Joseph Doherty 6ee553cf8f feat(s7): expose ReadMultipleVarsAsync through the IS7Plc seam 2026-08-17 03:48:15 -04:00
Joseph Doherty 88e0977ae6 fix(s7): bound async wire ops with a wall-clock deadline (R2-01 read leg)
v2-ci / build (pull_request) Successful in 5m5s
v2-ci / unit-tests (pull_request) Failing after 13m50s
The R2-01 live gate (S7_1500ConnectTimeoutOutageTests, docker-pause blackhole)
surfaced a real gap the offline fakes couldn't: S7.Net's ReadTimeout/WriteTimeout
map to the TcpClient's ReceiveTimeout/SendTimeout, which govern only SYNCHRONOUS
socket calls — the async read/write paths S7.Net uses ignore them. On an
established-but-frozen peer (frozen PLC / firewall DROP / cable pulled mid-flow,
TCP session still open) a read blocked until the OS TCP stack gave up (minutes),
silently wedging the poll loop: no Bad tick, no reconnect. STAB-14 fixed only the
CONNECT leg (EnsureConnectedAsync CancelAfter); this is its READ-leg sibling.

- New S7OperationDeadline: bounds every data-plane wire op with a wall-clock
  ceiling (= _options.Timeout), surfacing an overrun as TimeoutException. Applied
  in S7PlcAdapter to Read/ReadBytes/Write/WriteBytes/ReadStatus. OpenAsync is left
  to EnsureConnectedAsync's own CancelAfter (not double-bounded).
- IsS7ConnectionFatal now classifies TimeoutException fatal → handle marked dead →
  next EnsureConnectedAsync reopens (connect-timeout fix takes over from there).
- Tests: 5 S7OperationDeadline unit tests (deadline / token-honouring / caller-
  cancel-passthrough / resultless), 1 driver-reaction test (read TimeoutException
  → reopen). Driver.S7.Tests 260/260.
- Live gate S7_1500ConnectTimeoutOutageTests now GREEN against the real snap7 sim
  (8s: baseline Good -> pause blackhole -> Bad tick -> unpause -> recovered Good).
2026-07-15 07:11:42 -04:00
Joseph Doherty 3b5ef439d4 docs(xmldoc): fix genuine doc issues surfaced by /fixdocs (17 fixes)
v2-ci / build (push) Successful in 3m11s
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (push) Failing after 3m51s
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (push) Failing after 1m50s
v2-ci / unit-tests (push) Failing after 8m37s
- CapabilityInvoker: 3 methods that implement IDriverCapabilityInvoker now use
  <inheritdoc /> instead of duplicating the interface docs (MissingInheritDoc).
- TwinCAT NativeRegistration ctor: added the 8 missing <param> tags (MissingParam).
- Stripped the arch-review bookkeeping IDs STAB-1 (IS7Plc, S7Driver) + STAB-2
  (TwinCATDriver x4) from comments, keeping the descriptive text.

Left the other 86 flagged items untouched — they are checker false positives on
legitimate technical content: interface-implemented events / IEqualityComparer /
IDisposable members whose <inheritdoc/> IS correct (10 InheritDocMisused), and domain
terms the heuristic misreads as tracking IDs (IEEE-754, S7-1200/300/400/1500, PLC-5,
D2-260, S7/Melsec memory addresses, OPC UA Part 9, phase-N design-doc filename refs,
UNS level-N descriptions, and prose like 'the #1 bug source' / failover 'pick #3').
2026-07-10 06:23:12 -04:00
Joseph Doherty 25c0c6f68f fix(s7): add lazy reconnect path (archreview STAB-1 / Critical 3)
The S7 Plc was opened once in InitializeAsync and never re-opened: a transient
PLC reboot / network blip permanently killed the driver until redeploy. Introduce
an IS7Plc / IS7PlcFactory seam (mirrors TwinCAT's ITwinCATClientFactory) and a lazy
EnsureConnectedAsync that disposes a dead handle and re-opens a fresh connection on
the next data call. Reads/writes mark the handle dead on a connection-fatal fault
(socket drop / ErrorCode.ConnectionError) but NOT on a data-address error; the probe
loop routes through EnsureConnectedAsync as a backstop.

The seam also closes the S7 TEST-1 gap — the reconnect state machine is now unit-
testable without a live PLC (S7.Net.Plc is sealed with no in-process fake).

Verification:
- 4 deterministic unit guards (fatal→reopen, data-error→no-reopen, raw socket→reopen,
  reopen-fail→degrade-then-recover); full S7 unit suite 234/234 green.
- LIVE end-to-end proof against real python-snap7 (S7_1500ReconnectTests, double-gated
  on sim reachability + S7_RECONNECT_BOUNCE_CMD): bounced the container, driver observed
  the outage and resumed Good reads with NO redeploy. Baseline smoke 3/3 still green.
2026-07-08 17:04:46 -04:00