Task 22 (spec section 8 P5), with the controller rulings that exclude PLC-5 and LogixPccc.
- Transport is nullable on both option records; null (key absent) means "use the default" and is
never serialized. Factory DTO parse: absent -> null; a bad value still fails via ParseEnum.
- One resolver per driver (AbCipTransportResolver / AbLegacyTransportResolver), used by the driver
constructor, the Test Connect probe and (through the driver) the CLI.
AbCip: null -> Native. AbLegacy: null -> Native unless any device is Plc5 or LogixPccc, then the
whole driver resolves to Libplctag. Explicit values always win; explicit Native with a
Plc5/LogixPccc device logs one Warning at init.
- Init log shows configured vs effective, e.g. transport=Native (default).
- AdminUI forms: "Default (...)" / "Native (managed)" / "libplctag (fallback)". Default omits the
key on save (reverses Task 19's explicit re-emit, which would have pinned every edited driver).
- CLIs: --transport default|native|libplctag, default "default" via the resolver, so
--plc-type Plc5 with no --transport runs libplctag.
- Tests pinned to Libplctag where a default-path runtime was created: found by instrumenting the
native factories with the current xUnit test name (one unit test, AbLegacyReinitConfigAdoption;
plus the two fixture-gated AbCip probe E2E tests whose exact messages were proven on libplctag).
TransportMatrix and the differential harness already pass explicit transports.
- Switch/resolver/CLI/form tests are falsified by mutating the resolver (default -> Libplctag,
exclusion removed, AbLegacy default -> Libplctag): each mutation turns them red.
- Replaces the inline role-name literal in AbCipDriverFactoryExtensions' ParseEnum call with a named
constant; RoleAuthorityGuardTests was already red on the base commit for that line.
- Docs: AbCip.md / AbLegacy.md default + release note; CLAUDE.md AB section.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
AdminUI driver-instance pages serialized enum config fields (S7 CpuType,
Modbus DataType/Region, AbCip PlcFamily, ...) as JSON *numbers* because each
page's _jsonOpts lacked a JsonStringEnumConverter. The driver factories,
however, deserialize into string-typed DTOs (+ lenient ParseEnum) and throw
when binding a JSON number to a string? — so an AdminUI-authored config
containing any enum field produced a blob the driver could not parse,
faulting the driver on deploy. Proven end-to-end for S7 and Modbus; latent
for AbCip/AbLegacy/TwinCAT/FOCAS/Galaxy/Historian. Only OpcUaClient was safe
(its factory + probe already carried the converter).
Add JsonStringEnumConverter to all 9 driver-instance pages' _jsonOpts and the
8 missing driver probes' _opts (factories unchanged — already string-via-
ParseEnum; strictly more permissive, also lets pages load hand-seeded
string-enum configs back into the form).
Also fix DriverProbeHandshakeE2eTests.AbCip_Green_AgainstSim to probe a real
sim tag (TestDINT) — the no-tags @raw_cpu_type fallback is rejected by the
ab_server sim with ErrorBadParam (a real ControlLogix returns ErrorNotFound,
which the probe treats as reachable; hardware-gated follow-up).
Tests: reflection guard over all driver pages' _jsonOpts (AdminUI.Tests);
factory round-trip + numeric-form-throws guards for S7 and Modbus.
Found by running the never-before-run FB-9/FB-10 live verifies.
Replaces the bare-TCP AbLegacyDriverProbe with a two-phase probe:
Phase 1 is the existing TCP preflight; Phase 2 initialises a
LibplctagLegacyTagRuntime (Protocol.ab_eip + per-family PlcType) to
open a real PCCC-over-EIP session, using AbLegacyProbeOptions.ProbeAddress
("S:0") as the probe tag. Status-code discrimination mirrors the AbCip
probe: ErrorNotFound/ErrorNoMatch/ErrorBadDevice → Ok=true "controller
reachable"; transport errors → Ok=false "handshake failed".
Adds AbLegacyDriverProbeTests (5 unit tests, all green, 168 total).
Cheap-and-fast probe: open TCP socket to the configured endpoint,
close immediately. Surfaces SocketError on failure, latency on
success, "timed out" on caller cancel. Sufficient for the AdminUI
Test Connect "can we reach the host?" question. Richer protocol-
level probes (OPC UA session open, FOCAS handshake, gRPC ping)
are a documented follow-up. Each probe registered as
AddSingleton<IDriverProbe, X> in DriverFactoryBootstrap so they
flow through DI into AdminOperationsActor.
Historian.Wonderware returns a clean "TCP probe not applicable"
result because it communicates over a Windows named pipe, not TCP.
Also adds OpcUaClient + Historian.Wonderware.Client project
references to Host.csproj (both were missing from the driver
ItemGroup).