Phase 3 PR 43 — Swap ModbusPal to pymodbus for the integration-test simulator. Replaces the .xmpp profiles shipped in PR 42 with pymodbus 3.13.0 ModbusSimulatorServer JSON configs in tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Pymodbus/. Substantive reasons for the swap (rationale block in the test-plan doc): ModbusPal 1.6b is abandoned (last release ~2019), Java GUI-only with no headless mode in the official JAR, and only exposes 2 of the 4 standard Modbus tables (holding_registers + coils — no input_registers, no discrete_inputs). pymodbus is current stable, pure Python CLI (pip install pymodbus[simulator]==3.13.0), exposes all four tables, has built-in declarative actions (increment / random / timestamp / uptime) for dynamic registers, supports custom Python actions for anything more complex, and ships an optional aiohttp-based web UI / REST API for live inspection. Pip-installable on Windows; sidesteps the privileged-port admin requirement by defaulting to TCP 5020.
ModbusSimulatorFixture default port bumped from 502 to 5020 to match the pymodbus convention. Override via MODBUS_SIM_ENDPOINT for a real PLC on its native 502. Skip-message updated to point at the new Pymodbus\serve.ps1 wrapper instead of 'start ModbusPal'. csproj <None Update> rule swapped from ModbusPal/** to Pymodbus/** so the new JSON profiles + serve.ps1 + README copy to test-output as PreserveNewest.
standard.json — generic Modbus TCP server, slave id 1, port 5020, shared blocks=false (independent coils + HR address spaces, more textbook-PLC-like). HR[0..31] seeded with address-as-value via per-register uint16 entries, HR[100] auto-increments via the built-in increment action with parameters minval=0/maxval=65535 (drives subscribe-and-receive integration tests so they have a register that ticks without a write — pymodbus's increment ticks per-access not wall-clock, which is good enough for a 250ms-poll test), HR[200..209] scratch range left at 0 for write tests, coils 0..31 alternating, coils 100..109 scratch. write list covers 0..1023 so any test address is mutable.
dl205.json — AutomationDirect DirectLOGIC DL205/DL260 quirk simulator, slave id 1, port 5020, shared blocks=true (matches DL series memory model where coils/DI/HR overlay the same word address space). Each quirky register seeded with the pre-computed raw uint16 value documented in docs/v2/dl205.md, with an inline _quirk JSON-comment naming the behavior so future-me reading the file knows why HR[1040]=25928 means 'H' lo / 'e' hi (the user's headline string-byte-order finding). Encoded quirks: V0 marker at HR[0]=0xCAFE; V2000 at HR[1024]=0x2000; V40400 at HR[8448]=0x4040; 'Hello' string at HR[1040..1042] first-char-low-byte; Float32 1.5f at HR[1056..1057] in CDAB word order (low word first); BCD register at HR[1072]=0x1234; FC03-128-cap block at HR[1280..1407]; Y0/C0 coil markers at 2048/3072; scratch C-relays at 4000..4007.
serve.ps1 wrapper — pwsh script with a -Profile {standard|dl205} parameter switch. Validates pymodbus.simulator is on PATH (clearer message than the raw CommandNotFoundException), validates the profile JSON exists, builds the right --modbus_server/--modbus_device/--json_file/--http_port arg list, and execs pymodbus.simulator in the foreground. -HttpPort 0 disables the web UI. Foreground exec lets the operator Ctrl+C to stop without an extra control script.
README.md fully rewritten for pymodbus: install command (pip install 'pymodbus[simulator]==3.13.0' — pinned for reproducibility, [simulator] extra pulls aiohttp), per-profile reference tables, the same DL205 quirk → register table from PR 42 but adjusted for pymodbus paths, what's-NEW-vs-ModbusPal section (all four tables, raw uint16 seeding, declarative actions, custom Python action modules, headless, web UI, maintained), trade-offs section (float32-as-two-uint16s for explicit CDAB control, increment ticks per-access not wall-clock, shared-blocks mode for DL205 vs separate for Standard), file-format quick reference for hand-authoring more profiles. References pinned to the pymodbus readthedocs simulator/config + REST API pages.
docs/v2/modbus-test-plan.md harness section rewritten with the swap rationale; PR-history list updated to mark PR 42 SUPERSEDED by PR 43 and call out PR 44+ as the per-quirk implementation track. Test-conventions bullet about 'don't depend on ModbusPal state between tests' generalized to 'don't depend on simulator state' and a note added that pymodbus's REST API can reset state between facts if a test ever needs it.
DL205Profile.cs and DL205SmokeTests.cs xml-doc updated to reference pymodbus / dl205.json instead of ModbusPal / DL205.xmpp.
Functional validation deferred — Python isn't installed on this dev box (winget search returned no matches for Python.Python.3 exact). JSON parses structurally (PowerShell ConvertFrom-Json clean on both files), build clean, .json + serve.ps1 + README all copy to test-output as expected. User installs pymodbus when they want to actually run the simulator end-to-end; if pymodbus rejects the config the README's reference link to pymodbus's simulator/config schema doc is the right next stop.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
|
||
|
|
9de96554dc |
Phase 3 PR 41 — Document AutomationDirect DL205 / DL260 Modbus quirks. Adds docs/v2/dl205.md (~300 lines, 8 H2 sections, primary-source citations) covering every place the DL205/DL260 family diverges from textbook Modbus or has non-obvious behavior a generic client gets wrong. Replaces the placeholder _pending_ list in modbus-test-plan.md with a confirmed-behaviors table that doubles as the integration-test roadmap.
The user explicitly flagged that DL205/DL260 strings don't follow Modbus convention; research turned up that and a lot more. Headline findings: String packing — TWO chars per V-memory register but the FIRST char is in the LOW byte (opposite of the big-endian Modbus convention generic drivers default to). 'Hello' in V2000 reads back as 'eHll o\0' on a textbook decoder. Kepware's DirectLogic driver exposes a per-tag 'String Byte Order = Low/High' toggle specifically for this; we'll need the same. Null-terminated, no length prefix, no dedicated KSTR address space — strings live wherever ladder allocates them in V-memory. V-memory addressing — DirectLOGIC's native V-memory is OCTAL (V2000, V40400) but Modbus is decimal. The CPU translates: V2000 octal = decimal 1024 = Modbus PDU 0x0400. The widespread 'V40400 = register 0' shorthand is wrong on modern firmware (that was DL05/DL06 relative mode); on H2-ECOM100 absolute mode (factory default) V40400 = PDU 0x2100. We'd surface this with an address-format helper in the device profile so operators write V2000 instead of computing 1024 by hand. Word order CDAB for all 32-bit values — DL205 and DL260 agree, ECOM modules don't re-swap. Already supported via ModbusByteOrder.WordSwap; just needs to be the default in the DL205 profile. BCD-as-default numeric storage — bit one I didn't expect. DirectLOGIC stores 'V2000 = 1234' as 0x1234 on the wire (BCD nibbles), not as 0x04D2 (decimal 1234). IEEE 754 Float32 only works when ladder used the explicit R type (LDR/OUTR instructions). We need a new decoder mode for BCD-encoded registers — current code assumes binary integers. FC quantity caps — FC03/04 cap at 128 (above spec's 125 — Bonus territory, current code already respects 125), FC16 caps at 100 (BELOW spec's 123 — important bulk-write batching gotcha). Quantity overrun returns exception 03 IllegalDataValue. Coil/discrete mappings — DL260: X0->discrete input 0, Y0->coil 2048, C0->coil 3072. SP specials at discrete input 1024-1535 RO. These are CPU-wired constants and cannot be remapped; need to be hardcoded in the DL205/DL260 device profile. Register 0 — accepted on DL205/DL260 with ECOM in absolute mode, contrary to the widespread internet claim that 'DirectLOGIC rejects register 0'. That rumour was an older DL05/DL06 relative-mode artefact. Our ModbusProbeOptions.ProbeAddress default of 0 is therefore safe for DL205/DL260. Exception codes — only the standard 01-04. Write-to-protected-bit returns 02 on newer firmware, 04 on older (firmware-transition revision unconfirmed); driver should map both to BadNotWritable. No proprietary exception codes. Behavioral oddities — H2-ECOM100 accepts MAX 4 simultaneous TCP connections (5th refused at TCP accept). No TCP keepalive (intermediate NAT/firewall drops idle sockets after 2-5 min — periodic probe required). No mid-stream resync on malformed MBAP — driver must reconnect + replay. TxId-drop-under-load forum rumour is unconfirmed; our single-flight + TxId-match guard handles it either way. Each H2 section ends with the integration-test names we'd ship per the modbus-test-plan.md DL205_<behavior> convention — twelve named test slots ready for PR 42+ to fill in one at a time. References (8) cited inline, primarily D2-USER-M, HA-ECOM-M, and the Kepware DirectLogic Ethernet driver manual which documents these vendor quirks explicitly because they have to cope with them. modbus-test-plan.md DL205 section rewritten as a priority-ordered table with three columns (quirk / driver impact / test name), pointing the reader at dl205.md for the full reference. Operator-reported items separated into a tail subsection so future-me knows which behaviors are documented vs reproduced-on-hardware. Pure documentation PR — no code changes. The actual driver work (string-byte-order option, BCD decoder mode, V-memory address helper, FC16 cap-per-device-family, multi-client TCP handling) lands one PR per quirk in PR 42+ as ModbusPal validation completes. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com> |
||
|
|
cb7b81a87a |
Phase 3 PR 30 — Modbus integration-test project scaffold. New tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests project is the harness modbus-test-plan.md called for: a skip-when-unreachable fixture that TCP-probes a Modbus simulator endpoint (MODBUS_SIM_ENDPOINT, default localhost:502) once per test session, a DL205 device profile stub (single writable holding register at address 100, probe disabled to avoid racing with assertions), and one happy-path smoke test that initializes the real ModbusDriver + real ModbusTcpTransport, writes a known Int16 value, reads it back, and asserts status=0 + value round-trip. No DL205 quirk assertions yet — those land one-per-PR as the user validates each behavior in ModbusPal (word order for 32-bit, register-zero access, coil addressing base, max registers per FC03, response framing under load, exception code on protected-bit coil write).
ModbusSimulatorFixture is a collection fixture so the 2s TCP probe runs once per run, not per test; SkipReason gets a clear operator-facing message ('start ModbusPal or override MODBUS_SIM_ENDPOINT'). Tests call Assert.Skip(sim.SkipReason) rather than silently returning — matches the test-plan convention and reads cleanly in CI logs. DL205Profile.BuildOptions deliberately disables the background probe loop since integration tests drive reads explicitly and the probe would race with assertions. Tag naming uses the DL205_ prefix so filter 'DisplayName~DL205' surfaces device-specific failures at a glance.
Project references: xunit.v3 + Shouldly + Microsoft.NET.Test.Sdk + xunit.runner.visualstudio (matches the existing Driver.Modbus.Tests unit project), project ref to src/Driver.Modbus. Registered in ZB.MOM.WW.OtOpcUa.slnx under tests/. ModbusPal/README.md documents the dev loop (install ModbusPal jar, load profile, start simulator, dotnet test), explains MODBUS_SIM_ENDPOINT override for real-PLC benchwork, and flags DL205.xmpp as the first profile to add in a follow-up PR.
dotnet test run against the scaffold (no simulator running) skips cleanly: 0 failed, 0 passed, 1 skipped, with the SkipReason surfaced. dotnet build clean (0 warnings, 0 errors). Updated docs/v2/modbus-test-plan.md to mark the scaffold PR done and renumbered future PRs from 'PR 27+' to 'PR 31+' to stay in sync with the actual PR chain.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
|
||
|
|
77d09bf64e |
Phase 3 PR 25 — modbus-test-plan.md: integration-test playbook with per-device quirk catalog. ModbusPal is the chosen simulator; AutomationDirect DL205 is the first target device class with 6 pending quirks to document and cover with named tests (word order for 32-bit values, register-zero access policy, coil addressing base, maximum registers per FC03, response framing under sustained load, exception code on protected-bit coil write). Each quirk placeholder has a proposed test name so the user's validation work translates directly into integration tests. Test conventions section codifies the named-per-quirk pattern, skip-when-unreachable guard, real ModbusTcpTransport usage, and inter-test isolation. Sets up the harness-and-catalog structure future device families (Allen-Bradley Micrologix, Siemens S7-1200 Modbus gateway, Schneider M340, whatever the user hits) will slot into — same per-device catalog shape, cross-device patterns section for recurring quirks that can get promoted into driver defaults. Next concrete PRs proposed: PR 26 for the integration test project scaffold + DL205 profile + fixture with skip-guard + one smoke test, PR 27+ for the individual confirmed quirks one-per-PR.