Array tags were advertised writable but every write threw InvalidCastException
in ConvertForWrite (reported BadTypeMismatch); STRING writes went through the
Beckhoff marshaller with no length check against STRING(n) and the host's
ANSI code page, which the read side deliberately avoids.
- Array write: TwinCATArrayCodec.ToWriteElements converts exactly ArrayLength
elements to the declared type (CLR lists convert - ScadaBridge writes int[]
to Int16 nodes; a length mismatch or out-of-range element is BadOutOfRange, a
scalar value BadTypeMismatch) before any wire traffic; the ADS client plans
the layout from the resolved PLC array (TwinCATTypeGuard.CheckArray, as the
read does), encodes with TwinCATArrayCodec.Encode - the exact inverse of
Decode - and writes the raw bytes (new ITwinCATClient.WriteArrayAsync).
- STRING / WSTRING write: encoded at the PLC's declared width by
TwinCATStringCodec.EncodeString/EncodeWString (Windows-1252 or UTF-8 per
target, NUL-padded, strict: an over-long value or unrepresentable character
is OverflowException -> BadOutOfRange) and written as raw bytes.
- TwinCAT CLI read/write gain --array-length (+ --separator) for the hardware
gate.
Refs #739
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Port of the ignitionoee TwinCAT string + type-reconciliation fixes onto the
Beckhoff-library client:
- STRING/WSTRING subscriptions never worked: AddDeviceNotificationExAsync was
called with typeof(string) and no length, and the Beckhoff any-type
marshaller throws ArgumentNullException for a string without one, so one
string tag tore down its whole subscribe call. A string now registers the
PLC's own byte width as raw bytes (0.19.2: STRING(n) of any n).
- Strings are read as raw bytes and decoded by TwinCATStringCodec. The
Beckhoff marshaller already cut a read at the first NUL (0.19.3 / TwinCAT-007
were not defects on the read path); the codec keeps that rule for both STRING
and WSTRING and extends it to the new notification path. A STRING now decodes
as Windows-1252 (TwinCAT-010) - or UTF-8 when the target reports UTF-8
strings - instead of the host culture's ANSI code page the Beckhoff
marshaller falls back to (1250 on a Polish host, 1251 Cyrillic, ...).
- TwinCATTypeGuard (TwinCAT-002/-008): a read refuses a numeric tag over a PLC
string (and vice versa / STRING vs WSTRING / string over a container) with
BadTypeMismatch instead of handing back a string object at Good; a
notification - raw bytes decoded as the DECLARED type - additionally refuses
width and float/integer mismatches (DINT over REAL reinterpreted the bits).
- A refused notification is isolated: that tag publishes BadTypeMismatch with
one WARN, keeps a dead intent for the probe-tick retry, and the rest of the
subscription registers.