscribe
# Native ADS notifications (default) — PLC pushes on its own cycle
otopcua-twincat-cli subscribe -n 192.168.1.40.1.1 -s GVL.Counter -t DInt -i 500
# Fall back to polling for runtimes where native notifications are constrained
otopcua-twincat-cli subscribe -n 192.168.1.40.1.1 -s GVL.Counter -t DInt -i 500 --poll-only
The subscribe banner announces which mechanism is in play — "ADS notification" or "polling" — so it's obvious in screen-recorded bug reports.
--poll-only polls go through the same cached-handle path as read, so
repeated polls of the same symbol carry only a 4-byte handle on the wire
rather than the full symbolic path.