A notifier folder read one event source, its NodeId identifier (a RawPath or an EquipmentId). AVEVA stores a
Galaxy object's A&E history under the object's tag_name (Source_Object), so AVEVA's own alarm and event
history reached no production folder. Its lower-case property keys were also missed, so every row read
Severity 1 with no ConditionName.
Sources. A folder's event history now reads its own source plus the Galaxy object of every native condition
that fires on it live: those parented under it and those WireAlarmNotifiers wired to it. Live and history use
the same membership. The object comes from the condition's Galaxy alarm reference, its raw tag's attributeRef,
up to the first '.':
- The composer reads it with the driver's own parser (GalaxyAttributeRef, shared with GalaxyDriver), only for
a GalaxyMxGateway tag with an alarm (RawTagPlan.NativeAlarmReference, part of plan equality).
- The applier binds it after materialising the condition (IOpcUaAddressSpaceSink.BindNativeAlarmHistory,
forwarded by the deferred sink). A rebuild or the condition's removal forgets it.
Each object is read with the #882 rule: its own events and <Object>.<Attribute> rows, never a prefix sibling.
Fan-out. historiangw's ReadEvents filter is a single predicate, so there is one request per source; the wire
contract is unchanged. EventSourceFanOut merges the reads as one source:
- order is (time, source position, arrival), reversed for a reverse read; ties are never re-sorted by EventId,
so the boundary skip stays stable;
- duplicates by EventId are dropped and the merge is cut to the cap;
- a truncated source bounds the page at the time it stopped.
Paging, continuation points (bound to the whole source set), the walked-back reverse read and the tie-cluster
over-fetch are unchanged. A folder with one source is read exactly as before.
ACL. Every source is read inside the folder's own HistoryRead, after AuthorizeHistoryRead (#826). A denied
folder reads nothing and fails closed.
Mapping (EventMapper, property names now case-insensitive):
- Severity: an AVEVA row's priority goes through GalaxyAlarmPriority, the table live Galaxy alarms use
(MxAccessSeverityMapper now delegates to it), so history matches live. Otherwise severity (OtOpcUa's own
rows, which AVEVA stores lower-cased), clamped. AVEVA's own 1-4 severity is ignored. The table ranks a
higher priority as more severe, which inverts AVEVA's convention: filed as #887.
- An AVEVA row whose source_conditionvariable names a native condition that fires on the folder takes that
condition's SourceNode and live ConditionName. Otherwise ConditionName is alarmname or the condition
variable's attribute.
- alarm_id/alarmid map to AlarmId.
Tests:
- GalaxyEquipmentEventHistoryWireTests (4, real SDK session, production Gateway backend, AVEVA-shaped fake
gateway): equipment EqA backed by objects Oven_007 + OvenDoor_07. Covers object and attribute events from
both objects, the prefix sibling excluded, cross-object and in-object ties, forward paging at 1-4 a page,
reverse whole and paged, SourceNode/ConditionName/Severity, the raw device folder, ACL deny with no backend
call plus a granted positive control, and a rebuild forgetting the bindings.
- EventSourceFanOutTests (8), EventMapper AVEVA cases (11), GalaxyAttributeRefTests (16), a composer test and
an applier ordering test.
- Mutation-checked, 17 mutants, all killed. Covered: parent-only membership, no scope, a case-sensitive
condition match, no condition rewrite, no truncation bound, EventId tie order, no sort, no cap, no stop at
the bound, unreversed source order, no dedupe, no '.' boundary, priority ignored, case-sensitive keys, no
applier bind, no deferred forward, and a composer that ignores the driver type. The forget-on-rematerialise
guard survives as belt-and-braces: the rebuild clear covers it.
- Live, read-only, no WinRM, vd03 HistorianGateway ea9f21c: equipment folder EQ-886-ZipsenLeft (objects
DevWinPlatform + Left_001). It read 0 events before and 92 now, equal to the unfiltered read's rows for both
objects. 1/7-event pages and reverse whole/5-event pages agree, and 73 rows resolve to their live condition.
diff_runs vs the #882 run: 221/226 identical. The 5 that differ are expected: DevWinPlatform Severity
1 -> 750/1000, and #881 capabilities.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Clears CommentChecker findings in src/ (3,280 -> 209, the remainder being false
positives like PLC-5/IEEE-754/M0.0) by adding missing summaries/params/returns,
normalising inheritdoc usage, and removing Gitea/review tracking IDs while keeping
the rationale they annotated. Comment-only: comment-stripped sources are identical
to the parent commit.
A tie cluster's truncated read left the width at one tick; once the gap
above it was under two milliseconds nothing floored it, so segHi
stepped down one tick per read: 30 rows at one ms 0.3 s below hi with a
carried 1 s width took 10,006 identical reads (S8). (a) The top-anchored
width is floored at the granularity, Min kept; (b) a segment no wider
than the granularity is the unit that escalates to
MaxTieClusterOverfetch and then refuses - per millisecond, exact for the
ms-resolution Gateway (documented). Both are needed: the floor alone
loops on crowded reads with a small tie budget. S8 is a repo test
(4 shapes, reads <= 30, 0 repeated requests); random-data tests now
measure the refusal unit as rows in any 1 ms window. Reviewer harness,
5,000 seeds x default/MSONLY/CROWD: worst page 70 reads (default/MSONLY),
63 (CROWD) at M=65536, p99.9 27-37; no page over 500 reads at any tie
budget.
The null source has no history in either direction; reporting false
made the server walk an empty reverse events read back through three
empty forward reads. It now answers the reverse overload with the empty
result itself (guard test unchanged: it still declares both members).
GatewayHistorianDataSource.ReadEventsAsync sized its result list to
maxEvents, which is int.MaxValue for NumValuesPerNode = 0: every
uncapped Gateway events read (forward on master, and the new walked
reverse one) threw 'Array dimensions exceeded' and counted as a backend
failure. Capacity is bounded at 1024. The events walk delegate moved to
ReverseEventsReader so it is tested over the real Gateway source