Joseph Doherty 8adc8f5ab8 Phase 3 PR 37 — End-to-end live-stack Galaxy smoke test. Closes the code side of LMX follow-up #5; once OtOpcUaGalaxyHost is installed + started on the dev box, the suite exercises the full topology GalaxyProxyDriver in-process → named-pipe IPC → running OtOpcUaGalaxyHost Windows service → MxAccessGalaxyBackend → live MXAccess runtime → real deployed Galaxy objects. Never spawns the Host process itself — connects to the already-running service per project_galaxy_host_service.md, which is the only way to exercise the production COM-apartment + service-account + pipe-ACL configuration.
LiveStackConfig resolves the pipe name + per-install shared secret from two sources in order: OTOPCUA_GALAXY_PIPE + OTOPCUA_GALAXY_SECRET env vars first (for CI / benchwork overrides), then the service's per-process Environment registry values under HKLM\SYSTEM\CurrentControlSet\Services\OtOpcUaGalaxyHost (what Install-Services.ps1 writes at install time). Registry read requires the test host to run elevated on most boxes — the skip message says so explicitly so operators see the right remediation. Hard-coded secrets are deliberately avoided: the installer generates 32 fresh random bytes per install, a committed secret would diverge from production the moment the service is re-installed.
LiveStackFixture is an IAsyncLifetime that (1) runs AvevaPrerequisites.CheckAllAsync with CheckGalaxyHostPipe=true + CheckHistorian=false — produces a structured PrerequisiteReport whose SkipReason is the exact operator-facing 'here's what you need to fix' text, (2) resolves LiveStackConfig and surfaces a clear skip when the secret isn't discoverable, (3) instantiates GalaxyProxyDriver + calls InitializeAsync (the IPC handshake), capturing a skip with the exception detail + common-cause hints (secret mismatch, SID not in pipe ACL, Host's backend couldn't connect to ZB) rather than letting a NullRef cascade through every subsequent test. SkipIfUnavailable() translates the captured SkipReason into Assert.Skip at the top of every fact so tests read as cleanly-skipped with a visible reason, not silently-passed or crashed.
LiveStackSmokeTests (5 facts, Collection=LiveStack, Category=LiveGalaxy): Fixture_initialized_successfully (cheapest possible end-to-end assertion — if this passes, the IPC handshake worked); Driver_reports_Healthy_after_IPC_handshake (DriverHealth.State post-connect); DiscoverAsync_returns_at_least_one_variable_from_live_galaxy (captures every Variable() call from DiscoverAsync via CapturingAddressSpaceBuilder and asserts > 0 — zero here usually means the Host couldn't read ZB, the skip message names OTOPCUA_GALAXY_ZB_CONN to check); GetHostStatuses_reports_at_least_one_platform (IHostConnectivityProbe surface — zero means the probe loop hasn't fired or no Platform is deployed locally); Can_read_a_discovered_variable_from_live_galaxy (reads the first discovered attribute's full reference, asserts status != BadInternalError — Galaxy's Uncertain-quality-until-first-Engine-scan is intentionally NOT treated as failure since it depends on runtime state that varies across test runs). Read-only by design; writes need an agreed scratch tag to avoid mutating a process-critical attribute — deferred to a follow-up PR that reuses this fixture.
CapturingAddressSpaceBuilder is a minimal IAddressSpaceBuilder that flattens every Variable() call into a list so tests can inspect what discovery produced without booting the full OPC UA node-manager stack; alarm annotation + property calls are no-ops. Scoped private to the test class.
Galaxy.Proxy.Tests csproj gains a ProjectReference to Driver.Galaxy.TestSupport (PR 36) for AvevaPrerequisites. The NU1702 warning about the Host project being net48-referenced-by-net10 is pre-existing from the HostSubprocessParityTests — Proxy.Tests only needs the Host EXE path for that parity scenario, not type surface.
Test run on THIS machine (OtOpcUaGalaxyHost not yet installed): Skipped! Failed 0, Passed 0, Skipped 5 — each skip message includes the full prerequisites report pointing at the missing service. Once the service is installed + started (scripts\install\Install-Services.ps1), the 5 facts will execute against live Galaxy. Proxy.Tests Unit: 17 pass / 0 fail (unchanged — new tests are Category=LiveGalaxy, separate suite). Full Proxy build clean. Memory already captures the 'live tests run via already-running service, don't spawn' convention (project_galaxy_host_service.md).
lmx-followups.md #5 updated: status is 'IN PROGRESS' across PRs 36 + 37 with the explicit remaining work (install + start services, subscribe-and-receive, write round-trip).

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-18 16:49:51 -04:00
..
Phase 3 PR 28 — Admin UI cert-trust management page. New /certificates route (FleetAdmin-only) surfaces the OPC UA server's PKI store rejected + trusted certs and gives operators Trust / Delete / Revoke actions so rejected client certs can be promoted without touching disk. CertTrustService reads $PkiStoreRoot/{rejected,trusted}/certs/*.der files directly via X509CertificateLoader — no Opc.Ua dependency in the Admin project, which keeps the Admin host runnable on a machine that doesn't have the full Server install locally (only needs the shared PKI directory reachable; typical deployment has Admin + Server side-by-side on the same box and PkiStoreRoot defaults match so a plain-vanilla install needs no override). CertTrustOptions bound from the Admin's 'CertTrust:PkiStoreRoot' section, default %ProgramData%\OtOpcUa\pki (matches OpcUaServerOptions.PkiStoreRoot default). Trust action moves the .der from rejected/certs/ to trusted/certs/ via File.Move(overwrite:true) — idempotent, tolerates a concurrent operator doing the same move. Delete wipes the file. Revoke removes from trusted/certs/ (Opc.Ua re-reads the Directory store on each new client handshake, so no explicit reload signal is needed; operators retry the rejected connection after trusting). Thumbprint matching is case-insensitive because X509Certificate2.Thumbprint is upper-case hex but operators copy-paste from logs that sometimes lowercase it. Malformed files in the store are logged + skipped — a single bad .der can't take the whole management page offline. Missing store directories produce empty lists rather than exceptions so a pristine install (Server never run yet, no rejected/trusted dirs yet) doesn't crash the page.
2026-04-18 14:37:55 -04:00
Phase 3 PR 15 — alarm-condition contract in IAddressSpaceBuilder + wire OnAlarmEvent through GenericDriverNodeManager. IAddressSpaceBuilder.IVariableHandle gains MarkAsAlarmCondition(AlarmConditionInfo) which returns an IAlarmConditionSink. AlarmConditionInfo carries SourceName/InitialSeverity/InitialDescription. Concrete address-space builders (the upcoming PR 16 OPC UA server backend) materialize a sibling AlarmConditionState node on the first call; the sink receives every lifecycle transition the generic node manager forwards. GenericDriverNodeManager gains a CapturingBuilder wrapper that transparently wraps every Folder/Variable call — the wrapper observes MarkAsAlarmCondition calls without participating in materialization, captures the resulting IAlarmConditionSink into an internal source-node-id → sink ConcurrentDictionary keyed by IVariableHandle.FullReference. After DiscoverAsync completes, if the driver implements IAlarmSource the node manager subscribes to OnAlarmEvent and routes every AlarmEventArgs to the sink registered for args.SourceNodeId — unknown source ids are dropped silently (may belong to another driver or to a variable the builder chose not to flag). Dispose unsubscribes the forwarder to prevent dangling invocation-list references across node-manager rebuilds. GalaxyProxyDriver.DiscoverAsync now calls handle.MarkAsAlarmCondition(new AlarmConditionInfo(fullName, AlarmSeverity.Medium, null)) on every attr.IsAlarm=true variable — severity seed is Medium because the live Priority byte arrives through the subsequent GalaxyAlarmEvent stream (which PR 14's GalaxyAlarmTracker now emits); the Admin UI sees the severity update on the first transition. RecordingAddressSpaceBuilder in Driver.Galaxy.E2E gains a RecordedAlarmCondition list + a RecordingSink implementation that captures AlarmEventArgs for test assertion — the E2E parity suite can now verify alarm-condition registration shape in addition to folder/variable shape. Tests (4 new GenericDriverNodeManagerTests): Alarm_events_are_routed_to_the_sink_registered_for_the_matching_source_node_id — 2 alarms registered (Tank.HiHi + Heater.OverTemp), driver raises an event for Tank.HiHi, the Tank.HiHi sink captures the payload, the Heater.OverTemp sink does not (tag-scoped fan-out, not broadcast); Non_alarm_variables_do_not_register_sinks — plain Tank.Level in the same discover is not in TrackedAlarmSources; Unknown_source_node_id_is_dropped_silently — a transition for Unknown.Source doesn't reach any sink + no exception; Dispose_unsubscribes_from_OnAlarmEvent — post-dispose, a transition for a previously-registered tag is no-op because the forwarder detached. InternalsVisibleTo('ZB.MOM.WW.OtOpcUa.Core.Tests') added to Core csproj so TrackedAlarmSources internal property is visible to the test. Full solution: 0 errors, 152 unit tests pass (8 Core + 14 Proxy + 14 Admin + 24 Configuration + 6 Shared + 84 Galaxy.Host + 2 Server). PR 16 will implement the concrete OPC UA address-space builder that materializes AlarmConditionState from this contract.
2026-04-18 07:51:35 -04:00
Phase 3 PR 15 — alarm-condition contract in IAddressSpaceBuilder + wire OnAlarmEvent through GenericDriverNodeManager. IAddressSpaceBuilder.IVariableHandle gains MarkAsAlarmCondition(AlarmConditionInfo) which returns an IAlarmConditionSink. AlarmConditionInfo carries SourceName/InitialSeverity/InitialDescription. Concrete address-space builders (the upcoming PR 16 OPC UA server backend) materialize a sibling AlarmConditionState node on the first call; the sink receives every lifecycle transition the generic node manager forwards. GenericDriverNodeManager gains a CapturingBuilder wrapper that transparently wraps every Folder/Variable call — the wrapper observes MarkAsAlarmCondition calls without participating in materialization, captures the resulting IAlarmConditionSink into an internal source-node-id → sink ConcurrentDictionary keyed by IVariableHandle.FullReference. After DiscoverAsync completes, if the driver implements IAlarmSource the node manager subscribes to OnAlarmEvent and routes every AlarmEventArgs to the sink registered for args.SourceNodeId — unknown source ids are dropped silently (may belong to another driver or to a variable the builder chose not to flag). Dispose unsubscribes the forwarder to prevent dangling invocation-list references across node-manager rebuilds. GalaxyProxyDriver.DiscoverAsync now calls handle.MarkAsAlarmCondition(new AlarmConditionInfo(fullName, AlarmSeverity.Medium, null)) on every attr.IsAlarm=true variable — severity seed is Medium because the live Priority byte arrives through the subsequent GalaxyAlarmEvent stream (which PR 14's GalaxyAlarmTracker now emits); the Admin UI sees the severity update on the first transition. RecordingAddressSpaceBuilder in Driver.Galaxy.E2E gains a RecordedAlarmCondition list + a RecordingSink implementation that captures AlarmEventArgs for test assertion — the E2E parity suite can now verify alarm-condition registration shape in addition to folder/variable shape. Tests (4 new GenericDriverNodeManagerTests): Alarm_events_are_routed_to_the_sink_registered_for_the_matching_source_node_id — 2 alarms registered (Tank.HiHi + Heater.OverTemp), driver raises an event for Tank.HiHi, the Tank.HiHi sink captures the payload, the Heater.OverTemp sink does not (tag-scoped fan-out, not broadcast); Non_alarm_variables_do_not_register_sinks — plain Tank.Level in the same discover is not in TrackedAlarmSources; Unknown_source_node_id_is_dropped_silently — a transition for Unknown.Source doesn't reach any sink + no exception; Dispose_unsubscribes_from_OnAlarmEvent — post-dispose, a transition for a previously-registered tag is no-op because the forwarder detached. InternalsVisibleTo('ZB.MOM.WW.OtOpcUa.Core.Tests') added to Core csproj so TrackedAlarmSources internal property is visible to the test. Full solution: 0 errors, 152 unit tests pass (8 Core + 14 Proxy + 14 Admin + 24 Configuration + 6 Shared + 84 Galaxy.Host + 2 Server). PR 16 will implement the concrete OPC UA address-space builder that materializes AlarmConditionState from this contract.
2026-04-18 07:51:35 -04:00
Phase 1 Streams B–E scaffold + Phase 2 Streams A–C scaffold — 8 new projects with ~70 new tests, all green alongside the 494 v1 IntegrationTests baseline (parity preserved: no v1 tests broken; legacy OtOpcUa.Host untouched). Phase 1 finish: Configuration project (16 entities + 10 enums + DbContext + DesignTimeDbContextFactory + InitialSchema/StoredProcedures/AuthorizationGrants migrations — 8 procs including sp_PublishGeneration with MERGE on ExternalIdReservation per decision #124, sp_RollbackToGeneration cloning rows into a new published generation, sp_ValidateDraft with cross-cluster-namespace + EquipmentUuid-immutability + ZTag/SAPID reservation pre-flight, sp_ComputeGenerationDiff with CHECKSUM-based row signature — plus OtOpcUaNode/OtOpcUaAdmin SQL roles with EXECUTE grants scoped to per-principal-class proc sets and DENY UPDATE/DELETE/INSERT/SELECT on dbo schema); managed DraftValidator covering UNS segment regex, path length, EquipmentUuid immutability across generations, same-cluster namespace binding (decision #122), reservation pre-flight, EquipmentId derivation (decision #125), driver↔namespace compatibility — returning every failing rule in one pass; LiteDB local cache with round-trip + ring pruning + corruption-fast-fail; GenerationApplier with per-entity Added/Removed/Modified diff and dependency-ordered callbacks (namespace → driver → device → equipment → poll-group → tag, Removed before Added); Core project with GenericDriverNodeManager (scaffold for the Phase 2 Galaxy port) and DriverHost lifecycle registry; Server project using Microsoft.Extensions.Hosting BackgroundService replacing TopShelf, with NodeBootstrap that falls back to LiteDB cache when the central DB is unreachable (decision #79); Admin project scaffolded as Blazor Server with Bootstrap 5 sidebar layout, cookie auth, three admin roles (ConfigViewer/ConfigEditor/FleetAdmin), Cluster + Generation services fronting the stored procs. Phase 2 scaffold: Driver.Galaxy.Shared (netstandard2.0) with full MessagePack IPC contract surface — Hello version negotiation, Open/CloseSession, Heartbeat, DiscoverHierarchy + GalaxyObjectInfo/GalaxyAttributeInfo, Read/WriteValues, Subscribe/Unsubscribe/OnDataChange, AlarmSubscribe/Event/Ack, HistoryRead, HostConnectivityStatus, Recycle — plus length-prefixed framing (decision #28) with a 16 MiB cap and thread-safe FrameWriter/FrameReader; Driver.Galaxy.Host (net48) implementing the Tier C cross-cutting protections from driver-stability.md — strict PipeAcl (allow configured server SID only, explicit deny on LocalSystem + Administrators), PipeServer with caller-SID verification via pipe.RunAsClient + WindowsIdentity.GetCurrent and per-process shared-secret Hello, Galaxy-specific MemoryWatchdog (warn at max(1.5×baseline, +200 MB), soft-recycle at max(2×baseline, +200 MB), hard ceiling 1.5 GB, slope ≥5 MB/min over 30-min rolling window), RecyclePolicy (1 soft recycle per hour cap + 03:00 local daily scheduled), PostMortemMmf (1000-entry ring buffer in %ProgramData%\OtOpcUa\driver-postmortem\galaxy.mmf, survives hard crash, readable cross-process), MxAccessHandle : SafeHandle (ReleaseHandle loops Marshal.ReleaseComObject until refcount=0 then calls optional unregister callback), StaPump with responsiveness probe (BlockingCollection dispatcher for Phase 1 — real Win32 GetMessage/DispatchMessage pump slots in with the same semantics when the Galaxy code lift happens), IsExternalInit shim for init setters on .NET 4.8; Driver.Galaxy.Proxy (net10) implementing IDriver + ITagDiscovery forwarding over the IPC channel with MX data-type and security-classification mapping, plus Supervisor pieces — Backoff (5s → 15s → 60s capped, reset-on-stable-run), CircuitBreaker (3 crashes per 5 min opens; 1h → 4h → manual cooldown escalation; sticky alert doesn't auto-clear), HeartbeatMonitor (2s cadence, 3 consecutive misses = host dead per driver-stability.md). Infrastructure: docker SQL Server remapped to host port 14330 to coexist with the native MSSQL14 Galaxy ZB DB instance on 1433; NuGetAuditSuppress applied per-project for two System.Security.Cryptography.Xml advisories that only reach via EF Core Design with PrivateAssets=all (fix ships in 11.0.0-preview); .slnx gains 14 project registrations. Deferred with explicit TODOs in docs/v2/implementation/phase-2-partial-exit-evidence.md: Phase 1 Stream E Admin UI pages (Generations listing + draft-diff-publish, Equipment CRUD with OPC 40010 fields, UNS Areas/Lines tabs, ACLs + permission simulator, Generic JSON config editor, SignalR real-time, Release-Reservation + Merge-Equipment workflows, LDAP login page, AppServer smoke test per decision #142), Phase 2 Stream D (Galaxy MXAccess code lift out of legacy OtOpcUa.Host, dual-service installer, appsettings → DriverConfig migration script, legacy Host deletion — blocked by parity), Phase 2 Stream E (v1 IntegrationTests against v2 topology, Client.CLI walkthrough diff, four 2026-04-13 stability findings regression tests, adversarial review — requires live MXAccess runtime).
2026-04-17 21:35:25 -04:00
Phase 3 PR 24 — Modbus PLC data type extensions. Extends ModbusDataType beyond the textbook Int16/UInt16/Int32/UInt32/Float32 set with Int64/UInt64/Float64 (4-register types), BitInRegister (single bit within a holding register, BitIndex 0-15 LSB-first), and String (ASCII packed 2 chars per register with StringLength-driven sizing). Adds ModbusByteOrder enum on ModbusTagDefinition covering the two word-orderings that matter in the real PLC population: BigEndian (ABCD — Modbus TCP standard, Schneider PLCs that follow it strictly) and WordSwap (CDAB — Siemens S7 family, several Allen-Bradley series, some Modicon families). NormalizeWordOrder helper reverses word pairs in-place for 32-bit values and reverses all four words for 64-bit values (keeps bytes big-endian within each register, which is universal; swaps only the word positions). Internal codec surface switched from (bytes, ModbusDataType) pairs to (bytes, ModbusTagDefinition) because the tag carries the ByteOrder + BitIndex + StringLength context the codec needs; RegisterCount similarly takes the tag so strings can compute ceil(StringLength/2). DriverDataType mapping in MapDataType extended to cover the new logical types — Int64/UInt64 widen to Int32 (PR 25 follow-up: extend DriverDataType enum with Int64 to avoid precision loss), Float64 maps to DriverDataType.Float64, String maps to DriverDataType.String, BitInRegister surfaces as Boolean, all other mappings preserved. BitInRegister writes throw a deliberate InvalidOperationException with a 'read-modify-write' hint — to atomically flip a single bit the driver needs to FC03 the register, OR/AND in the bit, then FC06 it back; that's a separate PR because the bit-modify atomicity story needs a per-register mutex and optional compare-and-write semantics. Everything else (decoder paths for both byte orders, Int64/UInt64/Float64 encode + decode, bit-index extraction across both register halves, String nul-truncation on decode, String nul-padding on encode) ships here. Tests (21 new ModbusDataTypeTests): RegisterCount_returns_correct_register_count_per_type theory (10 rows covering every numeric type); RegisterCount_for_String_rounds_up_to_register_pair theory (5 rows including the 0-char edge case that returns 0 registers); Int32_BigEndian_decodes_ABCD_layout + Int32_WordSwap_decodes_CDAB_layout + Float32_WordSwap_encode_decode_roundtrips (covers the two most-common 32-bit orderings); Int64_BigEndian_roundtrips + UInt64_WordSwap_reverses_four_words (word-swap on 64-bit reverses the four-word layout explicitly, with the test computing the expected wire shape by hand rather than trusting the implementation) + Float64_roundtrips_under_word_swap (3.14159265358979 survives the round-trip with 1e-12 tolerance); BitInRegister_extracts_bit_at_index theory (6 rows including LSB, MSB, and arbitrary bits in a multi-bit mask); BitInRegister_write_is_not_supported_in_PR24 (asserts the exception message steers the reader to the 'read-modify-write' follow-up); String_decodes_ASCII_packed_two_chars_per_register (decodes 'HELLO!' from 3 packed registers with the 'HELLO!'u8 test-only UTF-8 literal which happens to equal the ASCII bytes for this ASCII input); String_decode_truncates_at_first_nul ('Hi' padded with nuls reads back as 'Hi'); String_encode_nul_pads_remaining_bytes (short input writes remaining bytes as 0). Full solution: 0 errors, 217 unit + integration tests pass (22 + 30 new Modbus = 52 Modbus total, 165 pre-existing). ModbusDriver capability footprint now matches the most common industrial PLC workloads — Siemens S7 + Allen-Bradley + Modicon all supported via ByteOrder config without driver forks.
2026-04-18 12:27:12 -04:00
Phase 3 PR 34 — Host-status publisher (Server) + /hosts drill-down page (Admin). Closes LMX follow-up #7 by wiring together the data layer from PR 33. Server.HostStatusPublisher is a BackgroundService that walks every driver registered in DriverHost every 10 seconds, skips drivers that don't implement IHostConnectivityProbe, calls GetHostStatuses() on each probe-capable driver, and upserts one DriverHostStatus row per (NodeId, DriverInstanceId, HostName) into the central config DB. Upsert path: SingleOrDefaultAsync on the composite PK; if no row exists, Add a new one; if a row exists, LastSeenUtc advances unconditionally (heartbeat) and State + StateChangedUtc update only on transitions so Admin UI can distinguish 'still reporting, still Running' from 'freshly transitioned to Running'. MapState translates Core.Abstractions.HostState to Configuration.Enums.DriverHostState (intentional duplicate enum — Configuration project stays free of driver-runtime deps per PR 33's choice). If a driver's GetHostStatuses throws, log warning and skip that driver this tick — never take down the Server on a publisher failure. If the DB is unreachable, log warning + retry next heartbeat (no buffering — next tick's current-state snapshot is more useful than replaying stale transitions after a long outage). 2-second startup delay so NodeBootstrap's RegisterAsync calls land before the first publish tick, then tick runs immediately so a freshly-started Server surfaces its host topology in the Admin UI without waiting a full interval.
2026-04-18 15:51:55 -04:00