The AbCip controller browse could never be verified end to end: libplctag's
ab_server answers CIP service 0x55 (Get Instance Attribute List) on the Symbol
Object class with "unsupported", so the `@tags` walk had no backend. #468's own
definition of done offered a sim that serves `@tags` as an alternative to real
hardware; this is that.
The fixture now applies a vendored patch teaching ab_server to serve the Symbol
Object listing, with partial-transfer paging. Correctness is checked against
libplctag's own `list_tags_logix` rather than against our decoder — our decoder
is the thing under test, so its agreement would prove nothing. The clone is also
pinned to a concrete tag: the Dockerfile called `--branch release` "pinned" while
tracking a branch that moves.
That immediately exposed a real defect. CipSymbolObjectDecoder advanced to an
even byte boundary after each symbol name, but entries are packed with no
padding — libplctag walks them by sizeof(entry) + string_len, and a captured
reply confirms it. Any odd-length name therefore desynchronised every entry
behind it, and odd-length names are ordinary. In the live browse below,
`Motor_Run` is 9 bytes and first on the wire, so the old decoder would have
shown that one tag and silently dropped the other eight.
Every existing multi-entry test passed throughout, because the test builder
padded exactly as the decoder did: the two agreed with each other and neither
agreed with a controller. The builder no longer pads, and the layout is pinned
by a captured reply (CipSymbolObjectWireCaptureTests) instead of by a second
statement of the assumption. Restoring the alignment step reddens exactly the
three new tests and none of the 29 others.
Live gate on docker-dev, all three of #468's criteria:
- populated tree — all nine seeded tags render as leaves, in wire order
- refresh re-captures
- leaf commit — Pump_1_Speed + TestDINT saved with their CIP tag paths
The gate also surfaced two things it was not asked about: browse-commit drops
the discovered data type, so a browsed REAL commits as a DINT and the driver
decodes it as one (filed as #536), and Test Connect fails against this fixture
regardless of the device because it probes `@raw_cpu_type` (documented).
TwinCAT and FOCAS still have no browsable backend; #468's AbCip half is closed,
theirs is not.
Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
Replace pre-declared options.Tags (typed <Driver>TagDefinition lists) with
options.RawTags (IReadOnlyList<RawTagEntry>) across all 6 Docker-gated driver
integration suites so they COMPILE against the v3 driver API.
Each project gets a local <Driver>RawTags helper mirroring the unit-test
project's helper: it serialises a typed def back to its TagConfig blob via the
driver's <Driver>TagDefinitionFactory.ToTagConfig and packages it as a
RawTagEntry (RawPath = def.Name; DeviceName = def.DeviceHostAddress for the
multi-device drivers AbCip/AbLegacy/TwinCAT/FOCAS). Test intent (addresses,
data types, device routing, assertions) is unchanged — only the
tag-authoring/config-delivery shape was migrated.
Docker-gated: these still skip at runtime without fixtures; COMPILE is the gate.
KnownProfiles.All used a { get; } = [...] initialiser declared textually
before the static readonly profile fields it references, so C# static-init
order captured an all-null list. ForFamily() then NRE'd on p.Family, faulting
AbServerFixture..ctor and blocking the whole AbCip.IntegrationTests suite.
Expression-body it so it evaluates on access, after the fields are set.
Live-verified against the controllogix fixture: suite goes 6F/1P/3skip ->
10 pass / 0 fail / 3 skip (skips = emulator-mode tests).
Integration-sweep follow-up #1 (archreview/plans/INTEGRATION-SWEEP-STATUS.md).
Inject the custom UnwrappedCapabilityCallAnalyzer as an OutputItemType=Analyzer
ProjectReference from Directory.Build.props (excluding the analyzer + its test
project) so OTOPCUA0001 runs on every src/ and tests/ compilation — it previously
enforced its CapabilityInvoker-wrapping rule against nothing but its own 31 unit
tests (the 'built-but-never-wired' failure mode).
Triage of the ~280 surfaced hits, three categories:
1. RESILIENCE-DISPATCH-GAP (7 sites, DriverInstanceActor x6 + GenericDriverNodeManager
x1): a REAL, previously-untracked gap the analyzer caught on first wiring — the
Phase 6.1 CapabilityInvoker resilience pipeline (retry/breaker/bulkhead/telemetry)
is constructed ONLY in tests and was never wired into the production dispatch
layer. Scoped per-site #pragma with a greppable RESILIENCE-DISPATCH-GAP marker
explicitly noting these are tracked-but-not-intentional, pending the dispatch-wiring
remediation (filed as a follow-up). Keeps the analyzer live everywhere else in
those projects so a NEW unwrapped call still fails the build.
2. Driver-INTERNAL self-calls (3 sites, AbCipAlarmProjection x2 + S7Driver x1):
a driver's own poll/ack path calling its own capability method. The invoker wraps
the driver from the dispatch layer OUTWARD; a driver re-wrapping its own internal
calls would double-wrap. Genuinely intentional — scoped #pragma with that rationale.
3. Wire-level test suites + manual-testing CLIs (12 projects): invoke drivers directly
by design — the analyzer's own documented intentional case. Project-level NoWarn
with a comment.
Verified: full solution build green, 0 OTOPCUA0001 hits; analyzer's 31 tests pass;
negative control — dropping one dispatch-gap pragma re-fires OTOPCUA0001 and fails
the Runtime build, proving the analyzer is genuinely live tree-wide, not disabled.
Add AbCipEmulateNestedUdtTests (skip-gated, AB_SERVER_PROFILE=emulate) to close
the live-gate gap for nested-struct UDT discovery via CIP Template Object (class 0x6C)
threaded by commits 3d8ce4e8/d203f31c. Compiles + skips cleanly against ab_server
(no CIP Template Object service). Update docs/drivers/AbCip.md nested-struct section
to record the shipped decode path, the Emulate-only live-gate, and offline unit coverage.
All five suppressed advisories are now resolved at baseline/resolved versions,
so every NuGetAuditSuppress is removed repo-wide:
- System.Security.Cryptography.Xml (GHSA-37gx-xxp4-5rgx / GHSA-w3x6-4m5h-cxqf)
-> fixed by the .NET 10 baseline (10.0.6)
- OPCFoundation Opc.Ua.Core (GHSA-h958-fxgg-g7w3) -> fixed at resolved 1.5.378.106
Two were still live and are now patched via direct security pins:
- OpenTelemetry.Api 1.9.0 -> 1.15.3 (GHSA-g94r-2vxg-569j) pinned in Cluster;
Runtime/ControlPlane/AdminUI + tests inherit via project reference
- Tmds.DBus.Protocol 0.20.0 -> 0.21.3 (GHSA-xrw6-gwf8-vvr9) pinned in Client.UI
Also correct the Historian sidecar runtime comments (x86 -> x64, matching the
csproj PlatformTarget). Solution audit: 0 vulnerable packages; full build clean.
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
Adds Directory.Packages.props (ManagePackageVersionsCentrally) and
Directory.Build.props (net10.0/nullable/implicit usings/LangVersion latest).
Strips Version attributes from every csproj PackageReference and consolidates
versions into the central file.
Side fixes (necessary to keep the build green on .NET SDK 10.0.105 on macOS):
- Microsoft.CodeAnalysis.CSharp{,.Workspaces}: 5.3.0 -> 5.0.0. The 5.3.0
analyzer DLL references compiler 5.3.0.0 and the local SDK ships compiler
5.0.0.0, producing CS9057 on every project that loaded the Analyzers
output. Master itself was broken on this machine pre-change.
- Server + Server.Tests pin OPCFoundation.NetStandard.Opc.Ua.{Configuration,
Client} to 1.5.374.126 via VersionOverride, matching Opc.Ua.Server's
pin. Mixing 1.5.378.106 Opc.Ua.Core transitively with 1.5.374.126
Opc.Ua.Server breaks CustomNodeManager2 override signatures
(CS0115 on LoadPredefinedNodes/Browse/HistoryRead*) and CS7069 in
the tests. The pin disappears when the legacy Server project is
deleted in Task 56.
- Client.UI + Client.UI.Tests: NuGetAuditSuppress for
GHSA-xrw6-gwf8-vvr9 (Tmds.DBus.Protocol 0.20.0 reaches both projects
transitively from Avalonia.Desktop on Linux/macOS only).
Deviation from the plan: TreatWarningsAsErrors=true is NOT set in
Directory.Build.props because the pre-v2 Admin/Server test projects carry
~240 xUnit1051 analyzer warnings that would fail the build. New v2 projects
opt in via their own csproj; the global flag can return once the legacy
projects are deleted in Task 56.
UnsTabDragDropE2ETests were timing out at the 'UNS Structure' nav-link
locator because AdminWebAppFactory never registered AdminHubConnectionFactory
/ HubTokenService / DataProtection — ClusterDetail.razor's @inject threw at
circuit boot, so the page never advanced past the Loading placeholder. 2 → 3
pass after the registrations land. Also documents the Modbus standard-vs-
exception_injection coverage matrix in the fixture README + cross-references
docs/drivers/AbServer-Test-Fixture.md from each Emulate test so a developer
landing on a skipped test has a direct doc pointer.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Two real bugs uncovered by re-running with the new fixture defaults
pointing at the shared docker host. Both are test-side, not driver-side.
AbCip — Driver_reads_seeded_DInt_from_ab_server (4 parametrized rows):
Hardcoded 'ab://127.0.0.1:{port}/1,0' in the deviceUri instead of
the resolved fixture.Host. The new 10.100.0.35 default (and any
AB_SERVER_ENDPOINT override) silently couldn't reach this test —
the driver tried to connect to a non-existent localhost:44818 and
returned BadCommunicationError on all 4 profile rows. The sibling
Emulate tests already use the fixture's resolved endpoint; this
smoke test was missed in the original migration.
Fix: deviceUri = $"ab://{fixture.Host}:{fixture.Port}/1,0".
Modbus — Float32_With_CDAB_Roundtrips_Through_Wire:
Test wrote a Float32 to HR 100 (2 consecutive registers: 100+101).
standard.json's writable HR range declares [100,100] only — a
single-cell auto-incrementing register, not a 2-register pair. The
write to register 101 was rejected with Illegal Data Address
(BadOutOfRange).
Fix: moved the tag from HR 100 to HR 200 (in standard.json's
'[200, 209]' scratch range — 10 consecutive writable HRs). The
Float32+CDAB semantic the test exercises is unchanged.
Modbus — Block_Read_Coalescing_Reduces_PDU_Count_End_To_End:
Test read HR 300, 302, 304 — outside both the writable ranges and
the uint16 seed list. pymodbus rejects reads to unseeded HRs even
though 'hr size' is 2048. BadOutOfRange on every read.
Fix: moved the tags from 300/302/304 to 200/202/204 (within the
scratch range). The non-contiguous coalescing semantic (3 tags
inside a 5-register window with MaxReadGap=5) is preserved.
After this commit:
- Modbus.IntegrationTests: 6/38 pass / 32 skip / 0 fail
(was 4 pass / 32 skip / 2 fail; 32 skips are profile-gated
ExceptionInjectionTests — they need MODBUS_SIM_PROFILE=
exception_injection and a different container, intentional gating)
- AbCip.IntegrationTests: 10/12 pass / 2 skip / 0 fail
(was 6 pass / 2 skip / 4 fail; 2 skips are Emulate tests that
need the fixture for separate scenarios)
No driver code changed.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
CLAUDE.md "Docker Workflow" claims (per the 2026-04-28 migration note)
that all fixture-class default endpoints were rewritten to target the
shared Docker host at 10.100.0.35. Audit during today's e2e run showed
the claim was incomplete — five fixture classes still defaulted to
localhost / 127.0.0.1, causing every fixture-touching integration test
to skip with "endpoint unreachable" on a fresh box that hadn't set
the override env vars.
Files corrected:
- tests/.../Modbus.IntegrationTests/ModbusSimulatorFixture.cs
DefaultEndpoint: localhost:5020 → 10.100.0.35:5020
- tests/.../S7.IntegrationTests/Snap7ServerFixture.cs
DefaultEndpoint: localhost:1102 → 10.100.0.35:1102
- tests/.../OpcUaClient.IntegrationTests/OpcPlcFixture.cs
DefaultEndpoint: opc.tcp://localhost:50000 → opc.tcp://10.100.0.35:50000
- tests/.../AbCip.IntegrationTests/AbServerFixture.cs
Host default + ResolveHost fallback: 127.0.0.1 → 10.100.0.35
- tests/.../AbLegacy.IntegrationTests/AbLegacyServerFixture.cs
Host default + ResolveEndpoint fallback: 127.0.0.1 → 10.100.0.35
XML doc comments referencing the old localhost defaults were updated in
the same pass so the class-summary documentation matches the actual
default. The override-via-env-var mechanism (MODBUS_SIM_ENDPOINT,
AB_SERVER_ENDPOINT, AB_LEGACY_ENDPOINT, S7_SIM_ENDPOINT,
OPCUA_SIM_ENDPOINT) is unchanged — pointing at a real PLC or a
locally-running container still works exactly as before.
Verification:
- Solution-wide dotnet build: 0 errors.
- S7.IntegrationTests: 3/3 pass without env-var override.
- OpcUaClient.IntegrationTests: 3/3 pass without env-var override.
- Modbus.IntegrationTests: 4/38 (same as the env-var-override run —
the 2 failures + 32 skips are pre-existing fixture-profile
mismatches unrelated to this fix).
- AbCip.IntegrationTests / AbLegacy.IntegrationTests: same results
as the env-var-override run.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Rewrite src/ and tests/ project paths in docs, CLAUDE.md, README.md, and
test-fixture READMEs to the new module-folder layout (Core/Server/Drivers/
Client/Tooling). References to retired v1 projects (Galaxy.Host/Proxy/Shared,
the legacy monolithic test projects) are left untouched.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Group all 69 projects into category subfolders under src/ and tests/ so the
Rider Solution Explorer mirrors the module structure. Folders: Core, Server,
Drivers (with a nested Driver CLIs subfolder), Client, Tooling.
- Move every project folder on disk with git mv (history preserved as renames).
- Recompute relative paths in 57 .csproj files: cross-category ProjectReferences,
the lib/ HintPath+None refs in Driver.Historian.Wonderware, and the external
mxaccessgw refs in Driver.Galaxy and its test project.
- Rebuild ZB.MOM.WW.OtOpcUa.slnx with nested solution folders.
- Re-prefix project paths in functional scripts (e2e, compliance, smoke SQL,
integration, install).
Build green (0 errors); unit tests pass. Docs left for a separate pass.