using Shouldly; using Xunit; using ZB.MOM.WW.OtOpcUa.Core.Abstractions; namespace ZB.MOM.WW.OtOpcUa.Driver.S7.IntegrationTests.S7_1500; /// /// Live gate for R07:P2 over real S7comm. The fixture's M area is 256 bytes. MW10 is seeded /// (4097); MD254 runs two bytes past the end of the area. With the gap budget opened wide /// the planner merges them into ONE block MB10..258, which the CPU refuses — before the fix /// that made the perfectly readable MW10 Bad (and the driver Degraded) on every poll. /// [Collection(Snap7ServerCollection.Name)] [Trait("Category", "Integration")] [Trait("Device", "S7_1500")] public sealed class S7_1500SpanRefusalTests(Snap7ServerFixture sim) { /// The good neighbour of an over-running member keeps reading its seeded value, every pass. [Fact] public async Task A_member_past_the_area_end_does_not_spoil_its_span_neighbour() { if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason); var ct = TestContext.Current.CancellationToken; var options = new S7DriverOptions { Host = sim.Host, Port = sim.Port, CpuType = S7CpuType.S71500, Timeout = TimeSpan.FromSeconds(5), Probe = new S7ProbeOptions { Enabled = false }, // Wide enough that MW10 and MD254 land in one planned span. SpanReadMaxGapBytes = 256, SpanReadMaxSpanBytes = 256, RawTags = S7RawTags.Entries( new S7TagDefinition("Mk/Word10", "MW10", S7DataType.UInt16, Writable: false), new S7TagDefinition("Mk/PastEnd", "MD254", S7DataType.Int32, Writable: false)), }; await using var drv = new S7Driver(options, driverInstanceId: "s7-span-refusal-live"); await drv.InitializeAsync("{}", ct); for (var pass = 0; pass < 3; pass++) { var r = await drv.ReadAsync(["Mk/Word10", "Mk/PastEnd"], ct); r[0].StatusCode.ShouldBe(0u, $"pass {pass}: the in-range neighbour must be served"); Convert.ToInt32(r[0].Value).ShouldBe(4097); r[1].StatusCode.ShouldNotBe(0u, "the over-running member is refused on its own"); drv.GetHealth().State.ShouldBe(DriverState.Healthy, "a refusal is not a comms fault"); } } }