Commit Graph

3 Commits

Author SHA1 Message Date
Joseph Doherty
ba52c179fd fix(driver-modbus-addressing): resolve Medium code-review finding (Driver.Modbus.Addressing-002)
Reject an empty 3rd field in the address parser by checking parts[2].Length > 0
before the All(char.IsDigit) guard, so a trailing-colon typo like "40001:F:"
produces a diagnostic instead of silently parsing as a scalar.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-22 09:52:52 -04:00
Joseph Doherty
1837b5a828 fix(driver-modbus-addressing): resolve High code-review finding (Driver.Modbus.Addressing-001)
The DL205 family-native branch routed every V-prefixed address through
DirectLogicAddress.UserVMemoryToPdu, a plain octal-to-decimal decode.
DL205/DL260 system V-memory (V40400 and up) is not a simple octal decode:
the CPU relocates the system bank to Modbus PDU 0x2100. Octal-decoding
V40400 produced 16640 (0x4100), the wrong register, so any tag addressing
a system register through the grammar string silently read/wrote the
wrong PLC memory.

- Add DirectLogicAddress.VMemoryToPdu, which decodes the octal V-address,
  detects the system bank (octal >= V40400 == SystemVMemoryOctalBase) and
  relocates it through SystemVMemoryToPdu to PDU 0x2100; user-bank
  addresses keep the plain octal decode.
- ModbusAddressParser's DL205 V branch now calls VMemoryToPdu instead of
  UserVMemoryToPdu. UserVMemoryToPdu is retained for user-bank-only callers.
- Correct the ModbusFamilyParserTests V40400 assertion (16640 -> 0x2100)
  and add system-bank regression cases plus direct helper coverage.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-22 06:59:39 -04:00
Joseph Doherty
8568f5cd85 docs(code-reviews): comprehensive per-module review pass at 76d35d1
Reviewed all 31 src/ production projects against the 10-category
checklist in REVIEW-PROCESS.md. Each module gets its own findings.md;
code-reviews/README.md is regenerated from them.

334 findings: 6 Critical, 46 High, 126 Medium, 156 Low.

Critical findings:
- Server-001: WriteNodeIdUnknown recurses unconditionally — a HistoryRead
  on an unresolvable node crashes the process (remote DoS).
- Admin-001/002: app-wide auth bypass (RouteView not AuthorizeRouteView)
  plus unauthenticated mutating routes.
- Core.Scripting-001: System.Environment reachable from operator scripts;
  Environment.Exit() terminates the server.
- Core.AlarmHistorian-001: rowIds/events parallel-list desync on a corrupt
  payload misapplies outcomes — silent alarm-event data loss.
- Driver.Galaxy-001: ReconnectSupervisor is built but never triggered, so
  a transient gateway drop permanently kills the event stream.

All findings are Status=Open; resolution is tracked per REVIEW-PROCESS.md
section 4. Review only — no source code changed.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>