Heidenhain LSV2 driver (read-only)
DriverType = "Heidenhain" (DriverTypeNames.Heidenhain) · projects Driver.Heidenhain (+ .Contracts) ·
Gitea #803.
A native, read-only Heidenhain LSV2 client over TCP (default port 19000) for iTNC/TNC controls. No
Java/Python runtime and no vendor SDK (RemoTools/DNC) — a managed System.Net.Sockets client. It is a port of the
ignitionoee v0.20.3 Java driver (commit d1dda0a5, modules/drivers/gateway/.../driver/heidenhain, wire reference
docs/reference/heidenhain-lsv2.md), whose protocol layouts are in turn derived from pyLSV2 commit 97a3d691.
The Java validation evidence (four real iTNC 530 controls, 2026-11-03) is reference evidence, not proof of this
port — see Hardware-gated.
Read-only boundary
Three independent layers, each sufficient on its own for its concern:
- No write capability.
HeidenhainDriverdoes not implementIWritable;DriverInstanceActorrefuses every OPC write before it reaches the driver (HeidenhainDriverEndToEndTests). - No writable nodes. A
ReadWriteaccess level is refused at authoring —RawTreeServicecreate/update/import (so the tag modal, manual entry, CSV import and browse commit), where the modal and the manual-entry grid also fix the access level at Read — and again by the deploy gateHeidenhainTagWritable, so no node is ever advertised writable. A"writable": trueTagConfig key is rejected by the tag reader and dropped by the typed editor. The same paths tieTag.DataTypeto what the driver publishes (the catalog type for a fixed address —Float64⇒Double— or the binding's declared type): the modals default it from the address, the save path refuses a mismatch, and the deploy gateHeidenhainTagDataTypeMismatchcatches anything older (one rule,HeidenhainTagRules). - Payload-aware outbound allowlist (
Lsv2ReadOnlyPolicy).Lsv2Codec.Frame— the only frame builder — checks command and payload immediately before any byte is written. There is no raw-command API (Lsv2Client's public surface is pinned by a reflection test) and no configuration knob that widens it.
| Request | Permitted payload | Reply |
|---|---|---|
A_LG |
role ∈ {INSPECT, DNC, DATA} NUL, optional NUL-free Latin-1 password NUL |
T_OK (empty) |
R_VR |
empty | S_VR |
R_PR |
empty | S_PR |
R_RI |
exactly a uint16be selector ∈ {22–28, 30–34, 51} | S_RI |
R_MB |
uint32be address + uint8 count, 1 ≤ count ≤ 247, no 32-bit wrap | S_MB |
R_DP |
four zero bytes + NUL-free path + NUL (≤ 247 bytes total) | S_DP |
Everything else is refused before transmission — every C_* (file/PLC/parameter writes, buffer negotiation),
A_LO, file reads (R_FL, R_DI, …), key/scope operations, PLCDEBUG/MONITOR/FILE roles, response
mnemonics sent as requests. Lsv2ReadOnlyPolicyTests.A_refused_request_never_reaches_the_socket proves zero bytes
leave the process for a refused request, even through the internal exchange primitive. Socket close ends a
session (no logout command). Do not broaden the allowlist to work around a controller refusal.
Transport
uint32be payloadLength | ASCII command[4] | payload — legacy buffer mode, 255-byte frame maximum, no C_CC
negotiation. One transaction at a time per control (a SemaphoreSlim in Lsv2Client, and a single acquisition
loop per device). Each transaction has one monotonic deadline (TimeoutMs) covering write + header + body, so a
trickling peer cannot extend it. EOF, deadline, an oversized (> 247) or unexpected reply, a malformed T_ER, or a
T_OK with a body closes the client — a later request can never consume leftover bytes. A complete
T_ER/T_BD refusal keeps the stream synchronised. Close() never waits for the transaction gate, so it always
interrupts a blocked read.
Configuration
Driver config (HeidenhainDriverOptions, AdminUI HeidenhainDriverForm) — every field is int/bool/string (no
enums, so the numeric-enum form/factory trap cannot occur):
| Key | Default | Range / meaning |
|---|---|---|
TimeoutMs |
5000 | 100–60000; connect + per-transaction deadline |
Access.TelemetryEnabled |
true | Off = no R_RI requests at all |
Access.DncLoginEnabled |
true | Optional DNC login; a refusal never blocks reads permitted under INSPECT |
Access.DataEnabled |
false | Opt-in DATA login, attempted only when a DATA: binding exists (iTNC only) |
Access.InspectPassword / DncPassword / DataPassword |
— | References only (below) |
Polling.StatusMs / CustomMs / SlowMs |
1000 / 1000 / 10000 | each 100–3600000 |
Polling.MaxAlarms |
64 | 1–256 |
Polling.TimersEnabled |
false | Experimental selectors 30–34 |
Reconnect.InitialDelayMs / MaxDelayMs |
1000 / 30000 | doubling backoff, bounded |
ProbeTimeoutSeconds |
10 | Test Connect, 1–60 |
Device config (one /raw Device per control, AdminUI HeidenhainDeviceForm): Host (required, no default),
Port (19000), optional per-device InspectPassword/DncPassword/DataPassword overrides. A device is validated
only once it carries tags, so an unconfigured default Device1 does not fault the driver.
Credentials — namespaced references only. A password field is one of:
| Form | Resolved from |
|---|---|
| blank | no password |
secret:heidenhain/<name> (e.g. secret:heidenhain/line3/inspect; [A-Za-z0-9._-] segments, no ..) |
the node's encrypted secret store (ISecretResolver), same slash-scoped naming as galaxy/<inst>/apikey |
env:OTOPCUA_HEIDENHAIN_<NAME> (exact upper-case prefix, NAME = [A-Z0-9_]+) |
the process environment |
Why namespaced: the reference is resolved on the node (for Test Connect: on the admin node) and sent in
cleartext in A_LG to whatever Host the author configured. An unscoped reference would let anyone who can edit
a driver exfiltrate env:ConnectionStrings__ConfigDb, env:ServerHistorian__ApiKey or any other secret by pointing
Host at their own machine. Anything outside the namespace is refused by every layer: the parser
(HeidenhainOptionsParser, so the factory and the probe), the resolver again at resolve time
(HeidenhainCredentials, fail-closed independently of earlier validation), the AdminUI save path
(RawTreeService create/update driver + device refuse the config server-side via DriverConfigSaveGate, and the
driver/device modals disable Save while it is invalid — so a literal never reaches the config database), and the
deploy gate HeidenhainCredentialPersisted. Messages never echo the value. Since #815 the parser and resolver are
the shared CredentialReferences / DriverCredentialPolicy (Core.Abstractions) that Galaxy and OpcUaClient use
too, and Test Connect / live browse also refuse an out-of-namespace reference before any probe or browser runs; a
prefix in another casing (SECRET:) is refused, and ${secret:heidenhain/<name>} is accepted as a spelling of
secret:heidenhain/<name>.
Resolved at each login, never held in options or session state. Fail-closed: an absent secret or unset
variable fails the login rather than sending the reference text. An unusable INSPECT credential fails the
connect (INSPECT is required). An unusable optional DNC/DATA credential — unresolvable, or a password the LSV2
login payload cannot carry (NUL, non-Latin-1, > 247 bytes) — never fails the session: the login is not sent, the
reads that need that role read BadConfigurationError (capability ConfigurationError), and INSPECT telemetry
continues. Plain LSV2 is unencrypted — reach the control over an externally managed secure network; there is no
SSH subsystem.
Addresses (TagConfig)
{"address": "<address>", "dataType": "<DriverDataType name>", "isArray": true|false} — parsed by
HeidenhainTagDefinitionFactory, the single authority shared by the driver, the deploy inspector
(EquipmentTagConfigInspector) and the AdminUI editor/validator.
Fixed namespace (device-relative; browse-committable from the /raw picker without contacting the control):
| Folder | Leaves (type) | Source | Group |
|---|---|---|---|
Controller |
Model, NcVersion, PlcVersion, Options (String) |
R_VR (4 or 5 fields; SPLC skipped; empty options preserved) |
Slow |
Status |
ExecutionState (Int32), ProgramState (Int32) — raw native enums |
R_RI 23, 26 |
Status |
Program |
Main, Current (String), Line (Int64) |
R_RI 24 |
Status |
Overrides |
Feed, Spindle, Rapid (Float64, percent) |
R_RI 25 (uint32 hundredths) |
Status |
Axes |
Names (String[]), Positions (Float64[]) — aligned, controller units |
R_RI 22 |
Status |
Tool |
Number (Int64), Index, AxisCode (Int32), Length, Radius (Float64) |
R_RI 51 (8-byte reply ⇒ geometry BadNotSupported, never 0) |
Slow |
Alarms |
Classes, Groups, Numbers (Int32[]), Messages (String[]), Count (Int32) |
R_RI 27 then 28; only refusal 57 ends the list |
Slow |
Timers |
NcUptime, MachineUptime, MachineRuntime, Spindle0Runtime, Spindle1Runtime (Int64, raw) |
R_RI 30–34, disabled by default |
Slow |
Capabilities |
one String per feature + PlcLayout, DncLogin, DataLogin |
local, never a wire read | Slow |
Array leaves require "isArray": true (variable length); the typed editor and browse commit write it. Capability
states: Unknown, Supported, Disabled, AccessDenied, Unsupported, InvalidData, CommunicationLost —
evidence about the last read, not a licence assertion.
PLC bindings PLC:<AREA>:<INDEX> + dataType, read via R_MB. INDEX is an element index (1–10 digits,
≤ uint32), multiplied by the native width and added to the region base the control advertises in R_PR.
Numeric R_PR counts are byte capacities (element count = ⌊bytes / width⌋; BYTE/WORD/DWORD share one pool);
the next populated advertised base is a defensive cap. Bit and STRING counts are entries.
| Area | Native | Allowed dataType |
|---|---|---|
MARKER, INPUT, OUTPUT, COUNTER, TIMER |
one byte per Boolean (0/1 only) | Boolean |
BYTE / WORD / DWORD |
signed int8 / int16le / int32le | Int16 (BYTE, WORD only), Int32, Int64 |
INPUT_WORD, OUTPUT_WORD |
uint16le | Int32, Int64 |
STRING |
advertised fixed width, terminated Latin-1 (too wide ⇒ error, never truncated) | String |
Example: PLC:WORD:4999 → R_MB at base + 4999×2. Note that DATA:/PLC/memory/W/9998 uses a native byte
offset — the two address spaces differ (see the wire reference).
DATA bindings DATA:<path> + dataType ∈ Boolean/Int16/Int32/Int64/Float64/String, read via R_DP under the
opt-in DATA role (/→\, "→' normalisation; NUL-free Latin-1; ≤ 242 chars). Value types 2/3/5/8/11/16/17 are
decoded strictly; Boolean accepts 00 and 01/FF (FF observed on real iTNC 530 I/O). Coercion never
truncates or wraps — otherwise BadTypeMismatch.
At most 256 PLC/DATA bindings per control (excess are skipped and reported on /hosts).
Quality
| Condition | Value status / capability |
|---|---|
| Refusal 22/24 | BadNotSupported / Unsupported — suppressed for the session |
| Refusal 23/49 | BadUserAccessDenied / AccessDenied — suppressed for the session, except a provisional denial while the optional DNC login is temporarily failing (retried) |
| Other refusal | BadUnexpectedError / Unknown — retried next poll |
| Malformed complete record (length, terminator, NaN, duplicate axis, …) | BadDecodingError / InvalidData |
| Binding type mismatch | BadTypeMismatch |
| Out-of-region binding, alarm overflow | BadOutOfRange / InvalidData (never a truncated list) |
| Disabled feature (telemetry off, timers off, DATA off) | BadNotSupported / Disabled |
| Unusable optional DNC/DATA credential, or a request the read-only policy refuses | BadConfigurationError / ConfigurationError — that role's reads only; never sent; the session stays up |
| Not yet acquired | BadWaitingForInitialData |
| Transport lost | every remote value of that control BadNoCommunication at once; capabilities CommunicationLost |
There is no cross-poll Good cache: each batch reads the wire; within a batch a shared selector (program, overrides, axes, tool, the whole alarm walk) and aliased custom addresses are read once.
Lifecycle, health and comms loss
- Construction and
InitializeAsyncopen nothing. Acquisition starts on the firstSubscribeAsync/ReadAsync, so the/rawbrowse (universal discovery browser, static catalog,RediscoverPolicy = Once) never opens a session to a production control. - One background loop per control: connect → INSPECT login →
R_VR(required) → optional DNC/DATA logins →R_PRwhen PLC bindings exist → poll the Status/Custom/Slow groups. Each established session is a new generation; a batch returning after its session was retired can never overwrite the outage invalidation. - Reads are cache-only (
ReadAsyncnever touches the wire); subscriptions push on (value, status) change, so a control returning with identical readings still re-publishes Good. - Comms loss → all-value invalidation → bounded exponential reconnect (
Reconnect.*, clamped to 100 ms–10 min). The backoff resets only after a session published a poll batch — a control that accepts login + version and then drops is backed off, not re-dialled everyInitialDelayMs. Unlike the Java base, an initial connect failure also retries (no manual restart). The loop survives any unexpected fault (logged, retired, backed off); JSON-nullconfig sections are normalised to defaults by the parser. - Subscriptions: the initial push and later publications are ordered under one lock, so a subscriber never receives an older value after a newer one. A re-init disposes every control loop first; a late start of a disposed loop is a no-op.
- Health:
Degradedonly while a control's session is down (connect failing / lost), withLastSuccessfulReadfrozen — the conjunction the #527 comms-loss watchdog needs. Per-tag refusals, denials and decode errors are quality, not health (else the watchdog would reconnect-loop a control that merely denies one selector). The reference's poll-group "partial data" aggregate is on the/hostsdiagnostics bag (<host:port>.data=Good/Partial/Lost, plus.stateand.model). Re-initialise tears down every session first (#630).
Test-Connect probe
HeidenhainDriverProbe (registered on admin and driver nodes, with the node's ISecretResolver) opens a real
session to the first device: INSPECT login + R_VR. A bare TCP listener does not read as healthy.
Tests
tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Heidenhain.Tests— in-process LSV2 simulator (Simulator/): a scripted raw-socket peer for framing tests and aSimulatedControlmodel that records every request and flags any non-allowlisted telegram. The Java fixtures' captured iTNC 530 replies (Fixtures/*.properties) are replayed as golden vectors (inspect-only telemetry on two controls; DATA boundary replies on three).Runtime.Tests/Drivers/HeidenhainDriverEndToEndTests— the real driver insideDriverInstanceActor.Configuration.Tests/DraftValidatorHeidenhainTests,AdminUI.Tests/Uns/HeidenhainAuthoringTests+ the fleet parity suites.- LiveIntegration (
--filter Category=LiveIntegration, skipped unlessHEIDENHAIN_LSV2_HOSTis set; optionalHEIDENHAIN_LSV2_PORT,OTOPCUA_HEIDENHAIN_INSPECT_PASSWORD): read-only INSPECT identity/selector/layout survey and a driver end-to-end status poll. Record its output as .NET commissioning evidence.
Hardware-gated — not yet proven
No real control was available for this port. Still open:
- .NET commissioning evidence on a real control (the LiveIntegration gate) — browse/types/arrays through a real OPC UA client, OPC write refusal, network interruption + recovery quality, bounded traffic under load.
- Controller families/versions other than iTNC 530 (TNC 320/430/640) — unproven even in the Java reference.
- Successful raw
R_MBdecoding and its Boolean encoding (denied on all four tested controls). - Physical units of axis positions / tool geometry vs. the HMI; experimental timer semantics (selectors 30–34).
- DNC/DATA permission matrices per control; sustained fleet/load operation.
Deliberate exclusions
Writes of any kind, file upload/download, remote input/keyboard/motion, parameter edits, PLCDEBUG/MONITOR/FILE roles, scope setup, arbitrary requests, buffer-size negotiation, vendor SDK, serial transport, built-in SSH, PLC-wide symbol discovery / memory scanning, OEE mapping, and native alarms as Part 9 conditions (alarms are published as typed arrays).