Group all 69 projects into category subfolders under src/ and tests/ so the Rider Solution Explorer mirrors the module structure. Folders: Core, Server, Drivers (with a nested Driver CLIs subfolder), Client, Tooling. - Move every project folder on disk with git mv (history preserved as renames). - Recompute relative paths in 57 .csproj files: cross-category ProjectReferences, the lib/ HintPath+None refs in Driver.Historian.Wonderware, and the external mxaccessgw refs in Driver.Galaxy and its test project. - Rebuild ZB.MOM.WW.OtOpcUa.slnx with nested solution folders. - Re-prefix project paths in functional scripts (e2e, compliance, smoke SQL, integration, install). Build green (0 errors); unit tests pass. Docs left for a separate pass. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
87 lines
3.8 KiB
C#
87 lines
3.8 KiB
C#
using Shouldly;
|
|
using Xunit;
|
|
using ZB.MOM.WW.OtOpcUa.Driver.Modbus;
|
|
|
|
namespace ZB.MOM.WW.OtOpcUa.Driver.Modbus.Addressing.Tests;
|
|
|
|
[Trait("Category", "Unit")]
|
|
public sealed class ModbusModiconAddressTests
|
|
{
|
|
[Theory]
|
|
// 5-digit form, one per region. Trailing 4 digits = 1-based register; PDU offset is one less.
|
|
[InlineData("00001", ModbusRegion.Coils, (ushort)0)]
|
|
[InlineData("09999", ModbusRegion.Coils, (ushort)9998)]
|
|
[InlineData("10001", ModbusRegion.DiscreteInputs, (ushort)0)]
|
|
[InlineData("19999", ModbusRegion.DiscreteInputs, (ushort)9998)]
|
|
[InlineData("30001", ModbusRegion.InputRegisters, (ushort)0)]
|
|
[InlineData("39999", ModbusRegion.InputRegisters, (ushort)9998)]
|
|
[InlineData("40001", ModbusRegion.HoldingRegisters, (ushort)0)]
|
|
[InlineData("49999", ModbusRegion.HoldingRegisters, (ushort)9998)]
|
|
// 6-digit form unlocks the full 16-bit address space — 1..65536 → PDU 0..65535.
|
|
[InlineData("400001", ModbusRegion.HoldingRegisters, (ushort)0)]
|
|
[InlineData("410000", ModbusRegion.HoldingRegisters, (ushort)9999)]
|
|
[InlineData("465536", ModbusRegion.HoldingRegisters, (ushort)65535)]
|
|
[InlineData("000001", ModbusRegion.Coils, (ushort)0)]
|
|
[InlineData("100001", ModbusRegion.DiscreteInputs, (ushort)0)]
|
|
[InlineData("365536", ModbusRegion.InputRegisters, (ushort)65535)]
|
|
public void Parse_Valid(string address, ModbusRegion expectedRegion, ushort expectedOffset)
|
|
{
|
|
var (region, offset) = ModbusModiconAddress.Parse(address);
|
|
region.ShouldBe(expectedRegion);
|
|
offset.ShouldBe(expectedOffset);
|
|
}
|
|
|
|
[Theory]
|
|
[InlineData("", "null or empty")]
|
|
[InlineData(" ", "null or empty")]
|
|
[InlineData("4001", "5 or 6 digits")] // 4 chars
|
|
[InlineData("4000001", "5 or 6 digits")] // 7 chars
|
|
[InlineData("4000A", "only digits")] // letter in body
|
|
[InlineData("X0001", "only digits")] // letter leading
|
|
[InlineData("20001", "leading digit must be 0/1/3/4")] // region 2 doesn't exist
|
|
[InlineData("50001", "leading digit must be 0/1/3/4")]
|
|
[InlineData("90001", "leading digit must be 0/1/3/4")]
|
|
[InlineData("40000", "must be >= 1")] // 0-based register number
|
|
[InlineData("400000", "must be >= 1")] // 6-digit zero
|
|
public void Parse_Invalid_Surfaces_Diagnostic(string address, string fragment)
|
|
{
|
|
Should.Throw<FormatException>(() => ModbusModiconAddress.Parse(address))
|
|
.Message.ShouldContain(fragment, Case.Insensitive);
|
|
}
|
|
|
|
[Fact]
|
|
public void TryParse_Returns_False_With_Diagnostic_On_Invalid()
|
|
{
|
|
var ok = ModbusModiconAddress.TryParse("not-an-address", out _, out _, out var error);
|
|
ok.ShouldBeFalse();
|
|
error.ShouldNotBeNull();
|
|
}
|
|
|
|
[Fact]
|
|
public void TryParse_Returns_True_With_Null_Error_On_Valid()
|
|
{
|
|
var ok = ModbusModiconAddress.TryParse("40001", out var region, out var offset, out var error);
|
|
ok.ShouldBeTrue();
|
|
region.ShouldBe(ModbusRegion.HoldingRegisters);
|
|
offset.ShouldBe((ushort)0);
|
|
error.ShouldBeNull();
|
|
}
|
|
|
|
[Fact]
|
|
public void TryParse_Handles_Null()
|
|
{
|
|
ModbusModiconAddress.TryParse(null, out _, out _, out var error).ShouldBeFalse();
|
|
error.ShouldNotBeNull();
|
|
}
|
|
|
|
[Fact]
|
|
public void TryParse_Trims_Whitespace()
|
|
{
|
|
// Tag spreadsheets often arrive with stray padding; the parser tolerates it rather than
|
|
// forcing every importer to trim — but stays strict on the 5/6-digit length once trimmed.
|
|
ModbusModiconAddress.TryParse(" 40001 ", out var region, out var offset, out _).ShouldBeTrue();
|
|
region.ShouldBe(ModbusRegion.HoldingRegisters);
|
|
offset.ShouldBe((ushort)0);
|
|
}
|
|
}
|