Against focas-mock:
- H15: a local TCP relay in front of the shared mock takes "the CNC" away and brings it
back without stopping the fixture. A FIXED-only driver goes Degraded with
LastSuccessfulRead frozen and its value Bad, then returns to Healthy with Good values
(the positive control).
- H20: the mock answers cnc_rdalmmsg2 in the 80-byte legacy layout. Nineteen alarms
(1,520 B = 20 x 76) now decode as the 19 seeded alarms; the old length test gives 20,
verified red. A 3-alarm reply is the control.
Refs #740