AB Legacy — DH+ via 1756-DHRIO bridging
PR ablegacy-13 / #256. The AB Legacy driver can address a PLC-5 sitting on a DH+ link by routing CIP requests through a 1756-DHRIO module installed in a ControlLogix chassis. This is the canonical way to keep an installed-base PLC-5 fleet alive after the chassis- level migration to ControlLogix; the DHRIO module exposes a DH+ "side" that talks to the legacy PLC-5 / SLC-DH+ peers and a backplane "side" that the ControlLogix CPU + Ethernet bridge can route through.
Wire layout
OtOpcUa server ──EtherNet/IP──► 1756-EN2T (slot 0) ──backplane──► 1756-DHRIO (slot N) ──DH+──► PLC-5
Two CIP hops:
- Backplane — port
1, slot<N>(the slot the DHRIO module lives in). - DH+ — port
2, station<S>(the DH+ node address of the target PLC-5, in octal).
Resulting CIP path: 1,<N>,2,<S>.
The first port
1is always the backplane; port2is the DH+ side of the 1756-DHRIO module. This mirrors the convention Rockwell uses in RSLinx + RSLogix 5.
Octal station number
The DH+ network was specified with octal node addresses. Rockwell tooling
displays them in octal too (RSLogix 5 → "DH+ Node Address" field on the
controller properties dialog). The driver follows suit — the station segment
of the CIP path must be parsed as octal (digits 0..7 only; 8, 9, and
multi-byte garbage are rejected).
DH+ addresses run 0..77 octal == 0..63 decimal. Quick reference:
| Octal | Decimal | Octal | Decimal | Octal | Decimal | Octal | Decimal |
|---|---|---|---|---|---|---|---|
| 00 | 0 | 20 | 16 | 40 | 32 | 60 | 48 |
| 01 | 1 | 21 | 17 | 41 | 33 | 61 | 49 |
| 02 | 2 | 22 | 18 | 42 | 34 | 62 | 50 |
| 03 | 3 | 23 | 19 | 43 | 35 | 63 | 51 |
| 04 | 4 | 24 | 20 | 44 | 36 | 64 | 52 |
| 05 | 5 | 25 | 21 | 45 | 37 | 65 | 53 |
| 06 | 6 | 26 | 22 | 46 | 38 | 66 | 54 |
| 07 | 7 | 27 | 23 | 47 | 39 | 67 | 55 |
| 10 | 8 | 30 | 24 | 50 | 40 | 70 | 56 |
| 11 | 9 | 31 | 25 | 51 | 41 | 71 | 57 |
| 12 | 10 | 32 | 26 | 52 | 42 | 72 | 58 |
| 13 | 11 | 33 | 27 | 53 | 43 | 73 | 59 |
| 14 | 12 | 34 | 28 | 54 | 44 | 74 | 60 |
| 15 | 13 | 35 | 29 | 55 | 45 | 75 | 61 |
| 16 | 14 | 36 | 30 | 56 | 46 | 76 | 62 |
| 17 | 15 | 37 | 31 | 57 | 47 | 77 | 63 |
Anything past 77 octal (i.e. decimal > 63) is invalid on a real DH+ network
and rejected by the parser.
PLC-5 only
DHRIO bridging is PLC-5-only. The driver enforces this at
AbLegacyDriver.InitializeAsync time: a DH+ bridge path combined with
PlcFamily=Slc500 / MicroLogix / LogixPccc throws
InvalidOperationException("DHRIO bridging is PLC-5-only") immediately rather
than letting reads silently fail with BadCommunicationError on the wire.
Background: the 1756-DHRIO module only speaks DH+ to PLC-5 / SLC-DH+ peers, and libplctag's PCCC stack only exposes the PLC-5 side. SLC 5/04 boxes on DH+ can be physically reached through a DHRIO module, but the protocol stack needed to drive them isn't exposed by libplctag — out of scope for this driver.
CLI worked example
PLC-5 at DH+ node 07 (octal == 7 decimal), DHRIO module in slot 3, gateway
192.168.1.10:
otopcua-ablegacy-cli probe `
-g ab://192.168.1.10/1,3,2,07 `
-P Plc5 `
-a N7:0
# Read N7:10 from the PLC-5 across the DHRIO bridge
otopcua-ablegacy-cli read `
-g ab://192.168.1.10/1,3,2,07 `
-P Plc5 `
-a N7:10 `
-t Int
The driver surfaces the parsed bridge form on the host-address record:
BackplaneSlot=3, DhPlusPort=2, DhPlusStation=7 (decimal-translated). Use
those values when reading driver-diagnostics output to confirm the bridge was
recognised — a non-bridge CIP path leaves all three fields null.
Manual smoke procedure
There is no automated end-to-end coverage for DH+ bridging because the only
path to wire-level validation is real hardware (libplctag's ab_server Docker
image doesn't simulate the DHRIO + DH+ + PLC-5 stack). The unit-test layer
covers parser positive / negative cases.
Hardware smoke checklist:
-
Confirm the 1756-DHRIO module is present in the target ControlLogix chassis. RSLinx Classic should show
DH+, 1under the chassis tree with the PLC-5 nodes enumerated underneath. -
Note the DHRIO module's slot number (the
<N>in1,<N>,2,<S>). -
Note the target PLC-5's DH+ node address — read it off the front-panel switch bank, or the controller properties in RSLogix 5. Read it as octal.
-
From an OtOpcUa box that can reach the EtherNet/IP gateway:
otopcua-ablegacy-cli probe -g ab://<gateway>/1,<slot>,2,<station-octal> -P Plc5 -a S:0S:0(status file word 0) is non-destructive and present on every PLC-5. -
If the probe succeeds, exercise an N file read against a known non-zero address. Compare against the value displayed in RSLogix 5 → Online → Data → N7.
If the probe fails with BadCommunicationError:
- Wrong slot number — re-check via RSLinx.
- Wrong octal node — convert from RSLogix 5's display value (already octal); a decimal-thinking conversion mistake is the most common smoke failure.
- DHRIO module's DH+ baud rate doesn't match the PLC-5's switch setting (57.6k / 115.2k / 230.4k) — driver-side problem this can't paper over.
- A scanner on the DHRIO is in scheduled-mode and starving unscheduled PCCC traffic — bump the DHRIO's unscheduled-message slice in RSLogix 5000.
See also
Driver.AbLegacy.Cli.md— the family / CIP-path cheat sheet now carries a DHRIO row.drivers/AbLegacy-Test-Fixture.md— DH+ bridging is unit-only; no Docker fixture supports it.