lmxopcua/docs/v2/focas-version-matrix.md
T
Joseph Doherty 5f0a52864c feat(focas): real FANUC 30i/31i-B PDU-v3 support (live-validated on a 31i-B)
First real FOCAS hardware contact (Makino Pro 5 / 31i-B @ 10.201.31.5). A full
v3 data-PDU capture corrected the initial diagnosis: the v3 block envelope is
identical to v1, so only specific payload structs / request math / one client
robustness gap were wrong — not "framing rewrites".

Fixes (all re-validated live through the fixed driver):
- version gate: accept inbound PDU {1,3}, keep emitting v1 (FocasWireProtocol).
- cnc_rdtimer: 8-byte {minute,msec} payload is little-endian (ParseTimer) — the
  only decode with an in-range msec field.
- pmc_rdpmcrng: request range widened to the data-type byte width
  (end = start + width - 1) so a Word/Long isn't truncated to 0 values
  (was spurious BadOutOfRange); decode extracted to ParsePmcRange.
- cnc_rdsvmeter: per-axis LOADELM is 8 bytes (not 12) and names come from the
  0x0089 block — ParseServoMeters fixes the misaligned 655360 garbage. Also the
  "hang" was NetworkStream.ReadAsync not aborting a stalled socket: ReadExactlyAsync
  now disposes the stream on cancellation so a stalled peer can't wedge a poll loop.
- cnc_rddynamic2: contract guard rejecting axis < 1 (driver poll already 1-based).
- FocasDriverProbe: run a real wire session (initiate + cnc_statinfo) instead of
  degrading to Ok=true "TCP reachability only" when FWLIB is absent — a bare TCP
  listener no longer reports HEALTHY.

cnc_rdparam (0x000e) is unsupported on this control — EW_FUNC across 14
request-framing variants x 4 known-present params; needs a reference FWLIB trace
or is restricted. Deferred (deployed config uses macros, not parameters).

Tests: FOCAS suite 234 green (+16), full solution builds 0 errors. Raw v3
captures checked in under tests/.../Fixtures/v3/. Capture tools under scripts/focas/.

Docs: docs/plans/2026-06-25-focas-pdu-v3-{30i-b-support,implementation-plan}.md,
docs/drivers/FOCAS.md, docs/v2/focas-version-matrix.md,
docs/deployments/wonder-app-vd03-makino-z-34184.md.
2026-06-25 16:41:42 -04:00

7.5 KiB
Raw Blame History

FOCAS version / capability matrix

Authoritative source for the per-CNC-series ranges that FocasCapabilityMatrix enforces at driver init time. Every row cites the Fanuc FOCAS Developer Kit function whose documented input range determines the ceiling.

Why this exists — we have no FOCAS hardware on the bench and no working simulator. FWLIB (Fwlib64, or Fwlib32 on legacy deployments) returns EW_NUMBER / EW_PARAM when you hand it an address outside the controller's supported range; the driver would map that to a per-read BadOutOfRange at steady state. Catching at InitializeAsync with this matrix surfaces operator typos + mismatched series declarations as config errors before any session is opened, which is the only feedback loop available without a live CNC to read against.

Who declares the seriesFocasDeviceOptions.Series in appsettings.json. Defaults to Unknown, which is permissive — every address passes validation. Pre-matrix configs don't break on upgrade.


Series covered

Enum value Controller family Typical era
Unknown (legacy / not declared) permissive fallback
Sixteen_i 16i / 18i / 21i 1997-2008
Zero_i_D 0i-D 2008-2013
Zero_i_F 0i-F 2013-present, general-purpose
Zero_i_MF 0i-MF 0i-F lathe variant
Zero_i_TF 0i-TF 0i-F turning variant
Thirty_i 30i-A / 30i-B 2007-present, high-end
ThirtyOne_i 31i-A / 31i-B 30i simpler variant
ThirtyTwo_i 32i-A / 32i-B 30i compact
PowerMotion_i Power Motion i-A / i-MODEL A motion-only controller

Macro variable range (cnc_rdmacro / cnc_wrmacro)

Common macros 1-33 + 100-199 + 500-999 are universal across all series. Extended macros (#10000+) exist only on higher-end series. The numbers below reflect the extended ceiling per series per the DevKit range tables.

Series Min Max Notes
Sixteen_i 0 999 legacy ceiling — no extended
Zero_i_D 0 999 0i-D still at legacy ceiling
Zero_i_F / Zero_i_MF / Zero_i_TF 0 9999 extended added on 0i-F
Thirty_i / ThirtyOne_i / ThirtyTwo_i 0 99999 full extended set
PowerMotion_i 0 999 atypical — limited macro coverage

Parameter range (cnc_rdparam / cnc_wrparam)

Series Min Max
Sixteen_i 0 9999
Zero_i_D / Zero_i_F / Zero_i_MF / Zero_i_TF 0 14999
Thirty_i / ThirtyOne_i / ThirtyTwo_i 0 29999
PowerMotion_i 0 29999

PMC letters (pmc_rdpmcrng / pmc_wrpmcrng)

Addresses are letter + number (e.g. R100, F50.3). Legacy controllers omit the F/G signal groups that 30i-family ladder programs use, and only the 30i-family exposes K (keep-relay) + T (timer).

Letter 16i 0i-D 0i-F family 30i family Power Motion-i
X yes yes yes yes yes
Y yes yes yes yes yes
R yes yes yes yes yes
D yes yes yes yes yes
E yes yes yes
A yes yes yes
F yes yes
G yes yes
M yes yes
C yes yes
K yes
T yes

Letter match is case-insensitive. FocasAddress.PmcLetter is carried as a string (not char) so the matrix can do ordinal-ignore-case comparison.

PMC address-number ceiling

PMC addresses are byte-addressed on read + bit-addressed on write; FocasAddress carries the bit index separately, so these are byte ceilings.

Series Max byte Notes
Sixteen_i 999 legacy
Zero_i_D 1999 doubled since 16i
Zero_i_F family 9999
Thirty_i family 59999 highest density
PowerMotion_i 1999

Error surface

When a tag fails validation, FocasDriver.InitializeAsync throws InvalidOperationException with a message of the form:

FOCAS tag '<name>' (<address>) rejected by capability matrix: <reason>

<reason> is the verbatim string from FocasCapabilityMatrix.Validate and always names the series + the documented limit so the operator can either raise the limit (if wrong) or correct the CNC series they declared (if mismatched). Sample:

FOCAS tag 'X_axis_macro_ext' (MACRO:50000) rejected by capability
matrix: Macro variable #50000 is outside the documented range
[0, 9999] for Zero_i_F.

How this matrix stays honest

  • Every row is covered by a parameterized test in FocasCapabilityMatrixTests.cs — 46 cases across macro / parameter / PMC-letter / PMC-number boundaries + unknown-series permissiveness + rejection-message content + case-insensitivity.
  • Widening or narrowing a range in the matrix without updating this doc will fail a test, because the theories cite the specific row they reflect in their InlineData.
  • The matrix is not comprehensive — it encodes only the subset of FOCAS surface the driver currently exposes (Macro / Parameter / PMC). When the driver gains a new capability (e.g. tool management, alarm history), add its series-specific range tables here + matching tests at the same time.

Follow-up

This validation closes the cheap half of the FOCAS hardware-free stability gap — config errors now fail at load instead of per-read. The expensive half is Tier-C process isolation so that a crashing Fwlib64.dll doesn't take the main OPC UA server down with it. See docs/v2/implementation/focas-isolation-plan.md for that plan (task #220).

Real-hardware validation (first live FOCAS contact)

2026-06-25 — FANUC 31i-B (Makino Pro 5), 10.201.31.5:8193. The first time the managed wire client met real FOCAS hardware. The control answers PDU version 3; the 10-byte header framing and response block envelope are byte-identical to v1 (only the version field differs). cnc_sysinfo reports CncType 31, Series G431, 7 axes (X Y Z B C A A), MtType MM.

Command family v3 result Notes
cnc_sysinfo, cnc_rdaxisname, cnc_rdspdlname validated identity / axis / spindle names
cnc_rddynamic2 (positions, feed, spindle, program/seq) validated 1-based axis iteration; program O-number reads via big-endian
cnc_rdopmode, cnc_exeprgname2 validated mode + executing program
cnc_rdmacro validated deployed MACRO:3901/3902 tags read Good
cnc_rdtimer validated 8-byte {minute, msec} payload is little-endian (unlike the big-endian envelope)
pmc_rdpmcrng validated request range must be widened to the data-type byte width (end = start + width - 1)
cnc_rdsvmeter validated per-axis LOADELM is 8 bytes, not 12; names come from the 0x0089 block; load scaling unconfirmed
cnc_rdalmmsg2 validated read a live active alarm (#3080)
cnc_rdparam unsupported EW_FUNC across 14 request-framing variants × 4 known-present params — likely wrong v3 command id (0x000e) or restricted on this control; needs a reference FWLIB trace

Full finding + captured wire bytes + the fix per surface: ../plans/2026-06-25-focas-pdu-v3-30i-b-support.md.