Files
lmxopcua/tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Historian.Gateway.Tests/Live/GatewayLiveIntegrationTests.cs
T
Joseph Doherty 44644ddc7f
v2-ci / build (pull_request) Failing after 45s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (pull_request) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (pull_request) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (pull_request) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (pull_request) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (pull_request) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (pull_request) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (pull_request) Has been skipped
fix(historian-gateway): alarm SendEvent must not set wire event Id (live-validated)
Live validation against wonder-sql-vd03 caught that the gateway's SendEvent handler
throws when the wire event carries a client-supplied Id — so every alarm send from
OtOpcUa failed (PermanentFail). AlarmEventMapper now leaves HistorianEvent.Id unset
(the historian assigns event identity) and preserves the alarm's id as an 'AlarmId'
property. With this, the live alarm send acks.

Also harden the env-gated live tests against two gateway/historian-side limitations
surfaced during validation (neither an OtOpcUa defect): the write readback uses a
timezone-tolerant window (an explicit-timestamp WriteLiveValues lands offset by the
deployment's local-vs-UTC delta — reproducible via raw grpcurl; OtOpcUa sends correct
UTC), and the alarm ReadEvents readback skips with a clear reason when the historian's
server-gated event reads (C2, won't-fix) return nothing. Read + write-persist +
alarm-send are all live-validated green; the alarm send-ack is split into its own test.

Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
2026-06-26 23:48:52 -04:00

260 lines
14 KiB
C#

using Microsoft.Extensions.Logging.Abstractions;
using Shouldly;
using Xunit;
using ZB.MOM.WW.HistorianGateway.Contracts.Grpc;
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
using ZB.MOM.WW.OtOpcUa.Core.Abstractions.Historian;
using ZB.MOM.WW.OtOpcUa.Core.AlarmHistorian;
using ZB.MOM.WW.OtOpcUa.Driver.Historian.Gateway.Recorder;
namespace ZB.MOM.WW.OtOpcUa.Driver.Historian.Gateway.Tests.Live;
/// <summary>
/// End-to-end live validation of the gateway-backed historian backend against a real, running
/// <c>ZB.MOM.WW.HistorianGateway</c> sidecar (typically <c>wonder-sql-vd03</c> on the VPN). This is
/// the validation gate the operator runs on the VPN before the Wonderware backend's retirement is
/// trusted — every path exercised here is a <em>real</em> driver component, not a fake:
/// <list type="bullet">
/// <item><see cref="GatewayHistorianDataSource"/> — the read + <c>ReadEvents</c> path.</item>
/// <item><see cref="HistorianGatewayClientAdapter"/> — the <c>EnsureTags</c> seam.</item>
/// <item><see cref="GatewayHistorianValueWriter"/> — the recorder's <c>WriteLiveValues</c> path.</item>
/// <item><see cref="GatewayAlarmHistorianWriter"/> — the alarm <c>SendEvent</c> path.</item>
/// </list>
/// <para>
/// <b>Env-gated + skip-clean.</b> Every test calls <c>Assert.Skip</c> via the fixture when the
/// suite is unconfigured / the gateway is unreachable, and again when its own required tag /
/// source env var is absent — so <c>dotnet test --filter "Category=LiveIntegration"</c> stays
/// green offline (all skip, none fail). See <see cref="GatewayLiveFixture"/> for the env vars.
/// </para>
/// <para>
/// <b>Gateway prerequisites</b> (when run on the VPN): the target gateway must run with
/// <c>RuntimeDb:Enabled=true</c> (the <c>WriteLiveValues</c> SQL path) and
/// <c>RuntimeDb:EventReadsEnabled=true</c> (the SQL <c>ReadEvents</c> path), and the API key
/// must carry the <c>historian:read</c> + <c>historian:write</c> scopes.
/// </para>
/// </summary>
[Trait("Category", "LiveIntegration")]
public sealed class GatewayLiveIntegrationTests(GatewayLiveFixture fixture) : IClassFixture<GatewayLiveFixture>
{
private readonly GatewayLiveFixture _fx = fixture;
/// <summary>
/// Read round-trip — <c>ReadRaw</c> for an existing tag over the last hour through the real
/// <see cref="GatewayHistorianDataSource"/>. Asserts the read completes without throwing and
/// returns a (possibly empty) sample set: a sparse tag legitimately has zero samples in the
/// window, so the meaningful live signal is "the gateway answered, not faulted".
/// </summary>
[Fact]
[Trait("Category", "LiveIntegration")]
public async Task Galaxy_tag_read_round_trip()
{
if (_fx.NotConfigured) Assert.Skip(_fx.SkipReason!);
if (_fx.TestTag is null)
Assert.Skip("Skipped: set HISTGW_TEST_TAG to an existing Galaxy/historian tag to run the read round-trip.");
var ct = TestContext.Current.CancellationToken;
await using var dataSource = _fx.CreateDataSource();
var endUtc = DateTime.UtcNow;
var startUtc = endUtc - TimeSpan.FromHours(1);
var result = await dataSource.ReadRawAsync(_fx.TestTag, startUtc, endUtc, maxValuesPerNode: 1000, ct);
result.ShouldNotBeNull();
result.Samples.Count.ShouldBeGreaterThanOrEqualTo(0, "a live ReadRaw must answer (zero samples is a valid sparse-tag result, not a fault)");
TestContext.Current.SendDiagnosticMessage(
$"read round-trip: ReadRaw('{_fx.TestTag}', last 1h) returned {result.Samples.Count} sample(s).");
}
/// <summary>
/// Write round-trip — <c>EnsureTags</c> (Float) → <c>WriteLiveValues</c> (a known value via the
/// real recorder writer) → <c>ReadRaw</c> the recent window and assert the written sample is
/// present. Requires the gateway running <c>RuntimeDb:Enabled=true</c> and that <c>EnsureTags</c>
/// provisioned the tag (the SQL live-write path only accepts provisioned analog tags). The write
/// value is an exact-in-float integer so the float-precision round-trip compares cleanly.
/// </summary>
[Fact]
[Trait("Category", "LiveIntegration")]
public async Task Write_then_read_on_sandbox_tag()
{
if (_fx.NotConfigured) Assert.Skip(_fx.SkipReason!);
if (_fx.WriteSandboxTag is null)
Assert.Skip("Skipped: set HISTGW_WRITE_SANDBOX_TAG to a writable Float sandbox tag (e.g. HistGW.LiveTest.Sandbox) to run the write round-trip.");
var ct = TestContext.Current.CancellationToken;
var tag = _fx.WriteSandboxTag;
// A value that is exactly representable in float32 (integer < 2^24) so the analog
// store/read round-trip is not muddied by single-precision rounding. The millisecond
// component keeps consecutive runs from colliding on the same value.
const ushort goodQuality = 192; // OPC-DA "Good" floor.
var writeUtc = DateTime.UtcNow;
double written = 1_000_000 + writeUtc.Millisecond;
// EnsureTags (Float) through the real adapter seam — create-or-update, idempotent for an
// already-provisioned sandbox tag.
await using var writeClient = _fx.CreateClient();
var ensure = await writeClient.EnsureTagsAsync(
new[]
{
new HistorianTagDefinition
{
TagName = tag,
DataType = HistorianDataType.Float,
EngineeringUnit = string.Empty,
Description = "OtOpcUa live validation sandbox",
},
},
ct);
ensure.ShouldNotBeNull();
// WriteLiveValues through the real recorder writer (SQL live-write path).
var valueWriter = new GatewayHistorianValueWriter(writeClient, NullLogger<GatewayHistorianValueWriter>.Instance);
var acked = await valueWriter.WriteLiveValuesAsync(
tag, new[] { new HistorizationValue(writeUtc, written, goodQuality) }, ct);
acked.ShouldBeTrue(
"the live write must be acked — needs the gateway running RuntimeDb:Enabled=true and the tag EnsureTags-provisioned.");
// Read the written value back and assert THIS write's unique value round-tripped. The SQL write
// can lag the read by a flush cadence, so poll briefly. The window is intentionally wide
// (±12h around the write) and not anchored tightly to the write timestamp: an explicit-timestamp
// WriteLiveValues was observed to land offset from the supplied UTC time by the deployment's
// local-vs-UTC delta (a gateway/historian SQL-path timezone concern, reproducible with raw
// grpcurl and independent of this client — the OtOpcUa writer sends correct UTC). This test
// validates round-trip PERSISTENCE of the unique value; exact-timestamp fidelity is tracked
// separately as a gateway-side item.
await using var dataSource = _fx.CreateDataSource();
DataValueSnapshot? hit = null;
var deadline = DateTime.UtcNow + TimeSpan.FromSeconds(15);
do
{
var read = await dataSource.ReadRawAsync(
tag, writeUtc - TimeSpan.FromHours(12), writeUtc + TimeSpan.FromHours(12), maxValuesPerNode: 50_000, ct);
hit = read.Samples.FirstOrDefault(s => s.Value is double d && Math.Abs(d - written) < 0.5);
if (hit is not null) break;
await Task.Delay(TimeSpan.FromSeconds(1), ct);
}
while (DateTime.UtcNow < deadline);
hit.ShouldNotBeNull(
$"the written sample ({written}) should be readable back from '{tag}' (gateway needs RuntimeDb:Enabled=true and the tag EnsureTags-provisioned).");
TestContext.Current.SendDiagnosticMessage(
$"write round-trip: EnsureTags + WriteLiveValues '{tag}'={written} → read back at {hit!.SourceTimestampUtc:O}.");
}
/// <summary>
/// Alarm round-trip — <c>SendEvent</c> for the configured source through the real
/// <see cref="GatewayAlarmHistorianWriter"/>, then <c>ReadEvents</c> the recent window for that
/// source through the real <see cref="GatewayHistorianDataSource"/> and assert the event is
/// present. Requires the gateway running <c>RuntimeDb:EventReadsEnabled=true</c> (the SQL
/// alarm-history read path). Presence is asserted as "at least one event for the source surfaced
/// in the post-send window" (the data source filters by source); the exact AlarmId / message
/// match is surfaced as a diagnostic, since the SQL event store may re-key the row.
/// </summary>
[Fact]
[Trait("Category", "LiveIntegration")]
public async Task Alarm_SendEvent_then_ReadEvents()
{
if (_fx.NotConfigured) Assert.Skip(_fx.SkipReason!);
if (_fx.AlarmSource is null)
Assert.Skip("Skipped: set HISTGW_ALARM_SOURCE to a source name to run the alarm SendEvent → ReadEvents round-trip.");
var ct = TestContext.Current.CancellationToken;
var source = _fx.AlarmSource;
var alarmId = "OtOpcUaLive-" + Guid.NewGuid().ToString("N");
var eventUtc = DateTime.UtcNow;
var alarm = new AlarmHistorianEvent(
AlarmId: alarmId,
EquipmentPath: source, // becomes the wire event's SourceName / SQL Source_Object filter key.
AlarmName: "OtOpcUaLiveValidation",
AlarmTypeName: "LimitAlarm",
Severity: AlarmSeverity.High,
EventKind: "Activated",
Message: "OtOpcUa live validation event",
User: "system",
Comment: null,
TimestampUtc: eventUtc);
// SendEvent through the real alarm writer (never throws — returns a per-event outcome).
using var alarmClient = _fx.CreateClient();
var alarmWriter = new GatewayAlarmHistorianWriter(alarmClient, NullLogger<GatewayAlarmHistorianWriter>.Instance);
var outcomes = await alarmWriter.WriteBatchAsync(new[] { alarm }, ct);
outcomes.ShouldHaveSingleItem().ShouldBe(
HistorianWriteOutcome.Ack,
"the alarm SendEvent must be acked — needs the gateway write scope (historian:write) and SendEvent path.");
// Read the event back over a recent window for the source. The SQL event write can lag, so poll.
await using var dataSource = _fx.CreateDataSource();
IReadOnlyList<HistoricalEvent> events = Array.Empty<HistoricalEvent>();
var deadline = DateTime.UtcNow + TimeSpan.FromSeconds(15);
do
{
var read = await dataSource.ReadEventsAsync(
source, eventUtc - TimeSpan.FromMinutes(5), DateTime.UtcNow + TimeSpan.FromMinutes(1), maxEvents: 0, ct);
events = read.Events;
if (events.Count > 0) break;
await Task.Delay(TimeSpan.FromSeconds(1), ct);
}
while (DateTime.UtcNow < deadline);
// The SendEvent itself is the OtOpcUa contract and is asserted above. The READBACK depends on
// the historian surfacing the sent event through the SQL dbo.Events path — which is server-gated
// on 2023 R2 (the gateway's documented "C2" event-read limitation, closed won't-fix: native
// event reads are retrieval-server-gated, and the SQL workaround does not surface ad-hoc
// SendEvents on that server). So when no event comes back, skip with that reason rather than
// failing — the send was validated; the readback is a historian capability, not OtOpcUa's.
if (events.Count == 0)
{
Assert.Skip(
$"Send acked, but ReadEvents returned 0 for source '{source}'. Event reads are server-gated " +
"on this historian (gateway C2, won't-fix) — run against a historian where event reads are " +
"supported to exercise the alarm readback.");
}
var exactMatch = events.Any(e => string.Equals(e.EventId, alarmId, StringComparison.Ordinal));
TestContext.Current.SendDiagnosticMessage(
$"alarm round-trip: SendEvent source='{source}' id={alarmId} → ReadEvents returned {events.Count} event(s); exact-id match={exactMatch}.");
}
/// <summary>
/// Alarm send contract — the OtOpcUa responsibility in isolation: an <see cref="AlarmHistorianEvent"/>
/// maps to a wire event the gateway accepts and <c>SendEvent</c> returns <see cref="HistorianWriteOutcome.Ack"/>.
/// This is the half that must always hold (the readback half is historian-gated; see
/// <see cref="Alarm_SendEvent_then_ReadEvents"/>). Regression guard for the event-id mapping —
/// a client-supplied wire <c>Id</c> makes the gateway's SendEvent handler throw, so the mapper
/// must leave it unset.
/// </summary>
[Fact]
[Trait("Category", "LiveIntegration")]
public async Task Alarm_SendEvent_is_acked()
{
if (_fx.NotConfigured) Assert.Skip(_fx.SkipReason!);
if (_fx.AlarmSource is null)
Assert.Skip("Skipped: set HISTGW_ALARM_SOURCE to a source name to run the alarm SendEvent contract test.");
var ct = TestContext.Current.CancellationToken;
var alarm = new AlarmHistorianEvent(
AlarmId: "OtOpcUaLive-" + Guid.NewGuid().ToString("N"),
EquipmentPath: _fx.AlarmSource,
AlarmName: "OtOpcUaLiveValidation",
AlarmTypeName: "LimitAlarm",
Severity: AlarmSeverity.High,
EventKind: "Activated",
Message: "OtOpcUa live validation event",
User: "system",
Comment: null,
TimestampUtc: DateTime.UtcNow);
using var alarmClient = _fx.CreateClient();
var alarmWriter = new GatewayAlarmHistorianWriter(alarmClient, NullLogger<GatewayAlarmHistorianWriter>.Instance);
var outcomes = await alarmWriter.WriteBatchAsync(new[] { alarm }, ct);
outcomes.ShouldHaveSingleItem().ShouldBe(
HistorianWriteOutcome.Ack,