otopcua-s7-cli — Siemens S7 test client

Ad-hoc probe / read / write / subscribe tool for Siemens S7-300 / S7-400 / S7-1200 / S7-1500 (and compatible soft-PLCs) over S7comm / ISO-on-TCP port 102. Uses the same S7Driver the OtOpcUa server does (S7.Net under the hood).

Fourth of four driver test-client CLIs.

Build + run

dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.S7.Cli -- --help

Common flags

Flag Default Purpose
-h / --host required PLC IP or hostname
-p / --port 102 ISO-on-TCP port (rarely changes)
-c / --cpu S71500 S7200 / S7200Smart / S7300 / S7400 / S71200 / S71500
--rack 0 Hardware rack (S7-400 distributed setups only)
--slot 0 CPU slot (S7-300 = 2, S7-400 = 2 or 3, S7-1200/1500 = 0)
--timeout-ms 5000 Per-operation timeout
--tsap-mode Auto ISO-on-TCP connection class: Auto / Pg / Op / S7Basic / Other. Hardened S7-1500 / ET 200SP CPUs may require Op or S7Basic. See s7.md TSAP / Connection Type.
--local-tsap (unset) Optional 16-bit local TSAP override (e.g. 0x0200). Required when --tsap-mode Other; wins over class default under Pg/Op/S7Basic.
--remote-tsap (unset) Optional 16-bit remote TSAP override. Required when --tsap-mode Other; wins over class default under Pg/Op/S7Basic.
--verbose off Serilog debug output

PUT/GET must be enabled

S7-1200 / S7-1500 ship with PUT/GET communication disabled by default. Enable it in TIA Portal: Device config → Protection & Security → Connection mechanisms → "Permit access with PUT/GET communication from remote partner". Without it the CLI's first read will surface BadNotSupported.

S7 address grammar cheat sheet

Form Meaning
DB1.DBW0 DB number 1, word offset 0
DB1.DBD4 DB number 1, dword offset 4
DB1.DBX2.3 DB number 1, byte 2, bit 3
DB10.STRING[0] DB 10 string starting at offset 0
M0.0 Merker bit 0.0
MW0 / MD4 Merker word / dword
IW4 Input word 4
QD8 Output dword 8

Commands

probe

# S7-1500 — default probe MW0
otopcua-s7-cli probe -h 192.168.1.30

# S7-300 (slot 2)
otopcua-s7-cli probe -h 192.168.1.31 -c S7300 --slot 2 -a DB1.DBW0

read

# DB word
otopcua-s7-cli read -h 192.168.1.30 -a DB1.DBW0 -t Int16

# Float32 from DB dword
otopcua-s7-cli read -h 192.168.1.30 -a DB1.DBD4 -t Float32

# Merker bit
otopcua-s7-cli read -h 192.168.1.30 -a M0.0 -t Bool

# 80-char S7 string
otopcua-s7-cli read -h 192.168.1.30 -a DB10.STRING[0] -t String --string-length 80

write

otopcua-s7-cli write -h 192.168.1.30 -a DB1.DBW0 -t Int16 -v 42
otopcua-s7-cli write -h 192.168.1.30 -a DB1.DBD4 -t Float32 -v 3.14
otopcua-s7-cli write -h 192.168.1.30 -a M0.0 -t Bool -v true

Writes to M / Q are real — they drive the PLC program. Be careful what you flip on a running machine.

Hardened CPU — forcing OP-class TSAP

# Probe a hardened S7-1500 that rejects PG class but accepts OP.
otopcua-s7-cli probe -h 10.50.12.30 --tsap-mode Op

# Read against the same CPU.
otopcua-s7-cli read -h 10.50.12.30 --tsap-mode Op -a DB1.DBW0 -t Int16

# Manual TSAP override (e.g. site with a fixed proprietary TSAP gateway).
otopcua-s7-cli probe -h 10.50.12.30 --tsap-mode Other --local-tsap 0x4D57 --remote-tsap 0x4D58

Without --tsap-mode, the CLI uses S7netplus's CpuType-derived default (PG class for almost everything). The same connection-refused failure shape that a wrong --slot produces also shows up when the CPU rejects PG class — try --tsap-mode Op first when the handshake is failing on otherwise-correct endpoint config. See s7.md TSAP / Connection Type for the byte table and motivation.

subscribe

otopcua-s7-cli subscribe -h 192.168.1.30 -a DB1.DBW0 -t Int16 -i 500

S7comm has no native push — the CLI polls through PollGroupEngine just like Modbus / AB.