{"title":"Phase 3 PR 55 -- Mitsubishi MELSEC Modbus TCP quirks research doc","body":"## Summary\n\nAdds `docs/v2/mitsubishi.md` (451 lines) covering MELSEC Q/L/iQ-R/iQ-F/FX3U Modbus TCP behavior. Mirrors `docs/v2/dl205.md` template for per-quirk implementation PRs.\n\n## Key findings for the implementation track\n\n- **Module naming trap** — `QJ71MB91` is SERIAL RTU, not TCP. TCP module is `QJ71MT91`. Surface clearly in driver docs.\n- **No canonical mapping** — per-site 'Modbus Device Assignment Parameter' block (up to 16 entries). Treat mapping as runtime config.\n- **X/Y hex vs octal depends on family** — Q/L/iQ-R use HEX (X20 = decimal 32); FX/iQ-F use OCTAL (X20 = decimal 16). Helper must take a family selector.\n- **Word order CDAB default** across all MELSEC families (opposite of Siemens S7). Driver Mitsubishi profile default: `ByteOrder.WordSwap`.\n- **D-registers binary by default** (opposite of DL205's BCD default). Caller opts in to `Bcd16`/`Bcd32` when ladder uses BCD.\n- **FX5U needs firmware ≥ 1.060** for Modbus TCP server — older is client-only.\n- **FX3U-ENET vs FX3U-ENET-P502 vs FX3U-ENET-ADP** — only the middle one binds port 502; the last has no Modbus at all. Common operator mis-purchase.\n- **QJ71MT91 does NOT support FC22 / FC23** — iQ-R / iQ-F do. Bulk-read optimization must gate on capability.\n- **STOP-mode writes configurable** on Q/L/iQ-R/iQ-F (default accept), always rejected on FX3U-ENET.\n\nThree unconfirmed rumours flagged separately.\n\nNo code, no tests — implementation lands in PRs 58+.\n\n## Test plan\n- [x] Doc renders as markdown\n- [x] 17 citations present\n- [x] Per-model test naming matrix included (`Mitsubishi_QJ71MT91_*`, `Mitsubishi_FX5U_*`, `Mitsubishi_FX3U_ENET_*`, shared `Mitsubishi_Common_*`)","head":"phase-3-pr55-mitsubishi-research-doc","base":"v2"}