# AB CIP — Performance knobs Phase 3 of the AB CIP driver plan introduces a small set of operator-tunable performance knobs that change how the driver talks to the controller without altering the address space or per-tag semantics. They consolidate decisions that Kepware exposes as a slider / advanced page so deployments running into high-latency PLCs, narrow-CPU CompactLogix parts, or legacy ControlLogix firmware have an explicit lever to pull. This document is the home for those knobs as PRs land. PR abcip-3.1 ships the first knob: per-device **CIP Connection Size**. ## Connection Size ### What it is CIP Connection Size — the byte ceiling on a single Forward Open response fragment, set during the EtherNet/IP Forward Open handshake. Larger connection sizes pack more tags into a single CIP RTT (higher request-packing density, fewer round-trips for the same scan list); smaller connection sizes stay compatible with legacy or narrow-buffer firmware that rejects oversized Forward Open requests. ### Family defaults The driver picks a Connection Size from the per-family profile when the device-level override is unset: | Family | Default | Rationale | |---|---:|---| | `ControlLogix` | `4002` | Large Forward Open — FW20+ | | `GuardLogix` | `4002` | Same wire protocol as ControlLogix | | `CompactLogix` | `504` | 5069-L1/L2/L3 narrow-buffer parts (5370 family) | | `Micro800` | `488` | Hard cap on Micro800 firmware | These map straight to libplctag's `connection_size` attribute and match the defaults Kepware uses out of the box for the same families. ### Override knob `AbCipDeviceOptions.ConnectionSize` (`int?`, default `null`) overrides the family default for one device. Bind it through driver config JSON: ```json { "Devices": [ { "HostAddress": "ab://10.0.0.5/1,0", "PlcFamily": "ControlLogix", "ConnectionSize": 504 } ] } ``` The override threads through every libplctag handle the driver creates for that device — read tags, write tags, probe tags, UDT-template reads, the `@tags` walker, and BOOL-in-DINT parent runtimes. There is no per-tag override; one Connection Size applies to the whole controller (matches CIP session semantics). ### Valid range `[500..4002]` bytes. This matches the slider Kepware exposes for the same family. Values outside the range fail driver `InitializeAsync` with an `InvalidOperationException` — there's no silent clamp; misconfigured devices fail loudly so operators see the problem at deploy time. | Value | Behaviour | |---|---| | `null` | Use family default (4002 / 504 / 488) | | `499` or below | Driver init fault — out-of-range | | `500..4002` | Threaded through to libplctag | | `4003` or above | Driver init fault — out-of-range | ### Legacy-firmware caveat ControlLogix firmware **v19 and earlier** caps the CIP buffer at **504 bytes** — Connection Sizes above that cause the controller to reject the Forward Open with CIP error 0x01/0x113. The 5069-L1/L2/L3 CompactLogix narrow parts are subject to the same cap. The driver emits a warning via `AbCipDriverOptions.OnWarning` when the configured Connection Size **exceeds 511** *and* the device's family profile default is also at-or-below the legacy cap (i.e. CompactLogix with default 504, or Micro800 with default 488). Production hosting should wire `OnWarning` to the application logger; the unit tests (`AbCipConnectionSizeTests`) collect into a list to assert which warnings fired. The warning fires once per device at `InitializeAsync`. It does not block initialisation — operators may need the override anyway when running newer CompactLogix firmware that does support the larger Forward Open. The controller will reject the connection at runtime if it can't honour the size, and that surfaces through the standard `IHostConnectivityProbe` channel. ### Performance trade-off | Larger Connection Size | Smaller Connection Size | |---|---| | More tags per CIP RTT — higher throughput | Compatible with legacy / narrow firmware | | Bigger buffers held by libplctag native (RSS impact) | Lower memory footprint | | Forward Open rejected on FW19- ControlLogix | Always works (assuming ≥500) | | Required for high-density scan lists | Forces more round-trips — higher latency | For most FW20+ ControlLogix shops, the default `4002` is correct and the override is unnecessary. The override is mainly useful when: 1. **Migrating off Kepware** with a controller-specific slider value already tuned in production — set Connection Size to match. 2. **Mixed-firmware fleets** where some controllers are still on FW19 — set the legacy controllers explicitly to `504`. 3. **CompactLogix L1/L2/L3** running newer firmware that supports a larger Forward Open than the family-default 504 — bump the override up. 4. **Micro800** never goes above `488`; the override is for documentation / discoverability rather than capability change. ### libplctag wrapper limitation The libplctag .NET wrapper (1.5.x) does not expose `connection_size` as a public `Tag` property. The driver propagates the value via reflection on the wrapper's internal `NativeTagWrapper.SetIntAttribute("connection_size", N)` after `InitializeAsync` — equivalent to libplctag's `plc_tag_set_int_attribute`. Because libplctag native parses `connection_size` only at create time, this is **best-effort** until either: - the libplctag .NET wrapper exposes `ConnectionSize` directly (planned in the upstream backlog), in which case the reflection no-ops cleanly, or - libplctag native gains post-create hot-update for `connection_size`, in which case the call lands as intended. In the meantime the value is correctly stored on `DeviceState.ConnectionSize` + surfaces in every `AbCipTagCreateParams` the driver builds, so the override is observable end-to-end through the public driver surface and unit tests even if the underlying wrapper isn't yet honouring it on the wire. Operators who need *guaranteed* Connection Size enforcement against FW19 controllers today can pin `libplctag` to a wrapper version that exposes `ConnectionSize` once one is available, or run a libplctag native build patched for runtime updates. Both paths are tracked in the AB CIP plan. ### See also - [`docs/Driver.AbCip.Cli.md`](../Driver.AbCip.Cli.md) — AB CIP CLI uses the family default ConnectionSize on each invocation; per-device overrides only apply through the driver's device-config JSON, not the CLI's command-line. - [`docs/drivers/AbServer-Test-Fixture.md`](AbServer-Test-Fixture.md) §5 — ab_server simulator does not enforce the narrow CompactLogix cap, so Connection Size correctness is verified by unit tests + Emulate-rig live smokes only. - [`PlcFamilies/AbCipPlcFamilyProfile.cs`](../../src/ZB.MOM.WW.OtOpcUa.Driver.AbCip/PlcFamilies/AbCipPlcFamilyProfile.cs) — per-family default values. - [`AbCipConnectionSize`](../../src/ZB.MOM.WW.OtOpcUa.Driver.AbCip/AbCipConnectionSize.cs) — range bounds + legacy-firmware threshold constants. ## Addressing mode ### What it is CIP exposes two equivalent ways to address a Logix tag on the wire: 1. **Symbolic** — the request carries the tag's ASCII name and the controller parses + resolves the path on every read. This is the libplctag default and what every previous driver build has used. 2. **Logical** — the request carries a CIP Symbol Object instance ID (a small integer assigned by the controller when the project was downloaded). The controller skips ASCII parsing entirely; the lookup is a single instance-table dereference. Logical addressing is faster on the controller side and produces smaller request frames. The trade-off is that the driver has to learn the name → instance-id mapping once, by reading the `@tags` pseudo-tag at startup, and the resolution step has to repeat after a controller program download (instance IDs are re-assigned). ### Enum values `AbCipDeviceOptions.AddressingMode` (`AddressingMode` enum, default `Auto`) takes one of three values: | Value | Behaviour | |---|---| | `Auto` | Driver picks. **Currently resolves to `Symbolic`** — a future PR will plumb a real auto-detection heuristic (firmware version + symbol-table size). | | `Symbolic` | Force ASCII symbolic addressing on the wire. The historical default. | | `Logical` | Use CIP logical-segment / instance-ID addressing. Triggers a one-time `@tags` walk at the first read; subsequent reads consult the cached map. | `Auto` is documented as "Symbolic-for-now" so deployments setting `Auto` explicitly today will silently flip to a real heuristic when one ships, matching the spirit of the toggle. Operators who want to pin the wire behaviour should set `Symbolic` or `Logical` directly. ### Family compatibility Logical addressing depends on the controller implementing CIP Symbol Object class 0x6B with stable instance IDs. Older AB families don't: | Family | Logical addressing supported? | Why | |---|---|---| | `ControlLogix` | yes | Native class 0x6B support, FW10+ | | `CompactLogix` | yes | Same wire protocol as ControlLogix | | `GuardLogix` | yes | Same wire protocol; safety partition is tag-level, not addressing-level | | `Micro800` | **no** | Firmware does not implement class 0x6B; instance-ID reads trip CIP "Path Segment Error" 0x04 | | `SLC500` / `PLC5` | **no** | Pre-CIP families; PCCC bridging only — no Symbol Object at all | When `AddressingMode = Logical` is set on an unsupported family, the driver **falls back to Symbolic with a warning** (via `OnWarning`) instead of faulting. This keeps mixed-firmware deployments working — operators can ship a uniform "Logical" config across the fleet and let the driver downgrade the families that can't honour it. The driver-level decision is exposed via `PlcFamilies.AbCipPlcFamilyProfile.SupportsLogicalAddressing` and resolved at `AbCipDriver.InitializeAsync` time; the resolved mode is stored on `DeviceState.AddressingMode` and threaded through every `AbCipTagCreateParams` from then on. ### One-time symbol-table walk The first read on a Logical-mode device triggers a one-time `@tags` walk via `LibplctagTagEnumerator` (the same component used for opt-in controller browse). The driver caches the resulting name → instance-id map on `DeviceState.LogicalInstanceMap`; subsequent reads consult the cache without issuing another walk. The walk is gated by a per-device `SemaphoreSlim` so parallel first-reads serialise on a single dispatch. The walk happens in `AbCipDriver.EnsureLogicalMappingsAsync` and runs only for devices that have actually resolved to `Logical`. Symbolic-mode devices skip the walk entirely. Walk failures are non-fatal: the `LogicalWalkComplete` flag still flips to `true` so the driver does not re-attempt indefinitely, and per-tag handles fall back to Symbolic addressing on the wire (libplctag's default). A controller program download invalidates the instance IDs. There is no auto-invalidation today — operators trigger a fresh walk by either restarting the driver or calling `RebrowseAsync` (the same surface that clears the UDT template cache) with logic-mode plumbing extended in a future PR. For now, restart-on-download is the recommended workflow. ### libplctag wrapper limitation The libplctag .NET wrapper (1.5.x) does **not** expose a public knob for instance-ID addressing. The driver translates Logical-mode params into libplctag attributes via reflection on `NativeTagWrapper.SetAttributeString("use_connected_msg", "1")` + `SetAttributeString("cip_addr", "0x6B,N")` — same best-effort fallback pattern as the Connection Size knob. This means **Logical mode is observable end-to-end through the public driver surface and unit tests today**, but the actual wire behaviour remains Symbolic until either: - the upstream libplctag .NET wrapper exposes the `UseConnectedMessaging` + `CipAddr` properties on `Tag` directly (planned in the upstream backlog), in which case the reflection no-ops cleanly, or - libplctag native gains post-create hot-update for `cip_addr`, in which case the call lands as intended. The driver-level bookkeeping (resolved mode, instance-id map, family compatibility, fall-back warning) is fully wired so the upgrade path is purely a wrapper-version bump. ### Performance trade-off | Symbolic addressing | Logical addressing | |---|---| | Works everywhere | Requires Symbol Object class 0x6B | | ASCII parse on every read (controller-side cost) | One-time walk; instance-id lookup thereafter | | No first-read latency | First read on a device pays the `@tags` walk | | Smaller code surface | Stale on program download — restart driver to re-walk | | Best for small / sparse tag sets | Best for >500-tag scans with stable controller | For scan lists in the **single-digit-tag** range, the per-poll ASCII parse cost is invisible. For **medium** scan lists (~100 tags) the gain is real but small — typically 5–10% per CIP RTT depending on tag-name length. The break-even point is where the ASCII-parse overhead starts dominating, roughly **>500 tags** in a tight scan loop, which is also where libplctag's own request-packing benefits compound. Large MES / batch projects with many UDT instances are the canonical case. ### Driver config JSON Bind the toggle through the driver-config JSON: ```json { "Devices": [ { "HostAddress": "ab://10.0.0.5/1,0", "PlcFamily": "ControlLogix", "AddressingMode": "Logical" } ] } ``` `"Auto"`, `"Symbolic"`, and `"Logical"` parse case-insensitively. Omitting the field defaults to `"Auto"`. ### See also - [`AbCipDriverOptions.AddressingMode`](../../src/ZB.MOM.WW.OtOpcUa.Driver.AbCip/AbCipDriverOptions.cs) — enum definition + per-value docstrings. - [`AbCipPlcFamilyProfile.SupportsLogicalAddressing`](../../src/ZB.MOM.WW.OtOpcUa.Driver.AbCip/PlcFamilies/AbCipPlcFamilyProfile.cs) — family compatibility table source-of-truth. - [`docs/drivers/AbServer-Test-Fixture.md`](AbServer-Test-Fixture.md) § "What it actually covers" — Logical-mode fixture coverage status. - [`AbCipAddressingModeBenchTests`](../../tests/ZB.MOM.WW.OtOpcUa.Driver.AbCip.IntegrationTests/AbCipAddressingModeBenchTests.cs) — scaffold for the wall-clock comparison; gated on `[AbServerFact]`. ## Read strategy (PR abcip-3.3) A per-device toggle that controls how multi-member UDT batches are read. The default `Auto` value matches every previous build's behaviour for dense reads but switches to per-member bundling when only a handful of members of a large UDT are subscribed — the canonical "5 of 50" sparse-subscription case where reading the whole UDT buffer just to extract a few fields wastes wire bandwidth. ### Three modes | Mode | When to use | |---|---| | `WholeUdt` | Most members of every subscribed UDT are read together. One libplctag read per parent UDT, members decoded in-memory at their byte offsets. The task #194 default. | | `MultiPacket` | A few members of a large UDT are subscribed at a time. One read per subscribed member, bundled per parent into one CIP Multi-Service Packet. | | `Auto` (default) | Planner picks per-batch from the subscribed-member fraction (see *Sparsity threshold*). | ### Sparsity threshold Auto mode divides `subscribedMembers / totalMembers` for each parent UDT and picks `MultiPacket` when the fraction is **strictly less than** the threshold, else `WholeUdt`. Default threshold `0.25` — a 1/4 subscription is the rough break-even where the wire-cost of one whole-UDT read still beats N member reads on a ControlLogix 4002-byte connection-size buffer; above 1/4, the per-member overhead dominates. Tune via `AbCipDeviceOptions.MultiPacketSparsityThreshold` (clamped to `[0..1]`). Threshold `0.0` = "never MultiPacket"; `1.0` = "always MultiPacket when any member is subscribed." ### Family compatibility `MultiPacket` requires CIP service `0x0A` (Multi-Service Packet) on the controller. Source of truth is [`AbCipPlcFamilyProfile.SupportsRequestPacking`](../../src/ZB.MOM.WW.OtOpcUa.Driver.AbCip/PlcFamilies/AbCipPlcFamilyProfile.cs): | Family | `SupportsRequestPacking` | |---|---| | ControlLogix | yes | | CompactLogix | yes | | GuardLogix | yes (wire identical to ControlLogix) | | Micro800 | **no** | | SLC500 / PLC5 (when those profiles ship) | **no** | User-forced `MultiPacket` against a non-packing family logs a warning at device init and falls back to `WholeUdt`. `Auto` against a non-packing family stays `Auto` at the device level — the per-batch heuristic caps the strategy to `WholeUdt` so the wire never sees a Multi-Service-Packet against a controller that can't decode it. ### libplctag wrapper limitation The libplctag .NET wrapper (1.5.x) does not expose the `0x0A` service as a public knob — same wrapper-version constraint that gates PR abcip-3.1's `connection_size` and PR abcip-3.2's instance-ID addressing. Today's MultiPacket runtime therefore issues N libplctag reads sequentially when the planner picks the strategy; the wire-level bundling lands cleanly when an upstream wrapper release exposes the primitive. The driver-level bookkeeping (resolved strategy, per-batch heuristic, family-compat fall-back, per-device dispatch counters) is fully wired so the upgrade path is a wrapper-version bump only — the planner already produces the right plan, and `AbCipMultiPacketReadPlanner.Build` is covered by unit tests that pin the plan shape rather than wire bytes. ### Driver config JSON ```json { "Devices": [ { "HostAddress": "ab://10.0.0.5/1,0", "PlcFamily": "ControlLogix", "ReadStrategy": "Auto", "MultiPacketSparsityThreshold": 0.25 } ] } ``` `"Auto"`, `"WholeUdt"`, and `"MultiPacket"` parse case-insensitively. Omitting the field defaults to `"Auto"`. Omitting `MultiPacketSparsityThreshold` defaults to `0.25`. ### See also - [`AbCipDriverOptions.ReadStrategy`](../../src/ZB.MOM.WW.OtOpcUa.Driver.AbCip/AbCipDriverOptions.cs) — enum definition + per-value docstrings. - [`AbCipMultiPacketReadPlanner`](../../src/ZB.MOM.WW.OtOpcUa.Driver.AbCip/AbCipMultiPacketReadPlanner.cs) — plan shape + Auto-mode heuristic. - [`AbCipPlcFamilyProfile.SupportsRequestPacking`](../../src/ZB.MOM.WW.OtOpcUa.Driver.AbCip/PlcFamilies/AbCipPlcFamilyProfile.cs) — family compatibility table source-of-truth. - [`AbCipReadStrategyTests`](../../tests/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests/AbCipReadStrategyTests.cs) — device-init resolution, heuristic edges, dispatch counters, DTO round-trip. - [`AbCipEmulateMultiPacketReadTests`](../../tests/ZB.MOM.WW.OtOpcUa.Driver.AbCip.IntegrationTests/Emulate/AbCipEmulateMultiPacketReadTests.cs) — golden-box-tier wire-level coverage scaffold; gated on `AB_SERVER_PROFILE=emulate`.