Commit Graph

4 Commits

Author SHA1 Message Date
Joseph Doherty db751d12a5 feat(alarms): condition Quality tracks source connectivity (#477)
v2-ci / build (pull_request) Successful in 4m49s
v2-ci / unit-tests (pull_request) Failing after 3h11m25s
Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good
so every native + scripted condition reported Good unconditionally — a
comms-lost device still showed a healthy, inactive, Good condition (a
wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs
bucketing on IsGood) could not tell "genuinely inactive" from "lost contact".

Layer 1 — make Quality a real, plumbed field:
- AlarmConditionSnapshot gains OpcUaQuality Quality (default Good).
- MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good).
- WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality
  member so a quality-bucket change fires a Part 9 event.

Layer 2 — drive native quality from driver connectivity (a comms-lost driver
emits no alarm transitions, and an alarm-bearing raw tag has no value variable,
so quality can't come from either existing channel):
- DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting.
- DriverHostActor fans it to every native condition the driver owns as
  OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect).
- New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and
  fires only on a bucket change — never touches Active/Acked/Retain (an active
  alarm that loses comms stays active). Not a full-snapshot re-projection, so it
  can't clobber severity/message and works for a never-fired condition.
  Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the
  reflection forwarding guard). Ungated by redundancy role; no /alerts row.

Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3).

Tests: node-level (materialise/project/no-clobber/unknown-node no-op),
NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor
fan-out, OpcUaPublishActor routing, and the wire-level guard
(Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified
against a simulated pre-fix always-Good server. Existing DriverInstanceActor
parent probes ignore the new ConnectivityChanged.

Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)";
design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.
2026-07-17 15:10:04 -04:00
Joseph Doherty 3cf3576c75 fix(v3-batch4-wp4): alarm fan-out hardening — event-delivery test, resolution-failure meter, teardown guards (Wave C review M1/M2/M3/L1/L3)
M1 — over-the-wire event-delivery proof (new NativeAlarmMultiNotifierEventDeliveryTests
in OpcUaServer.IntegrationTests): boots the real server, wires one condition to two
equipment folders, fires ONE transition, and asserts a Server-object subscriber gets
EXACTLY ONE event (the shared-InstanceStateSnapshot queue dedup), plus overlapping
Server + equipment-folder subscribers each get exactly one copy. Captures via the
subscription FastEventCallback keyed by ClientHandle (the per-item Notification/DequeueEvents
path delivers nothing for these conditions in the SDK client — the working capture is the
fast callback).

M2 — resolution-failure signal + path-agreement tripwire (AddressSpaceApplier): when a
native alarm HAS ReferencingEquipmentPaths but NONE resolve to an equipment folder, count
it as a failed node (degraded-apply meter) + LogWarning instead of a silent skip; documented
the DisplayName==Name coupling as a binding invariant. Tests:
Composer_referencing_equipment_paths_resolve_back_to_equipment_ids_in_the_applier (real
composer output → applier inversion) + ..._unresolvable_referencing_equipment_counts_as_failed.

M3 — WireAlarmNotifiers is now a RECONCILE (unwires a folder dropped from the supplied set,
bidirectionally) so a future surgical ChangedRawTags path can't leave a de-referenced
equipment receiving the alarm; binding guard comment added on the classifier's
ChangedRawTags→Rebuild branch. Test: WireAlarmNotifiers_reconciles_a_dropped_folder_out_of_the_notifier_set.

L1 — MaterialiseAlarmCondition's kind-swap drop-and-recreate now calls
UnwireAlarmNotifiers(conditionKey) before discarding the old instance (teardown symmetry).

L3 — BuildEquipmentIdByFolderPath LogWarnings on a duplicate Area/Line/Name collision
(defense-in-depth; UNS uniqueness prevents it).

Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
2026-07-16 12:52:34 -04:00
Joseph Doherty 8ebc712eff feat(v3-batch4-wp4): multi-notifier native alarms (single ReportEvent → raw + equipment notifiers) + teardown symmetry
Materialize each native alarm ONCE at the raw tag (ConditionId = RawPath, Raw
realm); wire the single condition as an SDK event notifier of each referencing
equipment's UNS folder so one ReportEvent fans to every root without
re-reporting per root (which would break Server-object dedup + Part 9 ack
correlation).

- New sink method WireAlarmNotifiers(alarmNodeId, alarmRealm,
  notifierFolderNodeIds, notifierFolderRealm) on IOpcUaAddressSpaceSink,
  forwarded through DeferredAddressSpaceSink + SdkAddressSpaceSink +
  NullOpcUaAddressSpaceSink (the forwarding-trap guard); auto-covered by the
  DeferredSinkForwardingReflectionTests realm + forwarding guards + a
  hand-written forward test.
- OtOpcUaNodeManager: the normative AddNotifier(isInverse) pair + idempotent
  EnsureFolderIsEventNotifier per equipment folder; tracked per condition in
  _alarmNotifierWiring. Teardown symmetry: RemoveNotifier(bidirectional:true) on
  RebuildAddressSpace, RemoveAlarmConditionNode, and RemoveEquipmentSubtree so no
  inverse-notifier entry leaks across redeploys.
- AddressSpaceApplier.MaterialiseRawSubtree wires notifiers for each native alarm
  tag, resolving its ReferencingEquipmentPaths (Area/Line/Equipment) to the
  EquipmentId folder NodeIds via BuildEquipmentIdByFolderPath.
- AlarmTransitionEvent gains ReferencingEquipmentPaths (empty default); /alerts
  renders the referencing-equipment list as display metadata.
- Un-skipped + rewrote the native-alarm dark tests
  (DriverHostActorNativeAlarmTests x6, DriverHostActorNativeAlarmAckRoutingTests
  x1) for the v3 raw-condition model; new NodeManagerMultiNotifierAlarmTests
  proves multi-notifier wiring + teardown symmetry (no leaked duplicates after a
  re-trip) + applier wiring test.

Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
2026-07-16 12:07:11 -04:00
Joseph Doherty 3efcf8014b feat(v3-batch4-wp3): raw-only binding + UNS fan-out + write routing
Wave B of Batch 4 — the runtime binding seam for the dual namespace.

Applier (both realms, explicit realm at every sink call site):
- MaterialiseRawSubtree: Raw containers as folders + Raw tags as variables
  keyed by RawPath (native-alarm tag → single Part 9 condition at the RawPath),
  all in AddressSpaceRealm.Raw; historian tagname = override else RawPath.
- MaterialiseUnsReferences: each UNS reference Variable under its equipment
  folder (Uns realm) + an Organizes UNS->Raw edge; inherits writable/array/
  historian tagname from the backing raw tag (both NodeIds -> one tagname).
- FeedHistorizedRefs / ProvisionHistorizedTags now source RAW tags (mux ref
  stays single, keyed by RawPath); ApplyPureRemove tears down raw tags + UNS
  refs in place (raw-container removal falls back to rebuild).

DriverHostActor (dual-NodeId, single-source fan-out):
- _nodeIdByDriverRef value gains a realm (NodeRealmRef); rebuilt from
  RawTags UNION UnsReferenceVariables so one (DriverInstanceId, RawPath) fans
  to the raw NodeId AND every referencing UNS NodeId with identical
  value/quality/timestamp. Write inverse map keyed by the bare id; the
  ns-qualified NodeId the write hook passes is normalised (BareNodeId) so a
  write to either NodeId resolves the same driver ref (-> RawPath write).
- Native raw alarm condition routing is realm-tagged (Raw); AttributeValueUpdate
  + AlarmStateUpdate carry the realm through to the sink.

Retire EquipmentNodeIds -> V3NodeIds.Uns (applier/VirtualTagHostActor) and
RawPaths.Combine (DiscoveredNodeMapper, discovered nodes are Raw now).

DeploymentArtifact.ParseComposition emits the Raw + UNS subtrees byte-parity
with the composer (reconstruct entities -> AddressSpaceComposer.Compose).

Sink surface: removed the transitional `= AddressSpaceRealm.Uns` defaults from
IOpcUaAddressSpaceSink / ISurgicalAddressSpaceSink / SdkAddressSpaceSink /
DeferredAddressSpaceSink / NullOpcUaAddressSpaceSink — every call site is now
explicit (realm reordered before the trailing optionals on EnsureVariable +
MaterialiseAlarmCondition). Node-manager convenience methods keep their
defaults (they are not the interface impl; Sdk delegates explicitly).

Tests: rewrote DriverHostActorLiveValueTests (fan-out drift, 1:N) +
DriverHostActorWriteRoutingTests (dual-NodeId raw/uns write routing) to the v3
raw+uns model; new AddressSpaceApplierRawUnsTests; migrated the EquipmentTags
provisioning/feed tests to RawTags; swept EquipmentNodeIds test callers.

Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
2026-07-16 10:56:31 -04:00