# `otopcua-abcip-cli` — AB CIP test client Ad-hoc probe / read / write / subscribe tool for ControlLogix / CompactLogix / Micro800 / GuardLogix PLCs, talking to the **same** `AbCipDriver` the OtOpcUa server uses (libplctag under the hood). Second of four driver test-client CLIs (Modbus → AB CIP → AB Legacy → S7 → TwinCAT). Shares `Driver.Cli.Common` with the others. ## Build + run ```powershell dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Cli -- --help ``` ## Common flags | Flag | Default | Purpose | |---|---|---| | `-g` / `--gateway` | **required** | Canonical `ab://host[:port]/cip-path` | | `-f` / `--family` | `ControlLogix` | ControlLogix / CompactLogix / Micro800 / GuardLogix | | `--timeout-ms` | `5000` | Per-operation timeout | | `--verbose` | off | Serilog debug output | Family ↔ CIP-path cheat sheet: - **ControlLogix / CompactLogix / GuardLogix** — `1,0` (slot 0 of chassis) - **Micro800** — empty path, just `ab://host/` - **Sub-slot Logix** (rare) — `1,3` for slot 3 ## Commands ### `probe` — is the PLC up? ```powershell # ControlLogix — read the canonical libplctag system tag otopcua-abcip-cli probe -g ab://10.0.0.5/1,0 -t @raw_cpu_type --type DInt # Micro800 — point at a user-supplied global otopcua-abcip-cli probe -g ab://10.0.0.6/ -f Micro800 -t _SYSVA_CLOCK_HOUR --type DInt ``` ### `read` — single Logix tag ```powershell # Controller scope otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real # Program scope otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Program:Main.Counter" --type DInt # Array element otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Recipe[3]" --type Real # UDT member (dotted path) otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Motor01.Speed" --type Real ``` ### `write` — single Logix tag Same shape as `read` plus `-v`. Values parse per `--type` using invariant culture. Booleans accept `true`/`false`/`1`/`0`/`yes`/`no`/`on`/`off`. Structure (UDT) writes need the member layout declared in a real driver config and are refused by the CLI. ```powershell otopcua-abcip-cli write -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real -v 3.14 otopcua-abcip-cli write -g ab://10.0.0.5/1,0 -t StartCommand --type Bool -v true ``` ### `subscribe` — watch a tag until Ctrl+C ```powershell otopcua-abcip-cli subscribe -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real -i 500 ``` ## Typical workflows - **"Is the PLC reachable?"** → `probe`. - **"Did my recipe write land?"** → `write` + `read` back. - **"Why is tag X flipping?"** → `subscribe`. - **"Is this GuardLogix safety tag writable from non-safety?"** → `write` and read the status code — safety tags surface `BadNotWritable` / CIP errors, non-safety tags surface `Good`.