Renames all 11 projects (5 src + 6 tests), the .slnx solution file, all source-file namespaces, all axaml namespace references, and all v1 documentation references in CLAUDE.md and docs/*.md (excluding docs/v2/ which is already in OtOpcUa form). Also updates the TopShelf service registration name from "LmxOpcUa" to "OtOpcUa" per Phase 0 Task 0.6.
Preserves runtime identifiers per Phase 0 Out-of-Scope rules to avoid breaking v1/v2 client trust during coexistence: OPC UA `ApplicationUri` defaults (`urn:{GalaxyName}:LmxOpcUa`), server `EndpointPath` (`/LmxOpcUa`), `ServerName` default (feeds cert subject CN), `MxAccessConfiguration.ClientName` default (defensive — stays "LmxOpcUa" for MxAccess audit-trail consistency), client OPC UA identifiers (`ApplicationName = "LmxOpcUaClient"`, `ApplicationUri = "urn:localhost:LmxOpcUaClient"`, cert directory `%LocalAppData%\LmxOpcUaClient\pki\`), and the `LmxOpcUaServer` class name (class rename out of Phase 0 scope per Task 0.5 sed pattern; happens in Phase 1 alongside `LmxNodeManager → GenericDriverNodeManager` Core extraction). 23 LmxOpcUa references retained, all enumerated and justified in `docs/v2/implementation/exit-gate-phase-0.md`.
Build clean: 0 errors, 30 warnings (lower than baseline 167). Tests at strict improvement over baseline: 821 passing / 1 failing vs baseline 820 / 2 (one flaky pre-existing failure passed this run; the other still fails — both pre-existing and unrelated to the rename). `Client.UI.Tests`, `Historian.Aveva.Tests`, `Client.Shared.Tests`, `IntegrationTests` all match baseline exactly. Exit gate compliance results recorded in `docs/v2/implementation/exit-gate-phase-0.md` with all 7 checks PASS or DEFERRED-to-PR-review (#7 service install verification needs Windows service permissions on the reviewer's box).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
166 lines
6.7 KiB
C#
166 lines
6.7 KiB
C#
using System.Collections.Generic;
|
|
using System.Threading.Tasks;
|
|
using Opc.Ua;
|
|
using Shouldly;
|
|
using Xunit;
|
|
using ZB.MOM.WW.OtOpcUa.Host.Domain;
|
|
using ZB.MOM.WW.OtOpcUa.Tests.Helpers;
|
|
|
|
namespace ZB.MOM.WW.OtOpcUa.Tests.Integration
|
|
{
|
|
public class AccessLevelTests
|
|
{
|
|
private static FakeGalaxyRepository CreateRepoWithSecurityLevels()
|
|
{
|
|
return new FakeGalaxyRepository
|
|
{
|
|
Hierarchy = new List<GalaxyObjectInfo>
|
|
{
|
|
new()
|
|
{
|
|
GobjectId = 1, TagName = "TestObj", BrowseName = "TestObj", ParentGobjectId = 0, IsArea = false
|
|
}
|
|
},
|
|
Attributes = new List<GalaxyAttributeInfo>
|
|
{
|
|
new()
|
|
{
|
|
GobjectId = 1, TagName = "TestObj", AttributeName = "FreeAttr",
|
|
FullTagReference = "TestObj.FreeAttr", MxDataType = 5, SecurityClassification = 0
|
|
},
|
|
new()
|
|
{
|
|
GobjectId = 1, TagName = "TestObj", AttributeName = "OperateAttr",
|
|
FullTagReference = "TestObj.OperateAttr", MxDataType = 5, SecurityClassification = 1
|
|
},
|
|
new()
|
|
{
|
|
GobjectId = 1, TagName = "TestObj", AttributeName = "SecuredAttr",
|
|
FullTagReference = "TestObj.SecuredAttr", MxDataType = 5, SecurityClassification = 2
|
|
},
|
|
new()
|
|
{
|
|
GobjectId = 1, TagName = "TestObj", AttributeName = "VerifiedAttr",
|
|
FullTagReference = "TestObj.VerifiedAttr", MxDataType = 5, SecurityClassification = 3
|
|
},
|
|
new()
|
|
{
|
|
GobjectId = 1, TagName = "TestObj", AttributeName = "TuneAttr",
|
|
FullTagReference = "TestObj.TuneAttr", MxDataType = 5, SecurityClassification = 4
|
|
},
|
|
new()
|
|
{
|
|
GobjectId = 1, TagName = "TestObj", AttributeName = "ConfigAttr",
|
|
FullTagReference = "TestObj.ConfigAttr", MxDataType = 5, SecurityClassification = 5
|
|
},
|
|
new()
|
|
{
|
|
GobjectId = 1, TagName = "TestObj", AttributeName = "ViewOnlyAttr",
|
|
FullTagReference = "TestObj.ViewOnlyAttr", MxDataType = 5, SecurityClassification = 6
|
|
}
|
|
}
|
|
};
|
|
}
|
|
|
|
/// <summary>
|
|
/// Verifies that writable Galaxy security classifications publish OPC UA variables with read-write access.
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task ReadWriteAttribute_HasCurrentReadOrWrite_AccessLevel()
|
|
{
|
|
var fixture = OpcUaServerFixture.WithFakeMxAccessClient(repo: CreateRepoWithSecurityLevels());
|
|
await fixture.InitializeAsync();
|
|
try
|
|
{
|
|
using var client = new OpcUaTestClient();
|
|
await client.ConnectAsync(fixture.EndpointUrl);
|
|
|
|
foreach (var attrName in new[] { "FreeAttr", "OperateAttr", "TuneAttr", "ConfigAttr" })
|
|
{
|
|
var nodeId = client.MakeNodeId($"TestObj.{attrName}");
|
|
var accessLevel = client.ReadAttribute(nodeId, Attributes.AccessLevel);
|
|
((byte)accessLevel.Value).ShouldBe(AccessLevels.CurrentReadOrWrite,
|
|
$"{attrName} should be ReadWrite");
|
|
}
|
|
}
|
|
finally
|
|
{
|
|
await fixture.DisposeAsync();
|
|
}
|
|
}
|
|
|
|
/// <summary>
|
|
/// Verifies that secured and view-only Galaxy classifications publish OPC UA variables with read-only access.
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task ReadOnlyAttribute_HasCurrentRead_AccessLevel()
|
|
{
|
|
var fixture = OpcUaServerFixture.WithFakeMxAccessClient(repo: CreateRepoWithSecurityLevels());
|
|
await fixture.InitializeAsync();
|
|
try
|
|
{
|
|
using var client = new OpcUaTestClient();
|
|
await client.ConnectAsync(fixture.EndpointUrl);
|
|
|
|
foreach (var attrName in new[] { "SecuredAttr", "VerifiedAttr", "ViewOnlyAttr" })
|
|
{
|
|
var nodeId = client.MakeNodeId($"TestObj.{attrName}");
|
|
var accessLevel = client.ReadAttribute(nodeId, Attributes.AccessLevel);
|
|
((byte)accessLevel.Value).ShouldBe(AccessLevels.CurrentRead,
|
|
$"{attrName} should be ReadOnly");
|
|
}
|
|
}
|
|
finally
|
|
{
|
|
await fixture.DisposeAsync();
|
|
}
|
|
}
|
|
|
|
/// <summary>
|
|
/// Verifies that the bridge rejects writes against Galaxy attributes whose security classification is read-only.
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task Write_ToReadOnlyAttribute_IsRejected()
|
|
{
|
|
var fixture = OpcUaServerFixture.WithFakeMxAccessClient(repo: CreateRepoWithSecurityLevels());
|
|
await fixture.InitializeAsync();
|
|
try
|
|
{
|
|
using var client = new OpcUaTestClient();
|
|
await client.ConnectAsync(fixture.EndpointUrl);
|
|
|
|
var nodeId = client.MakeNodeId("TestObj.ViewOnlyAttr");
|
|
var result = client.Write(nodeId, "test");
|
|
StatusCode.IsBad(result).ShouldBeTrue("Write to ReadOnly attribute should be rejected");
|
|
}
|
|
finally
|
|
{
|
|
await fixture.DisposeAsync();
|
|
}
|
|
}
|
|
|
|
/// <summary>
|
|
/// Verifies that writes succeed for Galaxy attributes whose security classification permits operator updates.
|
|
/// </summary>
|
|
[Fact]
|
|
public async Task Write_ToReadWriteAttribute_Succeeds()
|
|
{
|
|
var mxClient = new FakeMxAccessClient();
|
|
var fixture = OpcUaServerFixture.WithFakeMxAccessClient(mxClient, CreateRepoWithSecurityLevels());
|
|
await fixture.InitializeAsync();
|
|
try
|
|
{
|
|
using var client = new OpcUaTestClient();
|
|
await client.ConnectAsync(fixture.EndpointUrl);
|
|
|
|
var nodeId = client.MakeNodeId("TestObj.OperateAttr");
|
|
var result = client.Write(nodeId, "test");
|
|
StatusCode.IsGood(result).ShouldBeTrue("Write to ReadWrite attribute should succeed");
|
|
}
|
|
finally
|
|
{
|
|
await fixture.DisposeAsync();
|
|
}
|
|
}
|
|
}
|
|
} |