I-1: a PUT/GET-disabled CPU (every read denied) stayed Faulted with LastSuccessfulRead frozen, so the comms-loss watchdog reconnected and re-subscribed it every 90 s forever. Both access-denied arms now also record an answer: Faulted is kept (worst state wins), the stamp advances, and the sticky write fault still clears only on a real success. Pinned end to end in Runtime.Tests: the real S7Driver under the real DriverInstanceActor watchdog is not reconnected across 2x the threshold; the control (every read timing out) is. Minors: - m-1: injectable pass clock (UtcNow); "LastSuccessfulRead advanced" is now asserted strictly, including the write-refusal case. - m-2: the editor uses S7TagShapeRules.IsByteAnchored instead of its own list. - m-3: a release that races an init publish also cancels the probe loop the publish started after the release took its snapshot. - m-4: a retained poll failing during a lifecycle operation writes no health. - m-5: a multi-var chunk that fell back memoises its members refused alone. - m-7: access-denied needs S7.Net's exact wording and no transport fault in the chain. - m-8: sync teardown clears the write-side Degraded owner; a sync Dispose racing a running shutdown is tested. Refs #742 Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
26 KiB
Siemens S7 Driver
Getting-started guide for the Siemens S7 driver. This is the short path — for
the full per-field spec read docs/v2/driver-specs.md §5,
for hands-on CLI testing read Driver.S7.Cli.md, and for
the test-harness map read S7-Test-Fixture.md.
What it talks to
Siemens S7 PLCs — S7-300, S7-400, S7-1200, S7-1500, plus S7-200 / S7-200 Smart
/ LOGO! 0BA8 — over the native S7comm protocol on ISO-on-TCP, TCP port
102. The wire is spoken by the pure-managed S7netplus
(S7.Net) library: no native DLL, no P/Invoke, no out-of-process isolation. The
driver runs in-process in the OtOpcUa server's .NET 10 AnyCPU host on every OS
the server runs on.
This is the leanest OtOpcUa driver — read/write/subscribe/discover plus a connectivity probe, and nothing else. It implements no alarm source and no per-call host resolver (a single S7 instance targets a single CPU).
Project split
| Project | Target | Role |
|---|---|---|
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7/ |
net10.0 | In-process driver — hosts the S7.Net.Plc connection and the address parser |
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7.Contracts/ |
net10.0 | Dependency-free config records + enums (S7DriverOptions, S7CpuType, S7DataType) bound from DriverConfig JSON |
Minimum deployment
Register the driver instance in the central config DB (or appsettings.json).
No separate service, no DLL deployment:
"Drivers": {
"s7-line-1": {
"Type": "S7",
"Config": {
"Host": "10.20.30.40",
"CpuType": "S71500",
"Rack": 0,
"Slot": 0,
"Tags": [
{ "Name": "Running", "Address": "DB1.DBX0.0", "DataType": "Bool", "Writable": false },
{ "Name": "Speed", "Address": "DB1.DBD4", "DataType": "Float32", "Writable": true }
]
}
}
}
S7 exposes a symbol table, but S7.Net does not surface it — so the driver
operates off a static, per-site tag list, not live symbol discovery.
Rack / slot / CPU family
CpuType selects the ISO-TSAP slot byte used during the connection handshake;
pick the family that matches the PLC exactly. Rack is almost always 0
(relevant only for distributed S7-400 racks). Slot conventions per family:
S7-300 = slot 2, S7-400 = slot 2 or 3, S7-1200 / S7-1500 = slot 0 (onboard PN).
The CpuType JSON strings are S7300, S7400, S71200, S71500 and the legacy
families S7200 (S7-200), S7200Smart (S7-200 Smart) and Logo0BA8 (LOGO! 0BA8).
For the three legacy families S7.Net uses fixed TSAPs, so Rack / Slot are not
consulted — leave them 0 / 0; support is limited S7comm and unverified against
hardware. A wrong slot causes a connection refusal during the handshake. See
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7.Contracts/S7DriverOptions.cs for the
per-field defaults.
TSAP / connection-type override
By default S7.Net derives both ISO-TSAPs from CpuType / Rack / Slot (local 01.00; remote
03.<rack×0x20+slot> for the S7-300/400/1200/1500 families). Three optional keys override that
for CPUs and gateways that hand out connection resources by TSAP (S7-400H, CP343, LOGO!):
| Key | Form | Effect |
|---|---|---|
localTsap |
"01.00" (also "0100", "0x0100", or a 16-bit number) |
replaces the local TSAP |
remoteTsap |
"03.01" (same forms) |
replaces the whole remote TSAP |
connectionType |
"PG" | "OP" | "S7Basic" (string) |
writes 1 / 2 / 3 into the first remote-TSAP byte, keeping rack×0x20+slot as the second |
remoteTsap and connectionType are mutually exclusive (a config carrying both fails to load); a
malformed TSAP fails to load rather than silently falling back to the slot-derived default. With none of
the three set the connection is built exactly as before. The override applies to the driver, the AdminUI
Test Connect probe and the AdminUI S7 driver form (Connection type / Local TSAP / Remote TSAP fields).
Test Connect and PUT/GET
After the handshake, Test Connect reads 2 bytes from MB0. A CPU with PUT/GET disabled (the S7-1200/1500
default) completes the handshake but denies every read, so the probe fails with an actionable "enable
PUT/GET communication" message instead of a false green tick. A CPU that merely rejects that address (no
MB0) still passes — the connection is fine; any other read fault fails the probe with its message.
Both are recognised in the bare-Exception shape S7.Net's read path really raises. The handshake and
test read are bounded by the config's timeoutMs (the driver's own per-operation timeout), capped by the
Test Connect timeout — before R07:H7 the config value was ignored.
Address forms
Addresses use Siemens TIA-Portal / STEP 7 Classic syntax, parsed by
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7/S7AddressParser.cs:
| Area | Example | Meaning |
|---|---|---|
| Data block | DB1.DBX0.0 / DB1.DBW0 / DB1.DBD4 / DB1.DBB8 |
DB number + size suffix X(bit) / B(byte) / W(word) / D(dword), optional .bit for DBX |
| Merker (M) | MB0 / MW0 / MD4 / M0.0 |
Marker byte; size prefix B/W/D, or bare offset .bit for bit access |
| Input (I) | IB0 / IW0 / I0.0 |
Process-image input |
| Output (Q) | QB0 / QW0 / Q0.0 |
Process-image output |
| Timer | T0 / T15 |
Timer area (read-only — see Wide types section) |
| Counter | C0 / C10 |
Counter area (read-only — see Wide types section) |
Parsing is strict. Bit offsets must be 0-7, byte offsets non-negative, DB numbers >= 1.
Tag shape rules are judged per tag, at every gate (S7TagShapeRules, called by
S7TagDefinitionFactory.FromTagConfig): the AdminUI editor refuses the tag, the deploy gate
(Inspect) warns, and the driver's init skips it (reported through ISkippedTagReporter; it reads
BadNodeIdUnknown) while every other tag keeps working. Refused: an address that does not parse, a
wide/structured type that is an array or is not byte-addressed (DBB/MB/IB/QB), a narrow type at the
wrong access width (Int32 on DBW0, Bool on DBB0...), a Timer not typed Float64 or a Counter not typed
Int32, a writable or array Timer/Counter, a writable Bool array, and a Bool array that does not start
at bit 0 (a Bool array reads bit 0 of each byte, so DB1.DBX0.3 used to silently return bit 0 of bytes
0..n). These used to be init guards that THREW, so one typo faulted every tag on the PLC and the actor
retried the same init every 10 s forever (R07:H3).
Data types
S7DataType declares the semantic type; S7.Net returns an unsigned boxed
value (bool / byte / ushort / uint) that the driver reinterprets without an
extra PLC round-trip.
| DataType | S7 Type | Width | Read | Write |
|---|---|---|---|---|
Bool |
BOOL | 1 bit | yes | yes |
Byte |
BYTE | 1 byte | yes | yes |
Int16 |
INT | 2 bytes | yes | yes |
UInt16 |
WORD | 2 bytes | yes | yes |
Int32 |
DINT | 4 bytes | yes | yes |
UInt32 |
DWORD | 4 bytes | yes | yes |
Float32 |
REAL | 4 bytes | yes | yes |
Int64 |
LINT | 8 bytes | yes | yes |
UInt64 |
ULINT/LWORD | 8 bytes | yes | yes |
Float64 |
LREAL | 8 bytes | yes | yes |
String |
STRING | StringLength + 2 bytes |
yes | yes |
WString |
WSTRING | 4 + 2 × StringLength bytes |
yes | yes |
Char |
CHAR | 1 byte | yes | yes |
WChar |
WCHAR | 2 bytes | yes | yes |
DateTime |
DATE_AND_TIME (DT) | 8 bytes (BCD) | yes | yes |
Dtl |
DTL | 12 bytes | yes | yes |
Date |
DATE | 2 bytes | yes | yes |
Tod |
TIME_OF_DAY | 4 bytes | yes | yes |
Time |
TIME | 4 bytes | yes | yes |
S5Time |
S5TIME | 2 bytes | yes | yes |
Timer (T{n}) |
TIME | — | yes | read-only |
Counter (C{n}) |
COUNTER | — | yes | read-only |
Wide types (Int64, UInt64, Float64, String, DateTime, and the string / date-time
types below) and Timer/Counter require byte-anchored addressing — see the section below.
String, character and date/time/duration types
These add no new OPC UA data types — they map onto existing ones:
| DataType | OPC UA type | Representation | Write refuses (BadOutOfRange, nothing sent) |
|---|---|---|---|
String |
String | S7 [maxLen][curLen][chars], ASCII |
over StringLength (S7.Net behaviour) |
WString |
String | [maxLen UInt16][curLen UInt16][UTF-16BE]; stringLength is the declared max in characters, 0–16382 (default 254) |
more UTF-16 code units than StringLength |
Char |
String (1 char) | 1 byte, Latin-1 | a character above U+00FF |
WChar |
String (1 char) | UTF-16BE code unit | — (a string whose length is not 1 is BadTypeMismatch) |
DateTime |
DateTime | DT, 8-byte BCD (S7.Net codec; 1990–2089) | out-of-range year |
Dtl |
DateTime | year UInt16 + month/day/weekday/h/m/s + UInt32 nanoseconds; 100 ns resolution | year outside 1970–2262 |
Date |
DateTime (midnight) | UInt16 days since 1990-01-01 (max 2169-06-06) | before 1990-01-01 or after 2169-06-06 |
Tod |
Int32 ms since midnight | UInt32 ms | outside 0–86 399 999 |
Time |
Int32 ms (signed duration) | Int32 ms | outside the Int32 range |
S5Time |
Int32 ms | 2-bit time base (10 ms / 100 ms / 1 s / 10 s) + 3 BCD digits | above 9 990 000 ms, negative, or not exactly representable (resolution is 10 ms up to 9 990 ms, then coarser) — never rounded |
A fractional millisecond Double is rounded to the nearest whole millisecond (banker's rounding), exactly
as the driver does for every other Int32 tag write; only values off the S5TIME time-base grid are refused.
A write of a TimeSpan is also accepted for Tod / Time / S5Time. A PLC buffer the codec cannot
decode — an uninitialised (all-zero) Dtl, a non-BCD S5Time digit, a WString whose current length
exceeds its reserved length — reads BadOutOfRange for that tag only, without degrading driver health
or condemning the connection. S5Time writes pick the finest time base that holds the value. The
Timer area (T{n}) keeps its own S5TIME-to-seconds (Float64) decode.
Wide types & Timer/Counter
Byte-anchored addressing for wide / structured types
Wide types (Int64, UInt64, Float64/LReal, String, DateTime, WString, Char,
WChar, Dtl, Date, Tod, Time, S5Time) are byte-anchored: the address must use the B suffix pointing at the first
byte of the value; the driver reads the correct number of contiguous bytes
based on the DataType.
| DataType | Address form | Bytes read | Example |
|---|---|---|---|
Int64 |
DB{n}.DBB{offset} / MB{offset} / IB{offset} / QB{offset} |
8 | DB1.DBB8 → LINT at bytes 8–15 |
UInt64 |
same | 8 | DB2.DBB16 → ULINT at bytes 16–23 |
Float64 |
same | 8 | DB1.DBB8 → LREAL at bytes 8–15 |
DateTime |
same | 8 | DB3.DBB0 → DATE_AND_TIME at bytes 0–7 |
String |
same | StringLength + 2 |
DB4.DBB0, StringLength=40 → 42 bytes |
WString |
same | 4 + 2 × StringLength |
DB5.DBB0, StringLength=10 → 24 bytes |
Dtl |
same | 12 | DB6.DBB0 → DTL at bytes 0–11 |
Using a W or D suffix with a wide DataType is a config error caught at
InitializeAsync. For array tags (isArray: true), wide-type element arrays
are deferred — see Deferrals below.
Timer read
Address: T{n} (e.g. T0, T15). DataType must be Float64. The OPC UA node
is a scalar Float64 whose value is the timer's elapsed time in seconds (as a double).
Timers are read-only this phase; a write attempt returns BadNotWritable.
Counter read
Address: C{n} (e.g. C0, C10). DataType must be Int32. The OPC UA node is
a scalar Int32 containing the unsigned raw big-endian word, widened to Int32:
(bytes[0] << 8) | bytes[1]. S7.Net's Counter.FromByteArray performs no BCD
reinterpretation; for example, bytes 01 23 surface as 291. This describes the
current decoder, not verified agreement with a PLC's displayed count.
Counters are read-only this phase; a write attempt returns BadNotWritable.
The S7comm ReadVar C-area response encoding remains unverified on hardware.
PLC instruction representations do not by themselves establish network encoding:
Siemens documents a binary current value for L: Load counter
and separate CV and CV_BCD outputs for S_CD.
IEC counter values stored in DB memory use the DB address and declared integer
type, a different read path from C{n}. CPU family alone does not select the
counter kind or prove its wire representation. In particular, Siemens also lists
legacy SIMATIC counters for S7-1500 in its instruction comparison (pages 23–24).
The driver has no counter encoding selector; hardware-faithful counter support
requires independent raw-response evidence before any interpretation change.
Counter evidence follow-up (#616)
The existing S7_1500SpanReadTests exercises the python-snap7 profile's synthetic
raw words (C0 = 4711, C7 = 31337). These are outside the classic SIMATIC count
range 0..999 documented by S_CD. These expectations describe raw-word handling;
they do not establish classic counter count semantics. The recorded device-0 run cannot prove nonzero
numbering. The nonzero test is environment-gated, but its options remain
CpuType = S71500, rack 0, slot 0: setting S7_TIMER_NUMBER_ADDRESSING=1
does not configure a classic CPU or make the profile a classic counter gate.
Before claiming hardware validation or closing #616:
- Prepare a separate target-specific semantic gate with the actual CPU type, rack, slot and TSAP/connection settings. Keep the synthetic raw-word profile as its own evidence of the existing decoder contract.
- Record CPU model/order number, firmware, endpoint, connection settings and driver/S7netplus plus simulator versions where applicable.
- Observe independent PLC-side current counts and binary/BCD reference outputs
for valid classic counts such as
123, a second distinguishing count (42or999), and zero. Record the instruction/counter kind and DB reference addresses; do not derive reference values from the driver's output. - Capture the actual two-byte S7comm C-area responses alongside those references. Do not infer response bytes from a simulator seed or expected BCD value.
- Verify several distinct nonzero timer/counter numbers against their independent PLC values and captured requests/responses, and verify the read-only contract.
The raw-byte/count and nonzero-numbering gates remain open. Password/protection support inherited from #303/#632 is a separate follow-up, not evidence supplied by these counter checks.
Deferrals (not yet implemented)
The following are explicitly deferred and will produce a config error or
BadNotSupported if attempted:
- Wide-type arrays — array tags (
isArray: true) with element typesInt64,UInt64,Float64,String,DateTime, or any of the string / date-time types above. - Timer / Counter writes — surfaced as
BadNotWritableuntil write support lands.
Negotiated PDU size
The PDU size the CPU negotiates during the connection handshake (typically 240 bytes; 480 / 960 with
extended PDU) is snapshotted at every (re)connect and exposed as S7Driver.NegotiatedPduSize /
S7Driver.GetDiagnostics()["S7.NegotiatedPduSize"] (0 before the first connect and after shutdown). It is
also written to the S7Driver connected / reconnected log lines and to the AdminUI Test Connect
message (S7 connected (CPU S71500, PDU 240 bytes)). S7 also implements the optional
IDriverDiagnostics capability (explicitly, string-valued: S7.NegotiatedPduSize = "480", omitted while 0 =
not negotiated yet), so the value rides the driver-health snapshot and shows under the driver name on the
AdminUI /hosts page (Gitea #640). See docs/Telemetry.md ("Driver diagnostics ride driver-health").
Capability surface
S7Driver : IDriver, ITagDiscovery, IReadable, IWritable, ISubscribable, IHostConnectivityProbe
(src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7/S7Driver.cs).
| Capability | Path | Notes |
|---|---|---|
IReadable |
ReadAsync → S7.Net.Plc.ReadAsync |
One request/response per tag, serialized on a per-PLC semaphore |
IWritable |
WriteAsync → S7.Net.Plc.WriteAsync |
Read-only tags (Writable=false) return BadNotWritable |
ITagDiscovery |
DiscoverAsync |
Emits a flat S7/ folder of the configured tags — no live browse |
ISubscribable |
per-tag poll loop with capped exponential backoff | S7 has no push model; floor is 100 ms (the CPU services the comms mailbox once per scan) |
IHostConnectivityProbe |
periodic S7.Net.Plc.ReadStatusAsync (CPU-status PDU) |
host:port host key; Running/Stopped transitions raise OnHostStatusChanged. A tick that finds the gate held past the probe deadline (a long read pass) gives no verdict — it no longer reports Stopped for a connection that is busy, not lost (R07:H7) |
Single-connection policy
One S7.Net.Plc instance per PLC, serialized with a SemaphoreSlim.
Parallelising reads against a single CPU doesn't help — the CPU scans its
comms mailbox at most once per cycle and queues concurrent requests wire-side
anyway, while wasting the CPU's 8-64 connection-resource budget.
PUT/GET communication
S7-1200 / S7-1500 ship with PUT/GET access disabled by default. A driver
pointed at a freshly-flashed CPU sees a hard access-denied fault. The driver
maps it specifically to BadNotSupported, flags the instance Faulted (a
configuration alert, not a transient fault), and does not blind-retry —
because the CPU will keep refusing. Fix: enable PUT/GET communication in TIA
Portal under Protection & Security for the CPU.
Error mapping
| Condition | StatusCode | Health |
|---|---|---|
| Tag not in config | BadNodeIdUnknown |
unchanged |
| Read-only tag written | BadNotWritable |
unchanged |
| Unimplemented data type | BadNotSupported |
unchanged |
| PUT/GET denied | BadNotSupported |
Faulted (config alert) — also counts as answered, advances LastSuccessfulRead (no watchdog reconnect loop) |
| CPU refusal of the item (object does not exist, address out of range, type inconsistent, hardware fault) | BadDeviceFailure |
unchanged — counts as answered, advances LastSuccessfulRead; one Warning per tag |
Other device-layer fault (PlcException that is neither a refusal nor connection-fatal) |
BadDeviceFailure |
Degraded |
| Socket / timeout | BadCommunicationError |
Degraded |
| Reconnect suppressed (backoff window) | BadCommunicationError |
Degraded |
| Array write of the wrong shape / length / element type | BadTypeMismatch |
unchanged |
| Bool / wide-type array write | BadNotSupported |
unchanged |
Health is decided once per pass, worst state wins. A read pass and a write batch each
accumulate their outcomes and write health once (Healthy < Degraded < Faulted), so a PUT/GET-denied
Faulted item is not erased by a later Degraded or successful sibling. The write-side Faulted is
sticky against reads: a clean read pass (reads often work against a write-protected CPU) leaves
Faulted in place and only advances LastSuccessfulRead; the next write that succeeds clears it. A
transient Degraded write failure is cleared by a clean read, or by the next write batch the CPU
answers without a failure.
A refusal is an answer (R07:H4). S7.Net's read paths raise the CPU's item error as a bare
Exception ("Received error from PLC: Object does not exist." — live-probed on the snap7 fixture), its
write paths as a PlcException(WriteData); both are classified over the whole exception chain, and the
access-denied text inside either (S7.Net's exact "Accessing object not allowed", and never when the chain
also carries a transport fault) is the Faulted alert — which is ALSO an answer: it advances
LastSuccessfulRead, so a factory-default CPU with PUT/GET disabled stays Faulted instead of being
reconnected by the comms-loss watchdog every 90 s. A multi-var chunk that falls back per tag memoises the
members refused on their own, like a refused span. A refusal is deterministic, so it neither
degrades health nor reopens the connection, and because it proves the CPU is reachable it advances
LastSuccessfulRead and restores Healthy after an earlier comms fault. Before this, a driver whose
every tag was refused (a wrong DB number) sat Degraded with a frozen timestamp and the comms-loss
watchdog reconnected it every 90 s against a perfectly reachable PLC.
A dead handle ends the pass's wire traffic (R07:P1). Once a read pass or write batch marks the
connection dead (a wire op blew its deadline on a frozen-but-established peer, a socket dropped), the
remaining spans / multi-var chunks / tags / writes of that pass are stamped BadCommunicationError
without I/O; the next call reopens. A multi-var chunk that dies on a transport loss no longer falls back
to one doomed per-tag read per member. Without this an op that ignores its cancellation token would cost
one full deadline per remaining item under the gate, and Degraded (and so the comms-loss watchdog's
clock) only became visible after the whole pass.
A refused span falls back per member (R07:P2). A grouped block read covers the union of its members'
ranges, so one member the CPU refuses (running past the DB's real end, an over-declared stringLength)
used to make every neighbour in the block Bad on every poll. When the CPU refuses a multi-member span the
driver re-reads its members one at a time for that pass and remembers which tags must not be grouped —
the members refused on their own, or every member when none was — so later passes group only the rest.
The memo lasts until the next initialize. A span failure that is not a refusal still stamps every member.
Connect backoff. A dead PLC costs one connect attempt per backoff window (1 s doubling to a 30 s
cap), not one per read / poll tick / probe tick: inside the window EnsureConnectedAsync fails fast
(BadCommunicationError, Degraded) without a connect. A successful connect clears the window, so a
fresh drop after a healthy period reconnects immediately; worst-case recovery lag is the 30 s cap.
Testing
- Unit tests —
tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7.Tests/cover the address parser, the reinterpret/box conversions, and the driver lifecycle. - Integration fixture — a Docker S7 simulator on the shared docker host; see
S7-Test-Fixture.md for the coverage map and endpoint. The wide/date-time
codecs (STRING, WSTRING, CHAR, WCHAR, DTL, DATE, TOD, TIME, S5TIME) and the TSAP override keys have
live snap7 coverage in
S7_1500CodecTests; an unrepresentable STRING/DT write isBadOutOfRange(not a comms fault) like the other codecs. - CLI — Driver.S7.Cli.md documents the standalone read/write/probe CLI for manual checks against a real or simulated CPU.
1-D array support
An S7 tag becomes a 1-D OPC UA array node when its TagConfig JSON carries
"isArray": true and "arrayLength": N (N ≥ 1). The canonical rule:
isArray: true + arrayLength >= 1 → array; isArray: false (any length) → scalar.
Read mechanism — the driver issues a single ReadBytesAsync call over the contiguous
memory span starting at the declared address for N × (bytes per element) bytes, then
loops over the response buffer decoding each element individually using the same
reinterpret/box logic as scalar reads. This keeps wire round-trips at 1 per array tag
regardless of N.
Supported element types — the narrow scalar types (Bool, Byte, Int16, UInt16,
Int32, UInt32, Float32). Wide types (Int64, UInt64, Float64, String,
DateTime) and Timer/Counter are deferred for array contexts. The ReadBytesAsync
network half is a thin S7.Net call; the decode half is fully unit-tested.
Unit test coverage — tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7.Tests/ covers
the contiguous-block read and per-element decode loop. Integration fixture is down during
normal dev (the S7 sim is on the shared Docker host but currently offline).
Live-verify — integration-fixture-gated (not Mac-verifiable without the S7 sim up).
Array writes (S7-016) — a writable Byte / Int16 / UInt16 / Int32 / UInt32 / Float32 array
is written as ONE contiguous WriteBytesAsync of count x element-bytes (the inverse of the read
decode), and the value must be an array of exactly arrayLength elements (else BadTypeMismatch, no
health impact). Writable Bool arrays are refused per tag (see the tag shape rules above): the array
read is byte-granular, so a matching write would overwrite the 7 neighbouring bits of every byte it
touches, and a safe bit-packed write needs read-modify-write. Mark Bool arrays writable: false. A null array element is rejected (BadTypeMismatch, nothing written)
rather than coerced to 0. An array write larger than one PDU is split by S7.Net into several writes and is
not atomic — a mid-write failure can leave the PLC array partly updated.
The server exposes these as writable OPC UA array nodes (#610) for exactly the element types above —
a Bool / wide-type S7 array stays read-only at the node (BadNotWritable), see Uns.md §Array
writes. The driver path is also reachable directly through the Client
CLI / driver-level callers and is proven by the unit suite plus the snap7 fixture test
(S7_1500ArrayWriteTests); the AdminUI tag editor rejects wide-type and writable-Bool arrays at author time.
Deferrals — multi-dimensional arrays (out of scope by decision, see Uns.md), per-element historization,
wide-type array elements (Int64, UInt64, Float64, String, DateTime), and
Timer/Counter array elements.
See Uns.md §Array tags for the cross-driver coverage matrix and the UI authoring flow.
Further reading
docs/v2/driver-specs.md §5— full per-field spec, DriverConfig JSON shape, and operational stability notes- Driver.S7.Cli.md — standalone S7 driver CLI
- S7-Test-Fixture.md — simulator + test-harness map