using ZB.MOM.WW.OtOpcUa.Driver.Ab.Transport; namespace ZB.MOM.WW.OtOpcUa.Driver.AbCip; /// /// Maps libplctag / CIP General Status codes to OPC UA StatusCodes. Mirrors the shape of /// ModbusDriver.MapModbusExceptionToStatus so Admin UI status displays stay /// uniform across drivers. /// /// /// Coverage: the CIP general-status values an AB PLC actually returns during normal /// driver operation. Full CIP Volume 1 Appendix B lists 50+ codes; the ones here are the /// ones that move the driver's status needle: /// /// 0x00 success — OPC UA Good (0). /// 0x04 path segment error / 0x05 path destination unknown — BadNodeIdUnknown /// (tag doesn't exist). /// 0x06 partial data transfer — GoodMoreData (fragmented read underway). /// 0x08 service not supported — BadNotSupported (e.g. write on a safety /// partition tag from a non-safety task). /// 0x0A / 0x13 attribute-list error / insufficient data — BadOutOfRange /// (type mismatch or truncated buffer). /// 0x0B already in requested mode — benign, treated as Good. /// 0x0E attribute not settable — BadNotWritable. /// 0x10 device state conflict — BadDeviceFailure (program-mode protected /// writes during download / test-mode transitions). /// 0x16 object does not exist — BadNodeIdUnknown. /// 0x1E embedded service error — unwrap to the extended status when possible. /// Transport errors — mapped per-member by /// : timeout, not-found, not-allowed, and /// out-of-bounds get their specific OPC UA codes; the remaining transport errors /// fold into BadCommunicationError. /// /// public static class AbCipStatusMapper { public const uint Good = 0u; public const uint GoodMoreData = 0x00A60000u; public const uint BadInternalError = 0x80020000u; public const uint BadNodeIdUnknown = 0x80340000u; public const uint BadNotWritable = 0x803B0000u; public const uint BadOutOfRange = 0x803C0000u; public const uint BadNotSupported = 0x803D0000u; public const uint BadDeviceFailure = 0x808B0000u; public const uint BadCommunicationError = 0x80050000u; public const uint BadTimeout = 0x800A0000u; public const uint BadTypeMismatch = 0x80740000u; /// Map a CIP general-status byte to an OPC UA StatusCode. /// The CIP general-status byte value. /// The mapped OPC UA StatusCode value. public static uint MapCipGeneralStatus(byte status) => status switch { 0x00 => Good, 0x04 or 0x05 => BadNodeIdUnknown, 0x06 => GoodMoreData, 0x08 => BadNotSupported, 0x0A or 0x13 => BadOutOfRange, 0x0B => Good, 0x0E => BadNotWritable, 0x10 => BadDeviceFailure, 0x16 => BadNodeIdUnknown, _ => BadInternalError, }; /// /// Map a transport status code to an OPC UA StatusCode. The integer is /// , i.e. the underlying value of . /// /// The as an integer. /// The mapped OPC UA StatusCode value. public static uint MapStatus(int status) => MapStatus((AbStatus)status); /// /// Map an to an OPC UA StatusCode. Timeout, not-found, not-allowed and /// out-of-bounds get their specific codes; the remaining transport errors fold into /// . /// /// The transport status. /// The mapped OPC UA StatusCode value. public static uint MapStatus(AbStatus status) => status switch { AbStatus.Ok => Good, AbStatus.Pending => GoodMoreData, AbStatus.Timeout => BadTimeout, AbStatus.NotFound => BadNodeIdUnknown, AbStatus.NotAllowed => BadNotWritable, AbStatus.OutOfBounds or AbStatus.TooLarge or AbStatus.TooSmall => BadOutOfRange, AbStatus.Unsupported => BadNotSupported, AbStatus.TypeMismatch => BadTypeMismatch, AbStatus.DeviceStateConflict => BadDeviceFailure, _ => BadCommunicationError, // BadConnection, BadReply, Partial, Abort }; /// /// Status for an exception thrown while creating / reading a tag: a transport exception maps /// through its (so a tag the controller does not have reads /// , not a comms error); anything else is /// . /// /// The exception. /// The OPC UA status code. public static uint MapException(Exception ex) => ex is AbTransportException ate ? MapStatus(ate.Status) : BadCommunicationError; }