Files
lmxopcua/tests/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests/AbCipAlarmProjectionTests.cs
Joseph Doherty 4e80db4844 AbCip IAlarmSource via ALMD projection (#177) — feature-flagged OFF by default; when enabled, polls declared ALMD UDT member fields + raises OnAlarmEvent on 0→1 + 1→0 transitions. Closes task #177. The AB CIP driver now implements IAlarmSource so the generic-driver alarm dispatch path (PR 14's sinks + the Server.Security.AuthorizationGate AlarmSubscribe/AlarmAck invoker wrapping) can treat AB-backed alarms uniformly with Galaxy + OpcUaClient + FOCAS. Projection is ALMD-only in this pass: the Logix ALMD (digital alarm) instruction's UDT shape is well-understood (InFaulted + Acked + Severity + In + Cfg_ProgTime at stable member names) so the polled-read + state-diff pattern fits without concessions. ALMA (analog alarm) deferred to a follow-up because its HHLimit/HLimit/LLimit/LLLimit threshold + In value semantics deserve their own design pass — raising on threshold-crossing is not the same shape as raising on InFaulted-edge. AbCipDriverOptions gains two knobs: EnableAlarmProjection (default false) + AlarmPollInterval (default 1s). Explicit opt-in because projection semantics don't exactly mirror Rockwell FT Alarm & Events; shops running FT Live should leave this off + take alarms through the native A&E route. AbCipAlarmProjection is the state machine: per-subscription background loop polls the source-node set via the driver's public ReadAsync — which gains the #194 whole-UDT optimization for free when ALMDs are declared with their standard member set, so one poll tick reads (N alarms × 2 members) = N libplctag round-trips rather than 2N. Per-tick state diff: compare InFaulted + Severity against last-seen, fire raise (0→1) / clear (1→0) with AlarmSeverity bucketed via the 1-1000 Logix severity scale (≤250 Low, ≤500 Medium, ≤750 High, rest Critical — matches OpcUaClient's MapSeverity shape). ConditionId is {sourceNode}#active — matches a single active-branch per alarm which is all ALMD supports; when Cfg_ProgTime-based branch identity becomes interesting (re-raise after ack with new timestamp), a richer ConditionId pass can land. Subscribe-while-disabled returns a handle wrapping id=0 — capability negotiation (the server queries IAlarmSource presence at driver-load time) still succeeds, the alarm surface just never fires. Unsubscribe cancels the sub's CTS + awaits its loop; ShutdownAsync cancels every sub on its way out so a driver reload doesn't leak poll tasks. AcknowledgeAsync routes through the driver's existing WriteAsync path — per-ack writes {SourceNodeId}.Acked = true (the simpler semantic; operators whose ladder watches AckCmd + rising-edge can wire a client-side pulse until a driver-level edge-mode knob lands). Best-effort — per-ack faults are swallowed so one bad ack doesn't poison the whole batch. Six new AbCipAlarmProjectionTests: detector flags ALMD signature + skips non-signature UDTs + atomics; severity mapping matches OPC UA A&C bucket boundaries; feature-flag OFF returns a handle but never touches the fake runtime (proving no background polling happens); feature-flag ON fires a raise event on 0→1; clear event fires on 1→0 after a prior raise; unsubscribe stops the poll loop (ReadCount doesn't grow past cancel + at most one straggler read). Driver builds 0 errors; AbCip.Tests 233/233 (was 227, +6 new). Task #177 closed — the last pending AB CIP follow-up is now #194 (already shipped). Remaining pending fleet-wide: #150 (Galaxy MXAccess failover hardware) + #199 (UnsTab Playwright smoke).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-20 04:24:40 -04:00

191 lines
7.6 KiB
C#
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
using Shouldly;
using Xunit;
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
namespace ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests;
/// <summary>
/// Task #177 — tests covering ALMD projection detection, feature-flag gate,
/// subscribe/unsubscribe lifecycle, state-transition event emission, and acknowledge.
/// </summary>
[Trait("Category", "Unit")]
public sealed class AbCipAlarmProjectionTests
{
private const string Device = "ab://10.0.0.5/1,0";
private static AbCipTagDefinition AlmdTag(string name) => new(
name, Device, name, AbCipDataType.Structure, Members:
[
new AbCipStructureMember("InFaulted", AbCipDataType.DInt), // Logix stores ALMD bools as DINT
new AbCipStructureMember("Acked", AbCipDataType.DInt),
new AbCipStructureMember("Severity", AbCipDataType.DInt),
new AbCipStructureMember("In", AbCipDataType.DInt),
]);
[Fact]
public void AbCipAlarmDetector_Flags_AlmdSignature_As_Alarm()
{
var almd = AlmdTag("HighTemp");
AbCipAlarmDetector.IsAlmd(almd).ShouldBeTrue();
var plainUdt = new AbCipTagDefinition("Plain", Device, "Plain", AbCipDataType.Structure, Members:
[new AbCipStructureMember("X", AbCipDataType.DInt)]);
AbCipAlarmDetector.IsAlmd(plainUdt).ShouldBeFalse();
var atomic = new AbCipTagDefinition("Plain", Device, "Plain", AbCipDataType.DInt);
AbCipAlarmDetector.IsAlmd(atomic).ShouldBeFalse();
}
[Fact]
public void Severity_Mapping_Matches_OPC_UA_Convention()
{
// Logix severity 11000 — mirror the OpcUaClient ACAndC bucketing.
AbCipAlarmProjection.MapSeverity(100).ShouldBe(AlarmSeverity.Low);
AbCipAlarmProjection.MapSeverity(400).ShouldBe(AlarmSeverity.Medium);
AbCipAlarmProjection.MapSeverity(600).ShouldBe(AlarmSeverity.High);
AbCipAlarmProjection.MapSeverity(900).ShouldBe(AlarmSeverity.Critical);
}
[Fact]
public async Task FeatureFlag_Off_SubscribeAlarms_Returns_Handle_But_Never_Polls()
{
var factory = new FakeAbCipTagFactory();
var opts = new AbCipDriverOptions
{
Devices = [new AbCipDeviceOptions(Device)],
Tags = [AlmdTag("HighTemp")],
EnableAlarmProjection = false, // explicit; also the default
};
var drv = new AbCipDriver(opts, "drv-1", factory);
await drv.InitializeAsync("{}", CancellationToken.None);
var handle = await drv.SubscribeAlarmsAsync(["HighTemp"], CancellationToken.None);
handle.ShouldNotBeNull();
handle.DiagnosticId.ShouldContain("abcip-alarm-sub-");
// Wait a touch — if polling were active, a fake member-read would be triggered.
await Task.Delay(100);
factory.Tags.ShouldNotContainKey("HighTemp.InFaulted");
factory.Tags.ShouldNotContainKey("HighTemp.Severity");
await drv.UnsubscribeAlarmsAsync(handle, CancellationToken.None);
await drv.ShutdownAsync(CancellationToken.None);
}
[Fact]
public async Task FeatureFlag_On_Subscribe_Starts_Polling_And_Fires_Raise_On_0_to_1()
{
var factory = new FakeAbCipTagFactory();
var opts = new AbCipDriverOptions
{
Devices = [new AbCipDeviceOptions(Device)],
Tags = [AlmdTag("HighTemp")],
EnableAlarmProjection = true,
AlarmPollInterval = TimeSpan.FromMilliseconds(20),
};
var drv = new AbCipDriver(opts, "drv-1", factory);
await drv.InitializeAsync("{}", CancellationToken.None);
var events = new List<AlarmEventArgs>();
drv.OnAlarmEvent += (_, e) => { lock (events) events.Add(e); };
var handle = await drv.SubscribeAlarmsAsync(["HighTemp"], CancellationToken.None);
// The ALMD UDT is declared so whole-UDT grouping kicks in; the parent HighTemp runtime
// gets created + polled. Set InFaulted offset-value to 0 first (clear), wait a tick,
// then flip to 1 (fault) + wait for the raise event.
await WaitForTagCreation(factory, "HighTemp");
factory.Tags["HighTemp"].ValuesByOffset[0] = 0; // InFaulted=false at offset 0
factory.Tags["HighTemp"].ValuesByOffset[8] = 500; // Severity at offset 8 (after InFaulted+Acked)
await Task.Delay(80); // let a tick seed the "last-seen false" state
factory.Tags["HighTemp"].ValuesByOffset[0] = 1; // flip to faulted
await Task.Delay(200); // allow several polls to be safe
lock (events)
{
events.ShouldContain(e => e.SourceNodeId == "HighTemp" && e.AlarmType == "ALMD"
&& e.Message.Contains("raised"));
}
await drv.UnsubscribeAlarmsAsync(handle, CancellationToken.None);
await drv.ShutdownAsync(CancellationToken.None);
}
[Fact]
public async Task Clear_Event_Fires_On_1_to_0_Transition()
{
var factory = new FakeAbCipTagFactory();
var opts = new AbCipDriverOptions
{
Devices = [new AbCipDeviceOptions(Device)],
Tags = [AlmdTag("HighTemp")],
EnableAlarmProjection = true,
AlarmPollInterval = TimeSpan.FromMilliseconds(20),
};
var drv = new AbCipDriver(opts, "drv-1", factory);
await drv.InitializeAsync("{}", CancellationToken.None);
var events = new List<AlarmEventArgs>();
drv.OnAlarmEvent += (_, e) => { lock (events) events.Add(e); };
var handle = await drv.SubscribeAlarmsAsync(["HighTemp"], CancellationToken.None);
await WaitForTagCreation(factory, "HighTemp");
factory.Tags["HighTemp"].ValuesByOffset[0] = 1;
factory.Tags["HighTemp"].ValuesByOffset[8] = 500;
await Task.Delay(80); // observe raise
factory.Tags["HighTemp"].ValuesByOffset[0] = 0;
await Task.Delay(200);
lock (events)
{
events.ShouldContain(e => e.Message.Contains("raised"));
events.ShouldContain(e => e.Message.Contains("cleared"));
}
await drv.UnsubscribeAlarmsAsync(handle, CancellationToken.None);
await drv.ShutdownAsync(CancellationToken.None);
}
[Fact]
public async Task Unsubscribe_Stops_The_Poll_Loop()
{
var factory = new FakeAbCipTagFactory();
var opts = new AbCipDriverOptions
{
Devices = [new AbCipDeviceOptions(Device)],
Tags = [AlmdTag("HighTemp")],
EnableAlarmProjection = true,
AlarmPollInterval = TimeSpan.FromMilliseconds(20),
};
var drv = new AbCipDriver(opts, "drv-1", factory);
await drv.InitializeAsync("{}", CancellationToken.None);
var handle = await drv.SubscribeAlarmsAsync(["HighTemp"], CancellationToken.None);
await WaitForTagCreation(factory, "HighTemp");
var preUnsubReadCount = factory.Tags["HighTemp"].ReadCount;
await drv.UnsubscribeAlarmsAsync(handle, CancellationToken.None);
await Task.Delay(100); // well past several poll intervals if the loop were still alive
var postDelayReadCount = factory.Tags["HighTemp"].ReadCount;
// Allow at most one straggler read between the unsubscribe-cancel + the loop exit.
(postDelayReadCount - preUnsubReadCount).ShouldBeLessThanOrEqualTo(1);
await drv.ShutdownAsync(CancellationToken.None);
}
private static async Task WaitForTagCreation(FakeAbCipTagFactory factory, string tagName)
{
var deadline = DateTime.UtcNow.AddSeconds(2);
while (DateTime.UtcNow < deadline)
{
if (factory.Tags.ContainsKey(tagName)) return;
await Task.Delay(10);
}