Joseph Doherty f2bdd8bc1c review(Driver.S7): reject writable array tags at init instead of silent write failure
Re-review at 7286d320. S7-015 (Medium): a Writable array tag had no WriteArrayAsync path
and silently returned BadCommunicationError on write; now rejected at init with a clear
NotSupportedException (read-only arrays still accepted) + TDD. S7-016 (factory JSON can't
produce array tags; needs AdminUI DTO) deferred.
2026-06-19 11:34:34 -04:00
Joseph Doherty a0dccbf8ee test(drivers): tighten driver-page converter guard + clarify S7 numeric case
Code-review follow-ups: the page-coverage test now asserts every *DriverPage
declares a _jsonOpts serializer (so a new page that serialises config a
different way fails the guard, not just converter removal); clarify that 40 ==
(int)S7CpuType.S71500 in the numeric-throws test.
2026-06-19 05:06:43 -04:00
Joseph Doherty 4b14feb373 fix(drivers): serialize driver-config enums as strings in AdminUI pages + probes
AdminUI driver-instance pages serialized enum config fields (S7 CpuType,
Modbus DataType/Region, AbCip PlcFamily, ...) as JSON *numbers* because each
page's _jsonOpts lacked a JsonStringEnumConverter. The driver factories,
however, deserialize into string-typed DTOs (+ lenient ParseEnum) and throw
when binding a JSON number to a string? — so an AdminUI-authored config
containing any enum field produced a blob the driver could not parse,
faulting the driver on deploy. Proven end-to-end for S7 and Modbus; latent
for AbCip/AbLegacy/TwinCAT/FOCAS/Galaxy/Historian. Only OpcUaClient was safe
(its factory + probe already carried the converter).

Add JsonStringEnumConverter to all 9 driver-instance pages' _jsonOpts and the
8 missing driver probes' _opts (factories unchanged — already string-via-
ParseEnum; strictly more permissive, also lets pages load hand-seeded
string-enum configs back into the form).

Also fix DriverProbeHandshakeE2eTests.AbCip_Green_AgainstSim to probe a real
sim tag (TestDINT) — the no-tags @raw_cpu_type fallback is rejected by the
ab_server sim with ErrorBadParam (a real ControlLogix returns ErrorNotFound,
which the probe treats as reachable; hardware-gated follow-up).

Tests: reflection guard over all driver pages' _jsonOpts (AdminUI.Tests);
factory round-trip + numeric-form-throws guards for S7 and Modbus.

Found by running the never-before-run FB-9/FB-10 live verifies.
2026-06-19 04:52:47 -04:00
Joseph Doherty 988a7a938f fix(s7): UInt64 box cast + Timer/Counter transient-write returns BadNotWritable (final review)
M1: add missing (object) cast to UInt64 arm of DecodeScalarBlock switch expression,
matching the Int64 arm style and the comment that each arm is boxed explicitly.
M2: short-circuit Timer/Counter writes in WriteAsync to BadNotWritable before
WriteOneAsync, so transient equipment-tag refs (Writable=true from parser) return
the same status code as authored tags rejected at init — documented in the docs.
Adds 6 pure unit tests pinning the area-detection precondition the guard relies on.
EncodeScalarBlock Timer/Counter throws remain as the defensive backstop.
2026-06-17 06:31:41 -04:00
Joseph Doherty 11e8e4302d fix(s7): Counter raw-word note + reject Writable Timer/Counter + Timer time-base tests (bundle review) 2026-06-17 06:18:48 -04:00
Joseph Doherty 8cfb8e920e feat(s7): Timer/Counter read (read-only) + route Timer/Counter through buffer path 2026-06-17 06:03:47 -04:00
Joseph Doherty 5db08e9e85 feat(s7): DateTime (S7 DATE_AND_TIME) scalar read+write via S7.Net.Types.DateTime 2026-06-17 05:54:08 -04:00
Joseph Doherty 1e5fec2f85 feat(s7): String (S7 STRING) scalar read+write via S7.Net.Types.S7String 2026-06-17 05:50:49 -04:00
Joseph Doherty 286be5df88 feat(s7): byte-buffer codec dispatch + Int64/UInt64/LReal scalar read+write 2026-06-17 05:38:18 -04:00
Joseph Doherty 06b858eb02 feat(s7): unblock wide-type/Timer-Counter init guards + fix Int64/UInt64 node mapping 2026-06-17 05:24:48 -04:00
Joseph Doherty 3bbe39c166 fix(s7): treat ArrayCount>=1 as array so 1-element arrays read as arrays (review I-2) 2026-06-16 22:12:30 -04:00
Joseph Doherty a82c22c645 feat(s7): 1-D array block read + decode loop + IsArray discovery 2026-06-16 21:54:50 -04:00
Joseph Doherty 9a8336ff6e feat(probe): S7 Test-Connect does a real ISO-on-TCP + S7 setup handshake
Replace bare TCP-connect with a two-phase probe: Phase 1 keeps the
existing SocketException / timeout / generic preflight paths unchanged;
Phase 2 runs Plc.OpenAsync (COTP CR/CC + S7 setup-communication) so a
device that accepts TCP but is not an S7 PLC reads red instead of green.
A linked CTS distinguishes caller cancellation ("timed out") from the
S7netplus internal read-timeout OCE ("handshake failed: timed out").
2026-06-16 06:38:51 -04:00
Joseph Doherty b031a6ceef feat(s7): resolve equipment-tag refs (read + write) via EquipmentTagRefResolver 2026-06-13 11:25:31 -04:00
Joseph Doherty 57355405a6 chore(security): drop dead audit suppressions; patch OpenTelemetry + Tmds.DBus CVEs
All five suppressed advisories are now resolved at baseline/resolved versions,
so every NuGetAuditSuppress is removed repo-wide:
- System.Security.Cryptography.Xml (GHSA-37gx-xxp4-5rgx / GHSA-w3x6-4m5h-cxqf)
  -> fixed by the .NET 10 baseline (10.0.6)
- OPCFoundation Opc.Ua.Core (GHSA-h958-fxgg-g7w3) -> fixed at resolved 1.5.378.106

Two were still live and are now patched via direct security pins:
- OpenTelemetry.Api 1.9.0 -> 1.15.3 (GHSA-g94r-2vxg-569j) pinned in Cluster;
  Runtime/ControlPlane/AdminUI + tests inherit via project reference
- Tmds.DBus.Protocol 0.20.0 -> 0.21.3 (GHSA-xrw6-gwf8-vvr9) pinned in Client.UI

Also correct the Historian sidecar runtime comments (x86 -> x64, matching the
csproj PlatformTarget). Solution audit: 0 vulnerable packages; full build clean.
2026-06-12 09:03:42 -04:00
Joseph Doherty 9f62f2c242 refactor(driver-s7): extract S7DriverOptions to .Contracts with parallel CpuType enum
Introduces Driver.S7.Contracts (dependency-free POCO project) and moves
S7DriverOptions / S7ProbeOptions / S7TagDefinition / S7DataType into it.
Adds S7CpuType enum mirroring S7.Net.CpuType exactly (7 values with
explicit integer codes). Runtime S7CpuTypeMap bridges S7CpuType →
S7.Net.CpuType at the single Plc construction site in S7Driver.InitializeAsync.
S7DriverFactoryExtensions and S7CommandBase updated to use S7CpuType; test
files updated to match (S7_1500Profile, S7DriverScaffoldTests). AdminUI can
now reference Driver.S7.Contracts without pulling in S7netplus.
2026-05-28 09:08:27 -04:00
Joseph Doherty 64e3fbe035 docs: backfill XML documentation across 756 files
v2-ci / build (push) Failing after 1m43s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (push) Has been skipped
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
2026-05-28 08:10:17 -04:00
Joseph Doherty 2b811477d1 chore(build): introduce central package management for v2
Adds Directory.Packages.props (ManagePackageVersionsCentrally) and
Directory.Build.props (net10.0/nullable/implicit usings/LangVersion latest).
Strips Version attributes from every csproj PackageReference and consolidates
versions into the central file.

Side fixes (necessary to keep the build green on .NET SDK 10.0.105 on macOS):

- Microsoft.CodeAnalysis.CSharp{,.Workspaces}: 5.3.0 -> 5.0.0. The 5.3.0
  analyzer DLL references compiler 5.3.0.0 and the local SDK ships compiler
  5.0.0.0, producing CS9057 on every project that loaded the Analyzers
  output. Master itself was broken on this machine pre-change.
- Server + Server.Tests pin OPCFoundation.NetStandard.Opc.Ua.{Configuration,
  Client} to 1.5.374.126 via VersionOverride, matching Opc.Ua.Server's
  pin. Mixing 1.5.378.106 Opc.Ua.Core transitively with 1.5.374.126
  Opc.Ua.Server breaks CustomNodeManager2 override signatures
  (CS0115 on LoadPredefinedNodes/Browse/HistoryRead*) and CS7069 in
  the tests. The pin disappears when the legacy Server project is
  deleted in Task 56.
- Client.UI + Client.UI.Tests: NuGetAuditSuppress for
  GHSA-xrw6-gwf8-vvr9 (Tmds.DBus.Protocol 0.20.0 reaches both projects
  transitively from Avalonia.Desktop on Linux/macOS only).

Deviation from the plan: TreatWarningsAsErrors=true is NOT set in
Directory.Build.props because the pre-v2 Admin/Server test projects carry
~240 xUnit1051 analyzer warnings that would fail the build. New v2 projects
opt in via their own csproj; the global flag can return once the legacy
projects are deleted in Task 56.
2026-05-26 03:40:24 -04:00
Joseph Doherty af0f09d07e fix(driver-s7): resolve Low code-review findings (Driver.S7-003,005,009,010,013)
- Driver.S7-003: ArgumentNullException.ThrowIfNull on the references
  argument at the top of ReadAsync / WriteAsync (was reaching .Count
  before any null check).
- Driver.S7-005: drop the redundant global::S7.Net.Plc qualifiers in
  ReadOneAsync / WriteOneAsync — using S7.Net already covers Plc.
- Driver.S7-009: PollLoopAsync degrades _health to Degraded after
  sustained failure and backs off exponentially up to PollBackoffCap;
  resets on a healthy tick so an operator can see the loop wedge.
- Driver.S7-010: Dispose runs the synchronous teardown directly with a
  bounded WhenAll Wait drain instead of bridging via DisposeAsync().
- Driver.S7-013: reject unsupported S7DataType values (Int64 / UInt64 /
  Float64 / String / DateTime) at InitializeAsync so half-implemented
  types no longer leak BadNotSupported live nodes into the address space.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-23 07:45:45 -04:00
Joseph Doherty aeb5fc48ae test(driver-s7): resolve Medium code-review finding (Driver.S7-014)
Add S7TypeMappingTests.cs covering ReinterpretRawValue and BoxValueForWrite —
26 tests verifying every implemented type round-trip (Bool/Byte/UInt16/Int16/
UInt32/Int32/Float32), two's-complement reinterpret semantics (ushort→short,
uint→int), unsupported-type NotSupportedException, and overflow edge cases.
These methods were factored out as internal static in the S7-002/S7-008 commit.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-22 10:17:15 -04:00
Joseph Doherty 090d2a4b44 fix(driver-s7): resolve High code-review findings (Driver.S7-001, -006, -007, -011)
Driver.S7-001: Timer (T{n}) / Counter (C{n}) addresses parsed cleanly but
the read path had no S7DataType or decode case for them, so a Timer/Counter
tag passed fail-fast init and then threw a misleading type-mismatch on every
read. InitializeAsync now runs RejectUnsupportedTagAddresses, throwing a clear
NotSupportedException ("not yet supported", echoing tag name + address) so the
config error fails fast at init.

Driver.S7-006: ShutdownAsync cancelled the probe/poll CTSs but did not await
the fire-and-forget loop tasks before DisposeAsync disposed _gate, letting a
loop iteration mid-semaphore race a disposed object. The probe task is now
tracked in _probeTask and each poll task in SubscriptionState.PollTask;
ShutdownAsync cancels every CTS, awaits Task.WhenAll of those handles with a
bounded 5 s DrainTimeout, then disposes the CTSs and gate. Task.Run is passed
CancellationToken.None so the handle is always awaitable.

Driver.S7-007: a PUT/GET-disabled fault (permanent misconfiguration) was
mapped identically to a transient PlcException — both BadDeviceFailure +
Degraded. ReadAsync/WriteAsync now split the catch via an IsAccessDenied
filter (S7.Net exposes no typed code for AccessingObjectNotAllowed, so the
inner-exception chain is inspected for the "not allowed" marker). Access-denied
now maps to BadNotSupported and Faulted with a config-alert message pointing
at the TIA Portal PUT/GET toggle; genuine device faults stay BadDeviceFailure.

Driver.S7-011: S7Driver ignored driverConfigJson on Initialize/Reinitialize,
so a config change delivered through ReinitializeAsync (the only Core-initiated
in-process recovery path) was silently discarded. Config parsing was factored
into S7DriverFactoryExtensions.ParseOptions; InitializeAsync now re-parses
driverConfigJson and rebuilds _options whenever the document has a real body.
An empty / placeholder document keeps the constructor options.

Adds S7DriverCodeReviewFixTests covering Timer/Counter rejection, config-json
application on Initialize/Reinitialize, and shutdown-drain with active
subscriptions. All 68 S7 driver tests pass.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-22 06:41:26 -04:00
Joseph Doherty a25593a9c6 chore: organize solution into module folders (Core/Server/Drivers/Client/Tooling)
Group all 69 projects into category subfolders under src/ and tests/ so the
Rider Solution Explorer mirrors the module structure. Folders: Core, Server,
Drivers (with a nested Driver CLIs subfolder), Client, Tooling.

- Move every project folder on disk with git mv (history preserved as renames).
- Recompute relative paths in 57 .csproj files: cross-category ProjectReferences,
  the lib/ HintPath+None refs in Driver.Historian.Wonderware, and the external
  mxaccessgw refs in Driver.Galaxy and its test project.
- Rebuild ZB.MOM.WW.OtOpcUa.slnx with nested solution folders.
- Re-prefix project paths in functional scripts (e2e, compliance, smoke SQL,
  integration, install).

Build green (0 errors); unit tests pass. Docs left for a separate pass.