/// Maps the gateway's (raw MXAccess HRESULT + category bits)
/// to OPC UA StatusCode uints. Replaces the legacy
/// MxAccessGalaxyBackend.ToWire heuristic (Quality >= 192 → Good, else Uncertain)
/// with an explicit table that preserves specific codes (BadNotConnected, OutOfService,
/// UncertainSubNormal, etc.) instead of collapsing to category buckets.
///
///
/// OPC DA quality bytes are 16-bit values arranged as [QQSSSSSSLLNNNN]:
/// Q = quality category (Bad/Uncertain/Good = 0/1/3), S = substatus, L = limit, N = vendor.
/// This mapper consumes the LOW byte (where the Q+S bits live) — the same byte the legacy
/// Wonderware Historian SDK exposed as the raw quality byte. Category-only fallback paths
/// handle deployment versions of MXAccess that surface unfamiliar substatuses.
///
/// Unknown substatus values fall back to the matching category bucket (Good,
/// Uncertain, Bad) and emit a single diagnostic log line per session via
/// the supplied logger so field captures can extend the table.
///
internal static class StatusCodeMap
{
// OPC UA Part 4 standard StatusCodes — top-byte categories are 0x00 (Good),
// 0x40 (Uncertain), 0x80 (Bad). Specific codes layer onto the category byte.
public const uint Good = 0x00000000u;
public const uint GoodLocalOverride = 0x00D80000u;
public const uint Uncertain = 0x40000000u;
public const uint UncertainLastUsableValue = 0x40A40000u;
public const uint UncertainSensorNotAccurate = 0x408D0000u;
public const uint UncertainEngineeringUnitsExceeded = 0x408E0000u;
public const uint UncertainSubNormal = 0x408F0000u;
public const uint Bad = 0x80000000u;
public const uint BadConfigurationError = 0x80890000u;
public const uint BadNotConnected = 0x808A0000u;
public const uint BadDeviceFailure = 0x808B0000u;
public const uint BadSensorFailure = 0x808C0000u;
public const uint BadCommunicationError = 0x80050000u;
public const uint BadOutOfService = 0x808D0000u;
public const uint BadWaitingForInitialData = 0x80320000u;
public const uint BadInternalError = 0x80020000u;
///
/// Map a raw OPC DA quality byte (the low byte of an OPC DA OpcQuality ushort,
/// which is what Wonderware Historian + MXAccess surface as OPCITEMSTATE.qLong's
/// low byte) to the OPC UA StatusCode uint.
///
public static uint FromQualityByte(byte q, ILogger? logger = null) => q switch
{
// Good family — top two bits 11b (192-255).
192 => Good,
216 => GoodLocalOverride,
// Uncertain family — top two bits 01b (64-127).
64 => Uncertain,
68 => UncertainLastUsableValue,
80 => UncertainSensorNotAccurate,
84 => UncertainEngineeringUnitsExceeded,
88 => UncertainSubNormal,
// Bad family — top two bits 00b (0-63).
0 => Bad,
4 => BadConfigurationError,
8 => BadNotConnected,
12 => BadDeviceFailure,
16 => BadSensorFailure,
20 => BadCommunicationError,
24 => BadOutOfService,
32 => BadWaitingForInitialData,
_ => Categorize(q, logger),
};
///
/// Map a gateway-reported to OPC UA StatusCode. Uses
/// (category == OK AND success != 0)
/// as the canonical success test — the proto contract explicitly documents that
/// success is NOT a boolean and must not be checked in isolation; category is
/// the authoritative indicator. On failure, the detail byte (OPC DA quality substatus)
/// drives the specific code, with a transport-error fallback for pre-MXAccess failures.
///
public static uint FromMxStatus(MxStatusProxy? status, ILogger? logger = null)
{
if (status is null) return Good;
if (status.IsSuccess()) return Good;
// Detail field carries the substatus when the worker translated MX-style codes;
// when zero, infer from detected_by.
var detail = (byte)(status.Detail & 0xFF);
if (detail != 0) return FromQualityByte(detail, logger);
// detected_by != Mxaccess (raw_detected_by != the MXAccess source enum) implies
// the failure happened pre-call (gateway, worker, transport) — surface as a
// communication error rather than a generic Bad.
if (status.RawDetectedBy != 0) return BadCommunicationError;
return Bad;
}
///
/// Convert an OPC UA status-code uint back to the OPC DA quality category
/// byte — Good=192, Uncertain=64, Bad=0 — by extracting the top-two bits of the
/// high word. This is the inverse of the category-bucket arm of
/// . It is intentionally lossy (substatus bits are not
/// round-tripped) because the sole consumer
/// ()
/// only tests qualityByte < 192 to distinguish Running from Stopped. Keeping
/// the round-trip in one place means a future change to the OPC UA bit layout cannot
/// silently desync the probe-health decode.
///
public static byte ToQualityCategoryByte(uint statusCode) =>
(byte)(((statusCode >> 30) & 0x3u) switch
{
0u => 192u, // Good — top two bits 00b → OPC DA 0xC0
1u => 64u, // Uncertain — top two bits 01b → OPC DA 0x40
_ => 0u, // Bad — top two bits 10b/11b → OPC DA 0x00
});
private static uint Categorize(byte q, ILogger? logger)
{
if (q >= 192) { Log(logger, q, "Good"); return Good; }
if (q >= 64) { Log(logger, q, "Uncertain"); return Uncertain; }
Log(logger, q, "Bad");
return Bad;
}
private static void Log(ILogger? logger, byte q, string bucket)
{
// Best-effort diagnostic so field captures can extend the table — once per bucket
// per session is plenty (the LogWarning level is rate-limited by Serilog filters
// in production).
logger?.LogWarning(
"Unrecognised MXAccess quality byte 0x{Q:X2} — falling back to {Bucket} category. " +
"Field capture welcome — extend StatusCodeMap.FromQualityByte.", q, bucket);
}
}