Joseph Doherty
2b5222f5db
Phase 3 PR 47 -- DL205 V-memory octal-address helper. Adds DirectLogicAddress static class with two entry points: UserVMemoryToPdu(string) parses a DirectLOGIC V-address (V-prefixed or bare, whitespace tolerated) as OCTAL and returns the 0-based Modbus PDU address. V2000 octal = decimal 1024 = PDU 0x0400, which is the canonical start of the user V-memory bank on DL205/DL260. SystemVMemoryBasePdu + SystemVMemoryToPdu(ushort offset) handle the system bank (V40400 and up) which does NOT follow the simple octal-to-decimal formula -- the CPU relocates the system bank to PDU 0x2100 in H2-ECOM100 absolute mode. A naive caller converting 40400 octal would land at PDU 0x4100 (decimal 16640) and miss the system registers entirely; the helper routes the correct 0x2100 base. Why this matters: DirectLOGIC operators think in OCTAL (the ladder-logic editor, the Productivity/Do-more UI, every AutomationDirect manual addresses V-memory octally) while the Modbus wire is DECIMAL. Integrators routinely copy V-addresses from the PLC documentation into client configs and read garbage because they treated V2000 as decimal 2000 (HR[2000] = 0 in the dl205 sim, zero in most PLCs). The helper makes the translation explicit per the D2-USER-M appendix + H2-ECOM-M \u00A76.5 references cited in docs/v2/dl205.md. Unit tests: UserVMemoryToPdu_converts_octal_V_prefix (V0, V1, V7, V10, V2000, V7777, V10000, V17777 -- the exact sweep documented in dl205.md), UserVMemoryToPdu_accepts_bare_or_prefixed_or_padded (case + whitespace tolerance), UserVMemoryToPdu_rejects_non_octal_digits (V8/V19/V2009 must throw ArgumentException with 'octal' in the message -- .NET has no base-8 int.Parse so we hand-walk digits to catch 8/9 instead of silently accepting them), UserVMemoryToPdu_rejects_empty_input, UserVMemoryToPdu_overflow_rejected (200000 octal = 0x10000 overflows ushort), SystemVMemoryBasePdu_is_0x2100_for_V40400, SystemVMemoryToPdu_offsets_within_bank, SystemVMemoryToPdu_rejects_overflow. 23/23 Modbus.Tests pass. Integration tests against dl205.json pymodbus profile: DL205_V2000_user_memory_resolves_to_PDU_0x0400_marker (reads HR[0x0400]=0x2000), DL205_V40400_system_memory_resolves_to_PDU_0x2100_marker (reads HR[0x2100]=0x4040). 5/5 DL205 integration tests pass. Caller opts into the helper per tag by calling DirectLogicAddress.UserVMemoryToPdu("V2000") as the ModbusTagDefinition Address -- no driver-wide "DL205 mode" flag needed, because users mix DL and non-DL tags in a single driver instance all the time.
2026-04-18 21:49:58 -04:00
..
DirectLogicAddress.cs
Phase 3 PR 47 -- DL205 V-memory octal-address helper. Adds DirectLogicAddress static class with two entry points: UserVMemoryToPdu(string) parses a DirectLOGIC V-address (V-prefixed or bare, whitespace tolerated) as OCTAL and returns the 0-based Modbus PDU address. V2000 octal = decimal 1024 = PDU 0x0400, which is the canonical start of the user V-memory bank on DL205/DL260. SystemVMemoryBasePdu + SystemVMemoryToPdu(ushort offset) handle the system bank (V40400 and up) which does NOT follow the simple octal-to-decimal formula -- the CPU relocates the system bank to PDU 0x2100 in H2-ECOM100 absolute mode. A naive caller converting 40400 octal would land at PDU 0x4100 (decimal 16640) and miss the system registers entirely; the helper routes the correct 0x2100 base. Why this matters: DirectLOGIC operators think in OCTAL (the ladder-logic editor, the Productivity/Do-more UI, every AutomationDirect manual addresses V-memory octally) while the Modbus wire is DECIMAL. Integrators routinely copy V-addresses from the PLC documentation into client configs and read garbage because they treated V2000 as decimal 2000 (HR[2000] = 0 in the dl205 sim, zero in most PLCs). The helper makes the translation explicit per the D2-USER-M appendix + H2-ECOM-M \u00A76.5 references cited in docs/v2/dl205.md. Unit tests: UserVMemoryToPdu_converts_octal_V_prefix (V0, V1, V7, V10, V2000, V7777, V10000, V17777 -- the exact sweep documented in dl205.md), UserVMemoryToPdu_accepts_bare_or_prefixed_or_padded (case + whitespace tolerance), UserVMemoryToPdu_rejects_non_octal_digits (V8/V19/V2009 must throw ArgumentException with 'octal' in the message -- .NET has no base-8 int.Parse so we hand-walk digits to catch 8/9 instead of silently accepting them), UserVMemoryToPdu_rejects_empty_input, UserVMemoryToPdu_overflow_rejected (200000 octal = 0x10000 overflows ushort), SystemVMemoryBasePdu_is_0x2100_for_V40400, SystemVMemoryToPdu_offsets_within_bank, SystemVMemoryToPdu_rejects_overflow. 23/23 Modbus.Tests pass. Integration tests against dl205.json pymodbus profile: DL205_V2000_user_memory_resolves_to_PDU_0x0400_marker (reads HR[0x0400]=0x2000), DL205_V40400_system_memory_resolves_to_PDU_0x2100_marker (reads HR[0x2100]=0x4040). 5/5 DL205 integration tests pass. Caller opts into the helper per tag by calling DirectLogicAddress.UserVMemoryToPdu("V2000") as the ModbusTagDefinition Address -- no driver-wide "DL205 mode" flag needed, because users mix DL and non-DL tags in a single driver instance all the time.
2026-04-18 21:49:58 -04:00
IModbusTransport.cs
Phase 3 PR 21 — Modbus TCP driver: first native-protocol greenfield for v2. New src/Driver.Modbus project with ModbusDriver implementing IDriver + ITagDiscovery + IReadable + IWritable. Validates the driver-agnostic abstractions (IAddressSpaceBuilder, DriverAttributeInfo, DataValueSnapshot, WriteRequest/WriteResult) generalize beyond Galaxy — nothing Galaxy-specific is used here. ModbusDriverOptions carries Host/Port/UnitId/Timeout + a pre-declared tag list (Modbus has no discovery protocol — tags are configuration). IModbusTransport abstracts the socket layer so tests swap in-memory fakes; concrete ModbusTcpTransport speaks the MBAP ADU (TxId + Protocol=0 + Length + UnitId + PDU) over TcpClient, serializes requests through a semaphore for single-flight in-order responses, validates the response TxId matches, surfaces server exception PDUs as ModbusException with function code + exception code. DiscoverAsync streams one folder per driver with a BaseDataVariable per tag + DriverAttributeInfo that flags writable tags as SecurityClassification.Operate vs ViewOnly for read-only regions. ReadAsync routes per-tag by ModbusRegion: FC01 for Coils, FC02 for DiscreteInputs, FC03 for HoldingRegisters, FC04 for InputRegisters; register values decoded through System.Buffers.Binary.BinaryPrimitives (BigEndian for single-register Int16/UInt16 + two-register Int32/UInt32/Float32 per standard modbus word-swap conventions). WriteAsync uses FC05 (Write Single Coil with 0xFF00/0x0000 encoding) for booleans, FC06 (Write Single Register) for 16-bit types, FC16 (Write Multiple Registers) for 32-bit types. Unknown tag → BadNodeIdUnknown; write to InputRegister or DiscreteInput or Writable=false tag → BadNotWritable; exception during transport → BadInternalError + driver health Degraded. Subscriptions + Historian + Alarms deliberately out of scope — Modbus has no push model (subscribe would be a polling overlay, additive PR) and no history/alarm semantics at the protocol level. Tests (9 new ModbusDriverTests): InitializeAsync connects + populates the tag map + sets health=Healthy; Read Int16 from HoldingRegister returns BigEndian value; Read Float32 spans two registers BigEndian (IEEE 754 single for 25.5f round-trips exactly); Read Coil returns boolean from the bit-packed response; unknown tag name returns BadNodeIdUnknown without an exception; Write UInt16 round-trips via FC06; Write Float32 uses FC16 (two-register write verified by decoding back through the fake register bank); Write to InputRegister returns BadNotWritable; Discover streams one folder + one variable per tag with correct DriverDataType mapping (Int16/Int32→Int32, UInt16/UInt32→Int32, Float32→Float32, Bool→Boolean). FakeTransport simulates a 256-register/256-coil bank + implements the 7 function codes the driver uses. slnx updated with the new src + tests entries. Full solution post-add: 0 errors, 189 tests pass (9 Modbus + 180 pre-existing). IDriver abstraction validated against a fundamentally different protocol — Modbus TCP has no AlarmExtension, no ScanState, no IPC boundary, no historian, no LDAP — and the same builder/reader/writer contract plugged straight in. Future PRs on this driver: ISubscribable via a polling loop, IHostConnectivityProbe for dead-device detection, PLC-specific data-type extensions (Int64/BCD/string-in-registers).
2026-04-18 11:55:21 -04:00
ModbusDriver.cs
Phase 3 PR 46 -- DL205 BCD decoder (binary-coded-decimal numeric encoding). Adds ModbusDataType.Bcd16 and Bcd32 to the driver. Bcd16 is 1 register wide, Bcd32 is 2 registers wide; Bcd32 respects ModbusByteOrder (BigEndian/WordSwap) the same way Int32 does so the CDAB-style families (including DL205/DL260 themselves) can be configured. DecodeRegister uses the new internal DecodeBcd helper: walks each nibble from MSB to LSB, multiplies the running result by 10, adds the nibble as a decimal digit. Explicitly rejects nibbles > 9 with InvalidDataException -- hardware sometimes produces garbage during write-in-progress transitions and silently returning wrong numeric values would quietly corrupt the caller's data. EncodeRegister's new EncodeBcd inverts the operation (mod/div by 10 nibble-by-nibble) with an up-front overflow check against 10^nibbles-1. Why this matters for DL205/DL260: AutomationDirect DirectLOGIC uses BCD as the default numeric encoding for timers, counters, and operator-display numerics (not binary). A plain Int16 read of register 0x1234 returns 4660; the BCD path returns 1234. The two differ enough that silently defaulting to Int16 would give wildly wrong HMI values -- the caller must opt in to Bcd16/Bcd32 per tag. Unit tests: DecodeBcd (theory: 0,1,9,10,1234,9999), DecodeBcd_rejects_nibbles_above_nine, EncodeBcd (theory), Bcd16_decodes_DL205_register_1234_as_decimal_1234 (control: same bytes as Int16 decode to 4660), Bcd16_encode_round_trips_with_decode, Bcd16_encode_rejects_out_of_range_values, Bcd32_decodes_8_digits_big_endian, Bcd32_word_swap_handles_CDAB_layout, Bcd32_encode_round_trips_with_decode, Bcd_RegisterCount_matches_underlying_width. 66/66 Modbus.Tests pass. Integration test: DL205BcdQuirkTests.DL205_BCD16_decodes_HR1072_as_decimal_1234 against dl205.json pymodbus profile (HR[1072]=0x1234). Asserts Bcd16 decode=1234 AND Int16 decode=0x1234 on the same wire bytes to prove the paths are distinct. 3/3 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205.
2026-04-18 21:46:25 -04:00
ModbusDriverOptions.cs
Phase 3 PR 46 -- DL205 BCD decoder (binary-coded-decimal numeric encoding). Adds ModbusDataType.Bcd16 and Bcd32 to the driver. Bcd16 is 1 register wide, Bcd32 is 2 registers wide; Bcd32 respects ModbusByteOrder (BigEndian/WordSwap) the same way Int32 does so the CDAB-style families (including DL205/DL260 themselves) can be configured. DecodeRegister uses the new internal DecodeBcd helper: walks each nibble from MSB to LSB, multiplies the running result by 10, adds the nibble as a decimal digit. Explicitly rejects nibbles > 9 with InvalidDataException -- hardware sometimes produces garbage during write-in-progress transitions and silently returning wrong numeric values would quietly corrupt the caller's data. EncodeRegister's new EncodeBcd inverts the operation (mod/div by 10 nibble-by-nibble) with an up-front overflow check against 10^nibbles-1. Why this matters for DL205/DL260: AutomationDirect DirectLOGIC uses BCD as the default numeric encoding for timers, counters, and operator-display numerics (not binary). A plain Int16 read of register 0x1234 returns 4660; the BCD path returns 1234. The two differ enough that silently defaulting to Int16 would give wildly wrong HMI values -- the caller must opt in to Bcd16/Bcd32 per tag. Unit tests: DecodeBcd (theory: 0,1,9,10,1234,9999), DecodeBcd_rejects_nibbles_above_nine, EncodeBcd (theory), Bcd16_decodes_DL205_register_1234_as_decimal_1234 (control: same bytes as Int16 decode to 4660), Bcd16_encode_round_trips_with_decode, Bcd16_encode_rejects_out_of_range_values, Bcd32_decodes_8_digits_big_endian, Bcd32_word_swap_handles_CDAB_layout, Bcd32_encode_round_trips_with_decode, Bcd_RegisterCount_matches_underlying_width. 66/66 Modbus.Tests pass. Integration test: DL205BcdQuirkTests.DL205_BCD16_decodes_HR1072_as_decimal_1234 against dl205.json pymodbus profile (HR[1072]=0x1234). Asserts Bcd16 decode=1234 AND Int16 decode=0x1234 on the same wire bytes to prove the paths are distinct. 3/3 DL205 integration tests pass with MODBUS_SIM_PROFILE=dl205.
2026-04-18 21:46:25 -04:00
ModbusTcpTransport.cs
Phase 3 PR 43 — followup commit: validate pymodbus simulator end-to-end + fix three real bugs surfaced by running it. winget-installed Python 3.12.10 + pip-installed pymodbus[simulator]==3.13.0 on the dev box; both profiles boot cleanly, the integration-suite smoke test passes against either profile.
2026-04-18 21:14:02 -04:00
ZB.MOM.WW.OtOpcUa.Driver.Modbus.csproj
Phase 3 PR 21 — Modbus TCP driver: first native-protocol greenfield for v2. New src/Driver.Modbus project with ModbusDriver implementing IDriver + ITagDiscovery + IReadable + IWritable. Validates the driver-agnostic abstractions (IAddressSpaceBuilder, DriverAttributeInfo, DataValueSnapshot, WriteRequest/WriteResult) generalize beyond Galaxy — nothing Galaxy-specific is used here. ModbusDriverOptions carries Host/Port/UnitId/Timeout + a pre-declared tag list (Modbus has no discovery protocol — tags are configuration). IModbusTransport abstracts the socket layer so tests swap in-memory fakes; concrete ModbusTcpTransport speaks the MBAP ADU (TxId + Protocol=0 + Length + UnitId + PDU) over TcpClient, serializes requests through a semaphore for single-flight in-order responses, validates the response TxId matches, surfaces server exception PDUs as ModbusException with function code + exception code. DiscoverAsync streams one folder per driver with a BaseDataVariable per tag + DriverAttributeInfo that flags writable tags as SecurityClassification.Operate vs ViewOnly for read-only regions. ReadAsync routes per-tag by ModbusRegion: FC01 for Coils, FC02 for DiscreteInputs, FC03 for HoldingRegisters, FC04 for InputRegisters; register values decoded through System.Buffers.Binary.BinaryPrimitives (BigEndian for single-register Int16/UInt16 + two-register Int32/UInt32/Float32 per standard modbus word-swap conventions). WriteAsync uses FC05 (Write Single Coil with 0xFF00/0x0000 encoding) for booleans, FC06 (Write Single Register) for 16-bit types, FC16 (Write Multiple Registers) for 32-bit types. Unknown tag → BadNodeIdUnknown; write to InputRegister or DiscreteInput or Writable=false tag → BadNotWritable; exception during transport → BadInternalError + driver health Degraded. Subscriptions + Historian + Alarms deliberately out of scope — Modbus has no push model (subscribe would be a polling overlay, additive PR) and no history/alarm semantics at the protocol level. Tests (9 new ModbusDriverTests): InitializeAsync connects + populates the tag map + sets health=Healthy; Read Int16 from HoldingRegister returns BigEndian value; Read Float32 spans two registers BigEndian (IEEE 754 single for 25.5f round-trips exactly); Read Coil returns boolean from the bit-packed response; unknown tag name returns BadNodeIdUnknown without an exception; Write UInt16 round-trips via FC06; Write Float32 uses FC16 (two-register write verified by decoding back through the fake register bank); Write to InputRegister returns BadNotWritable; Discover streams one folder + one variable per tag with correct DriverDataType mapping (Int16/Int32→Int32, UInt16/UInt32→Int32, Float32→Float32, Bool→Boolean). FakeTransport simulates a 256-register/256-coil bank + implements the 7 function codes the driver uses. slnx updated with the new src + tests entries. Full solution post-add: 0 errors, 189 tests pass (9 Modbus + 180 pre-existing). IDriver abstraction validated against a fundamentally different protocol — Modbus TCP has no AlarmExtension, no ScanState, no IPC boundary, no historian, no LDAP — and the same builder/reader/writer contract plugged straight in. Future PRs on this driver: ISubscribable via a polling loop, IHostConnectivityProbe for dead-device detection, PLC-specific data-type extensions (Int64/BCD/string-in-registers).
2026-04-18 11:55:21 -04:00