Joseph Doherty 793c787315 Phase 3 PR 53 -- Transport reconnect-on-drop + SO_KEEPALIVE for DL205 no-keepalive quirk. AutomationDirect H2-ECOM100 does NOT send TCP keepalives per docs/v2/dl205.md behavioral-oddities section -- any NAT/firewall device between the gateway and the PLC can silently close an idle socket after 2-5 minutes of inactivity. The PLC itself never notices and the first SendAsync after the drop would previously surface as IOException / EndOfStreamException / SocketException to the caller even though the PLC is perfectly healthy. PR 53 makes ModbusTcpTransport survive mid-session socket drops: SendAsync wraps the previous body as SendOnceAsync; on the first attempt, if the failure is a socket-layer error (IOException, SocketException, EndOfStreamException, ObjectDisposedException) AND autoReconnect is enabled (default true), the transport tears down the dead socket, calls ConnectAsync to re-establish, and resends the PDU exactly once. Deliberately single-retry -- further failures propagate so the driver health surface reflects the real state, no masking a dead PLC. Protocol-layer failures (e.g. ModbusException with exception code 02) are specifically NOT caught by the reconnect path -- they would just come back with the same exception code after the reconnect, so retrying is wasted wire time. Socket-level vs protocol-level is a discriminator inside IsSocketLevelFailure. Also enables SO_KEEPALIVE on the TcpClient with aggressive timing: TcpKeepAliveTime=30s, TcpKeepAliveInterval=10s, TcpKeepAliveRetryCount=3. Total time-to-detect-dead-socket = 30 + 10*3 = 60s, vs the Windows default 2-hour idle + 9 retries = 2h40min. Best-effort: older OSes that don't expose the fine-grained keepalive knobs silently skip them (catch {}). New ModbusDriverOptions.AutoReconnect bool (default true) threads through to the default transport factory in ModbusDriver -- callers wanting the old 'fail loud on drop' behavior can set AutoReconnect=false, or use a custom transportFactory that ignores the option. Unit tests: ModbusTcpReconnectTests boots a FlakeyModbusServer in-process (real TcpListener on loopback) that serves one valid FC03 response then forcibly shuts down the socket. Transport_recovers_from_mid_session_drop_and_retries_successfully issues two consecutive SendAsync calls and asserts both return valid PDUs -- the second must trigger the reconnect path transparently. Transport_without_AutoReconnect_propagates_drop_to_caller asserts the legacy behavior when the opt-out is taken. Validates real socket semantics rather than mocked exceptions. 142/142 Modbus.Tests pass (113 prior + 2 mapper + 2 reconnect + 25 accumulated across PRs 45-52); 11/11 DL205 integration tests still pass with MODBUS_SIM_PROFILE=dl205 -- no regression from the transport change.
2026-04-18 22:32:13 -04:00
..
Phase 3 PR 34 — Host-status publisher (Server) + /hosts drill-down page (Admin). Closes LMX follow-up #7 by wiring together the data layer from PR 33. Server.HostStatusPublisher is a BackgroundService that walks every driver registered in DriverHost every 10 seconds, skips drivers that don't implement IHostConnectivityProbe, calls GetHostStatuses() on each probe-capable driver, and upserts one DriverHostStatus row per (NodeId, DriverInstanceId, HostName) into the central config DB. Upsert path: SingleOrDefaultAsync on the composite PK; if no row exists, Add a new one; if a row exists, LastSeenUtc advances unconditionally (heartbeat) and State + StateChangedUtc update only on transitions so Admin UI can distinguish 'still reporting, still Running' from 'freshly transitioned to Running'. MapState translates Core.Abstractions.HostState to Configuration.Enums.DriverHostState (intentional duplicate enum — Configuration project stays free of driver-runtime deps per PR 33's choice). If a driver's GetHostStatuses throws, log warning and skip that driver this tick — never take down the Server on a publisher failure. If the DB is unreachable, log warning + retry next heartbeat (no buffering — next tick's current-state snapshot is more useful than replaying stale transitions after a long outage). 2-second startup delay so NodeBootstrap's RegisterAsync calls land before the first publish tick, then tick runs immediately so a freshly-started Server surfaces its host topology in the Admin UI without waiting a full interval.
2026-04-18 15:51:55 -04:00
Phase 3 PR 16 — concrete OPC UA server scaffolding with AlarmConditionState materialization. Introduces the OPCFoundation.NetStandard.Opc.Ua.Server package (v1.5.374.126, same version the v1 stack already uses) and two new server-side classes: DriverNodeManager : CustomNodeManager2 is the concrete realization of PR 15's IAddressSpaceBuilder contract — Folder() creates FolderState nodes under an Organizes hierarchy rooted at ObjectsFolder > DriverInstanceId; Variable() creates BaseDataVariableState with DataType mapped from DriverDataType (Boolean/Int32/Float/Double/String/DateTime) + ValueRank (Scalar or OneDimension) + AccessLevel CurrentReadOrWrite; AddProperty() creates PropertyState with HasProperty reference. Read hook wires OnReadValue per variable to route to IReadable.ReadAsync; Write hook wires OnWriteValue to route to IWritable.WriteAsync and surface per-tag StatusCode. MarkAsAlarmCondition() materializes an OPC UA AlarmConditionState child of the variable, seeded from AlarmConditionInfo (SourceName, InitialSeverity → UA severity via Low=250/Medium=500/High=700/Critical=900, InitialDescription), initial state Enabled + Acknowledged + Inactive + Retain=false. Returns an IAlarmConditionSink whose OnTransition updates alarm.Severity/Time/Message and switches state per AlarmType string ('Active' → SetActiveState(true) + SetAcknowledgedState(false) + Retain=true; 'Acknowledged' → SetAcknowledgedState(true); 'Inactive' → SetActiveState(false) + Retain=false if already Acked) then calls alarm.ReportEvent to emit the OPC UA event to subscribed clients. Galaxy's GalaxyAlarmTracker (PR 14) now lands at a concrete AlarmConditionState node instead of just raising an unobserved C# event. OtOpcUaServer : StandardServer wires one DriverNodeManager per DriverHost.GetDriver during CreateMasterNodeManager — anonymous endpoint, no security profile (minimum-viable; LDAP + security-profile wire-up is the next PR). DriverHost gains public GetDriver(instanceId) so the server can enumerate drivers at startup. NestedBuilder inner class in DriverNodeManager implements IAddressSpaceBuilder by temporarily retargeting the parent's _currentFolder during each call so Folder→Variable→AddProperty land under the correct subtree — not thread-safe if discovery ran concurrently, but GenericDriverNodeManager.BuildAddressSpaceAsync is sequential per driver so this is safe by construction. NuGet audit suppress for GHSA-h958-fxgg-g7w3 (moderate-severity in OPCFoundation.NetStandard.Opc.Ua.Core 1.5.374.126; v1 stack already accepts this risk on the same package version). PR 16 is scoped as scaffolding — the actual server startup (ApplicationInstance, certificate config, endpoint binding, session management wiring into OpcUaServerService.ExecuteAsync) is deferred to a follow-up PR because it needs ApplicationConfiguration XML + optional-cert-store logic that depends on per-deployment policy decisions. The materialization shape is complete: a subsequent PR adds 100 LOC to start the server and all the already-written IAddressSpaceBuilder + alarm-condition + read/write wire-up activates end-to-end. Full solution: 0 errors, 152 unit tests pass (no new tests this PR — DriverNodeManager unit testing needs an IServerInternal mock which is heavyweight; live-endpoint integration tests land alongside the server-startup PR).
2026-04-18 08:00:36 -04:00
Phase 2 PR 14 — alarm subsystem wire-up. Per IsAlarm=true attribute (PR 9 added the discovery flag), GalaxyAlarmTracker in Backend/Alarms/ advises the four Galaxy alarm-state attributes: .InAlarm (boolean alarm active), .Priority (int severity), .DescAttrName (human-readable description), .Acked (boolean acknowledged). Runs the OPC UA Part 9 alarm lifecycle state machine simplified for the Galaxy AlarmExtension model and raises AlarmTransition events on transitions operators must react to — Active (InAlarm false→true, default Unacknowledged), Acknowledged (Acked false→true while InAlarm still true), Inactive (InAlarm true→false). MxAccessGalaxyBackend instantiates the tracker in its constructor with delegate-based subscribe/unsubscribe/write pointers to MxAccessClient, hooks TransitionRaised to forward each transition through the existing OnAlarmEvent IPC event that PR 4 ConnectionSink wires into MessageKind.AlarmEvent frames — no new contract messages required since GalaxyAlarmEvent already exists in Shared.Contracts. Field mapping: EventId = fresh Guid.ToString('N') per transition, ObjectTagName = alarm attribute full reference, AlarmName = alarm attribute full reference, Severity = tracked Priority, StateTransition = 'Active'|'Acknowledged'|'Inactive', Message = DescAttrName or tag fallback, UtcUnixMs = transition time. DiscoverAsync caches every IsAlarm=true attribute's full reference (tag.attribute) into _discoveredAlarmTags (ConcurrentBag cleared-then-filled on every re-Discover to track Galaxy redeploys). SubscribeAlarmsAsync iterates the cache and advises each via GalaxyAlarmTracker.TrackAsync; best-effort per-alarm — a subscribe failure on one alarm doesn't abort the whole call since operators prefer partial alarm coverage to none. Tracker is internally idempotent on repeat Track calls (second invocation for same alarm tag is a no-op; already-subscribed check short-circuits before the 4 MXAccess sub calls). Subscribe-failure rollback inside TrackAsync removes the alarm state + unadvises any of the 4 that did succeed so a partial advise can't leak a phantom tracking entry. AcknowledgeAlarmAsync routes to tracker.AcknowledgeAsync which writes the operator comment to <tag>.AckMsg via MxAccessClient.WriteAsync — writes use the existing MXAccess OnWriteComplete TCS-by-handle path (PR 4 Medium 4) so a runtime-refused ack bubbles up as Success=false rather than false-positive. State-machine quirks preserved from v1: (1) initial Acked=true on subscribe does NOT fire Acknowledged (alarm at rest, pre-acknowledged — default state is Acked=true so the first subscribe callback is a no-op transition), (2) Acked false→true only fires Acknowledged when InAlarm is currently true (acking a latched-inactive alarm is not a user-visible transition), (3) Active transition clears the Acked flag in-state so the next Acked callback correctly fires Acknowledged (v1 had this buried in the ConditionState logic; we track it on the AlarmState struct directly). Priority value handled as int/short/long via type pattern match with int.MaxValue guard — Galaxy attribute category returns varying CLR types (Int32 is canonical but some older templates use Int16), and a long overflow cast to int would silently corrupt the severity. Dispose cascade in MxAccessGalaxyBackend.Dispose: alarm-tracker unsubscribe→dispose, probe-manager unsubscribe→dispose, mx.ConnectionStateChanged detach, historian dispose — same discipline PR 6 / PR 8 / PR 13 established so dangling invocation-list refs don't survive a backend recycle. #pragma warning disable CS0067 around OnAlarmEvent removed since the event is now raised. Tests (9 new, GalaxyAlarmTrackerTests): four-attribute subscribe per alarm, idempotent repeat-track, InAlarm false→true fires Active with Priority + Desc, InAlarm true→false fires Inactive, Acked false→true while InAlarm fires Acknowledged, Acked transition while InAlarm=false does not fire, AckMsg write path carries the comment, snapshot reports latest four fields, foreign probe callback for a non-tracked tag is silently dropped. Full Galaxy.Host.Tests Unit suite 84 pass / 0 fail (9 new alarm + 12 PR 13 probe + 21 PR 12 quality + 42 pre-existing). Galaxy.Host builds clean (0/0). Branches off phase-2-pr13-runtime-probe so the MxAccessGalaxyBackend constructor/Dispose chain gets the probe-manager + alarm-tracker wire-up in a coherent order; fast-forwards if PR 13 merges first.
2026-04-18 07:34:13 -04:00
Phase 2 PR 11 — HistoryReadEvents IPC (alarm history). New Shared.Contracts messages HistoryReadEventsRequest/Response + GalaxyHistoricalEvent DTO (MessageKind 0x66/0x67). IGalaxyBackend gains HistoryReadEventsAsync, Stub/DbBacked return canonical pending error, MxAccessGalaxyBackend delegates to _historian.ReadEventsAsync (ported in PR 5) and maps HistorianEventDto → GalaxyHistoricalEvent — Guid.ToString() for EventId wire shape, DateTime → Unix ms for both EventTime (when the event fired in the process) and ReceivedTime (when the Historian persisted it), DisplayText + Severity pass through. SourceName is string? — null means 'all sources' (passed straight through to HistorianDataSource.ReadEventsAsync which adds the AddEventFilter('Source', Equal, ...) only when non-null). Distinct from the live GalaxyAlarmEvent type because historical rows carry both timestamps and lack StateTransition (Historian logs instantaneous events, not the OPC UA Part 9 alarm lifecycle; translating to OPC UA event lifecycle is the alarm-subsystem's job). Guards: null historian → Historian-disabled error; SDK exception → Success=false with message chained. Tests (3 new): disabled-error when historian null, maps HistorianEventDto with full field set (Id/Source/EventTime/ReceivedTime/DisplayText/Severity=900) to GalaxyHistoricalEvent, null SourceName passes through unchanged (verifies the 'all sources' contract). Galaxy.Host.Tests Unit suite 34 pass / 0 fail. Galaxy.Host builds clean. Branches off phase-2-pr10-history-attime since both extend the MessageKind enum; fast-forwards if PR 10 merges first.
2026-04-18 07:08:16 -04:00
Phase 3 PR 53 -- Transport reconnect-on-drop + SO_KEEPALIVE for DL205 no-keepalive quirk. AutomationDirect H2-ECOM100 does NOT send TCP keepalives per docs/v2/dl205.md behavioral-oddities section -- any NAT/firewall device between the gateway and the PLC can silently close an idle socket after 2-5 minutes of inactivity. The PLC itself never notices and the first SendAsync after the drop would previously surface as IOException / EndOfStreamException / SocketException to the caller even though the PLC is perfectly healthy. PR 53 makes ModbusTcpTransport survive mid-session socket drops: SendAsync wraps the previous body as SendOnceAsync; on the first attempt, if the failure is a socket-layer error (IOException, SocketException, EndOfStreamException, ObjectDisposedException) AND autoReconnect is enabled (default true), the transport tears down the dead socket, calls ConnectAsync to re-establish, and resends the PDU exactly once. Deliberately single-retry -- further failures propagate so the driver health surface reflects the real state, no masking a dead PLC. Protocol-layer failures (e.g. ModbusException with exception code 02) are specifically NOT caught by the reconnect path -- they would just come back with the same exception code after the reconnect, so retrying is wasted wire time. Socket-level vs protocol-level is a discriminator inside IsSocketLevelFailure. Also enables SO_KEEPALIVE on the TcpClient with aggressive timing: TcpKeepAliveTime=30s, TcpKeepAliveInterval=10s, TcpKeepAliveRetryCount=3. Total time-to-detect-dead-socket = 30 + 10*3 = 60s, vs the Windows default 2-hour idle + 9 retries = 2h40min. Best-effort: older OSes that don't expose the fine-grained keepalive knobs silently skip them (catch {}). New ModbusDriverOptions.AutoReconnect bool (default true) threads through to the default transport factory in ModbusDriver -- callers wanting the old 'fail loud on drop' behavior can set AutoReconnect=false, or use a custom transportFactory that ignores the option. Unit tests: ModbusTcpReconnectTests boots a FlakeyModbusServer in-process (real TcpListener on loopback) that serves one valid FC03 response then forcibly shuts down the socket. Transport_recovers_from_mid_session_drop_and_retries_successfully issues two consecutive SendAsync calls and asserts both return valid PDUs -- the second must trigger the reconnect path transparently. Transport_without_AutoReconnect_propagates_drop_to_caller asserts the legacy behavior when the opt-out is taken. Validates real socket semantics rather than mocked exceptions. 142/142 Modbus.Tests pass (113 prior + 2 mapper + 2 reconnect + 25 accumulated across PRs 45-52); 11/11 DL205 integration tests still pass with MODBUS_SIM_PROFILE=dl205 -- no regression from the transport change.
2026-04-18 22:32:13 -04:00