# `otopcua-abcip-cli` — AB CIP test client Ad-hoc probe / read / write / subscribe tool for ControlLogix / CompactLogix / Micro800 / GuardLogix PLCs, talking to the **same** `AbCipDriver` the OtOpcUa server uses (libplctag under the hood). Second of four driver test-client CLIs (Modbus → AB CIP → AB Legacy → S7 → TwinCAT). Shares `Driver.Cli.Common` with the others. ## Build + run ```powershell dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Cli -- --help ``` ## Common flags | Flag | Default | Purpose | |---|---|---| | `-g` / `--gateway` | **required** | Canonical `ab://host[:port]/cip-path` | | `-f` / `--family` | `ControlLogix` | ControlLogix / CompactLogix / Micro800 / GuardLogix | | `--timeout-ms` | `5000` | Per-operation timeout | | `--addressing-mode` | `Auto` | `Auto` / `Symbolic` / `Logical` — see [AbCip-Performance §Addressing mode](drivers/AbCip-Performance.md#addressing-mode). `Logical` against Micro800 silently falls back to Symbolic with a warning. | | `--verbose` | off | Serilog debug output | Family ↔ CIP-path cheat sheet: - **ControlLogix / CompactLogix / GuardLogix** — `1,0` (slot 0 of chassis) - **Micro800** — empty path, just `ab://host/` - **Sub-slot Logix** (rare) — `1,3` for slot 3 ## Commands ### `probe` — is the PLC up? ```powershell # ControlLogix — read the canonical libplctag system tag otopcua-abcip-cli probe -g ab://10.0.0.5/1,0 -t @raw_cpu_type --type DInt # Micro800 — point at a user-supplied global otopcua-abcip-cli probe -g ab://10.0.0.6/ -f Micro800 -t _SYSVA_CLOCK_HOUR --type DInt ``` ### `read` — single Logix tag ```powershell # Controller scope otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real # Program scope otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Program:Main.Counter" --type DInt # Array element otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Recipe[3]" --type Real # UDT member (dotted path) otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Motor01.Speed" --type Real ``` #### Diagnostic / system tags PR abcip-4.3 exposes five read-only diagnostic variables per device under `AbCip//_System/` in the OPC UA address space (see [AbCip-Operability §System tags](drivers/AbCip-Operability.md#system-tags--_system-folder) for the full table). These are not reachable through the AB CIP CLI — they live on the OPC UA server side, not the libplctag wire — so to read one, point the **OPC UA client** CLI at the running OtOpcUa server: ```powershell # Read _ConnectionStatus for one device through the OPC UA server otopcua-client-cli read -u opc.tcp://localhost:4840 \ -n "ns=2;s=AbCip/ab://10.0.0.5/1,0/_System/_ConnectionStatus" ``` ### `write` — single Logix tag Same shape as `read` plus `-v`. Values parse per `--type` using invariant culture. Booleans accept `true`/`false`/`1`/`0`/`yes`/`no`/`on`/`off`. Structure (UDT) writes need the member layout declared in a real driver config and are refused by the CLI. ```powershell otopcua-abcip-cli write -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real -v 3.14 otopcua-abcip-cli write -g ab://10.0.0.5/1,0 -t StartCommand --type Bool -v true ``` ### `subscribe` — watch a tag until Ctrl+C ```powershell otopcua-abcip-cli subscribe -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real -i 500 ``` ### `rebrowse` — force a controller-side `@tags` re-walk PR abcip-2.5 (issue #233) added `RebrowseAsync` to drop the cached UDT template shapes and re-run the symbol-table enumerator without restarting the driver. The CLI variant builds a transient driver against the supplied gateway, runs the rebrowse, and prints the freshly discovered tag names — useful after a controller program-download to confirm the new tags are visible on the wire before wiring them through the OtOpcUa server. ```powershell otopcua-abcip-cli rebrowse -g ab://10.0.0.5/1,0 ``` ## Refreshing the tag DB Two operator-facing surfaces drive the same `RebrowseAsync` plumbing — pick the one that matches your context: | Surface | When to use | Command | |---|---|---| | **CLI `rebrowse`** | Off-server validation. Spins up a transient driver against the gateway, prints the discovered tag list, no shared state with the live OtOpcUa server. | `otopcua-abcip-cli rebrowse -g ab://10.0.0.5/1,0` | | **OPC UA write to `_RefreshTagDb`** | Production / Admin-UI button (PR abcip-4.4). Forces the **live** driver to re-walk + clear its template cache. The `AbCip.RefreshTriggers` driver-diagnostics counter increments per truthy write. | `otopcua-client-cli write -u opc.tcp://localhost:4840 -n "ns=2;s=AbCip/ab://10.0.0.5/1,0/_System/_RefreshTagDb" -v true --type Boolean` | Read-back semantics: `_RefreshTagDb` always reads back as `false` (Kepware- style "latches to idle the moment the dispatch returns") so a subscribed client sees a stable shape regardless of how many refreshes have fired. Falsy / unparseable writes are no-ops that still report `Good` so a UI template that resets the trigger flag after firing it doesn't see a phantom error. See [AbCip-Operability §System tags](drivers/AbCip-Operability.md#refreshing-the-tag-db-via-opc-ua-write) for the full semantics + the diagnostics counter wiring. ## Typical workflows - **"Is the PLC reachable?"** → `probe`. - **"Did my recipe write land?"** → `write` + `read` back. - **"Why is tag X flipping?"** → `subscribe`. - **"Is this GuardLogix safety tag writable from non-safety?"** → `write` and read the status code — safety tags surface `BadNotWritable` / CIP errors, non-safety tags surface `Good`. - **"Did my program download show up in the address space?"** → `rebrowse` (off-server) or write `true` to the live server's `_RefreshTagDb` system tag (in-server, PR abcip-4.4) — both drop the template cache + force a fresh `@tags` walk. ## Connection Size PR abcip-3.1 introduced a per-device `ConnectionSize` override on the driver side (`AbCipDeviceOptions.ConnectionSize`, range `500..4002`). The CLI does not expose a flag for it — every CLI invocation uses the family-default Connection Size (4002 / 504 / 488 depending on `--family`). When a Forward Open is rejected with a CIP error like `0x01/0x113` ("connection request size invalid"), the symptom is almost always a **mismatch between the chosen family default and the controller firmware**: - **v19-and-earlier ControlLogix** caps at 504 — pick `--family CompactLogix` on the CLI to fall back to that narrower default. - **5069-L1/L2/L3 CompactLogix** narrow-buffer parts also cap at 504, which is the family default already. - **FW20+ ControlLogix** accepts the full 4002. For the warning *"AbCip device 'X' family 'Y' uses a narrow-buffer profile (default ConnectionSize Z); the configured ConnectionSize N exceeds the 511-byte legacy-firmware cap..."* see [`docs/drivers/AbCip-Performance.md`](drivers/AbCip-Performance.md) — that warning is fired by the driver host, not the CLI. ## Related operability knobs - [`docs/drivers/AbCip-Operability.md`](drivers/AbCip-Operability.md) — Phase 4 per-tag knobs (per-tag scan rate, deadband, etc). The CLI does not expose these knobs directly; they're set in driver config JSON and consumed by the driver at subscribe time.