6dda0549e2083e9b9c5501bab3d7f2f49ec64786
9 Commits
| Author | SHA1 | Message | Date | |
|---|---|---|---|---|
|
|
db751d12a5 |
feat(alarms): condition Quality tracks source connectivity (#477)
Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good so every native + scripted condition reported Good unconditionally — a comms-lost device still showed a healthy, inactive, Good condition (a wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs bucketing on IsGood) could not tell "genuinely inactive" from "lost contact". Layer 1 — make Quality a real, plumbed field: - AlarmConditionSnapshot gains OpcUaQuality Quality (default Good). - MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good). - WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality member so a quality-bucket change fires a Part 9 event. Layer 2 — drive native quality from driver connectivity (a comms-lost driver emits no alarm transitions, and an alarm-bearing raw tag has no value variable, so quality can't come from either existing channel): - DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting. - DriverHostActor fans it to every native condition the driver owns as OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect). - New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and fires only on a bucket change — never touches Active/Acked/Retain (an active alarm that loses comms stays active). Not a full-snapshot re-projection, so it can't clobber severity/message and works for a never-fired condition. Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the reflection forwarding guard). Ungated by redundancy role; no /alerts row. Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3). Tests: node-level (materialise/project/no-clobber/unknown-node no-op), NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor fan-out, OpcUaPublishActor routing, and the wire-level guard (Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified against a simulated pre-fix always-Good server. Existing DriverInstanceActor parent probes ignore the new ConnectivityChanged. Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)"; design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md. |
||
|
|
8ebc712eff |
feat(v3-batch4-wp4): multi-notifier native alarms (single ReportEvent → raw + equipment notifiers) + teardown symmetry
Materialize each native alarm ONCE at the raw tag (ConditionId = RawPath, Raw realm); wire the single condition as an SDK event notifier of each referencing equipment's UNS folder so one ReportEvent fans to every root without re-reporting per root (which would break Server-object dedup + Part 9 ack correlation). - New sink method WireAlarmNotifiers(alarmNodeId, alarmRealm, notifierFolderNodeIds, notifierFolderRealm) on IOpcUaAddressSpaceSink, forwarded through DeferredAddressSpaceSink + SdkAddressSpaceSink + NullOpcUaAddressSpaceSink (the forwarding-trap guard); auto-covered by the DeferredSinkForwardingReflectionTests realm + forwarding guards + a hand-written forward test. - OtOpcUaNodeManager: the normative AddNotifier(isInverse) pair + idempotent EnsureFolderIsEventNotifier per equipment folder; tracked per condition in _alarmNotifierWiring. Teardown symmetry: RemoveNotifier(bidirectional:true) on RebuildAddressSpace, RemoveAlarmConditionNode, and RemoveEquipmentSubtree so no inverse-notifier entry leaks across redeploys. - AddressSpaceApplier.MaterialiseRawSubtree wires notifiers for each native alarm tag, resolving its ReferencingEquipmentPaths (Area/Line/Equipment) to the EquipmentId folder NodeIds via BuildEquipmentIdByFolderPath. - AlarmTransitionEvent gains ReferencingEquipmentPaths (empty default); /alerts renders the referencing-equipment list as display metadata. - Un-skipped + rewrote the native-alarm dark tests (DriverHostActorNativeAlarmTests x6, DriverHostActorNativeAlarmAckRoutingTests x1) for the v3 raw-condition model; new NodeManagerMultiNotifierAlarmTests proves multi-notifier wiring + teardown symmetry (no leaked duplicates after a re-trip) + applier wiring test. Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox |
||
|
|
3efcf8014b |
feat(v3-batch4-wp3): raw-only binding + UNS fan-out + write routing
Wave B of Batch 4 — the runtime binding seam for the dual namespace. Applier (both realms, explicit realm at every sink call site): - MaterialiseRawSubtree: Raw containers as folders + Raw tags as variables keyed by RawPath (native-alarm tag → single Part 9 condition at the RawPath), all in AddressSpaceRealm.Raw; historian tagname = override else RawPath. - MaterialiseUnsReferences: each UNS reference Variable under its equipment folder (Uns realm) + an Organizes UNS->Raw edge; inherits writable/array/ historian tagname from the backing raw tag (both NodeIds -> one tagname). - FeedHistorizedRefs / ProvisionHistorizedTags now source RAW tags (mux ref stays single, keyed by RawPath); ApplyPureRemove tears down raw tags + UNS refs in place (raw-container removal falls back to rebuild). DriverHostActor (dual-NodeId, single-source fan-out): - _nodeIdByDriverRef value gains a realm (NodeRealmRef); rebuilt from RawTags UNION UnsReferenceVariables so one (DriverInstanceId, RawPath) fans to the raw NodeId AND every referencing UNS NodeId with identical value/quality/timestamp. Write inverse map keyed by the bare id; the ns-qualified NodeId the write hook passes is normalised (BareNodeId) so a write to either NodeId resolves the same driver ref (-> RawPath write). - Native raw alarm condition routing is realm-tagged (Raw); AttributeValueUpdate + AlarmStateUpdate carry the realm through to the sink. Retire EquipmentNodeIds -> V3NodeIds.Uns (applier/VirtualTagHostActor) and RawPaths.Combine (DiscoveredNodeMapper, discovered nodes are Raw now). DeploymentArtifact.ParseComposition emits the Raw + UNS subtrees byte-parity with the composer (reconstruct entities -> AddressSpaceComposer.Compose). Sink surface: removed the transitional `= AddressSpaceRealm.Uns` defaults from IOpcUaAddressSpaceSink / ISurgicalAddressSpaceSink / SdkAddressSpaceSink / DeferredAddressSpaceSink / NullOpcUaAddressSpaceSink — every call site is now explicit (realm reordered before the trailing optionals on EnsureVariable + MaterialiseAlarmCondition). Node-manager convenience methods keep their defaults (they are not the interface impl; Sdk delegates explicitly). Tests: rewrote DriverHostActorLiveValueTests (fan-out drift, 1:N) + DriverHostActorWriteRoutingTests (dual-NodeId raw/uns write routing) to the v3 raw+uns model; new AddressSpaceApplierRawUnsTests; migrated the EquipmentTags provisioning/feed tests to RawTags; swept EquipmentNodeIds test callers. Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox |
||
|
|
e95615cef3 |
fix(v3-batch4-wp2): AddReference sink seam for Organizes UNS→Raw (Wave A review M1)
Close the Wave-A M1 gap: the sink surface had no way to wire the mandated cross-tree Organizes reference from each UNS reference Variable to its backing Raw node, forcing WP3 to reopen the frozen surface. Add a dedicated realm-qualified AddReference method instead. - IOpcUaAddressSpaceSink.AddReference(sourceNodeId, sourceRealm, targetNodeId, targetRealm, referenceType="Organizes"): realm-qualified both ends; idempotent; a missing endpoint is a logged no-op (never throws) so a mid-rebuild race can't fault a deploy. Base-interface capability (no surgical sniff, no transitional default — WP3 wires it explicitly per UNS reference variable). - SdkAddressSpaceSink forwards to the node manager; DeferredAddressSpaceSink forwards unconditionally (like EnsureFolder); NullOpcUaAddressSpaceSink no-ops. - OtOpcUaNodeManager.AddReference: resolve both nodes by full ns-qualified key (variable/folder/condition via ResolveNodeState), guard both-exist, then wire the edge bidirectionally (forward Organizes on source, inverse on target) with a ReferenceExists idempotency guard + ClearChangeMasks on mutated sides. Reference type resolved by ResolveReferenceType (Organizes default). Added internal GetNodeReferences test/diagnostic accessor. - Reflection guard: the exhaustive-forwarding test + the realm-discriminator guard auto-cover AddReference (it has two AddressSpaceRealm params) — no edit needed. - New SdkAddressSpaceSinkTests: Organizes UNS→Raw edge created bidirectionally + idempotent; missing endpoint is a safe no-op. - All 15 IOpcUaAddressSpaceSink test doubles gain the AddReference no-op so the solution still builds. Build: dotnet build ZB.MOM.WW.OtOpcUa.slnx = 0 errors. Tests: Commons.Tests 310/310; OpcUaServer.Tests 337 passed / 4 pre-existing skips. Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox |
||
|
|
5534698d70 |
feat(v3-batch4-wp2): node manager dual-namespace + realm-aware sink surface
Register both v3 namespaces (Raw first, UNS second) on OtOpcUaNodeManager and thread an AddressSpaceRealm discriminator through every node-naming sink method so a bare node id is resolved to the correct namespace by realm — never parsed out of the id string. - IOpcUaAddressSpaceSink / ISurgicalAddressSpaceSink: every node-naming method gains `AddressSpaceRealm realm = AddressSpaceRealm.Uns` (transitional default so un-migrated WP3 call sites still compile; WP3/Wave B makes them explicit and removes the default). Null + SdkAddressSpaceSink impls updated; DeferredAddress- SpaceSink forwards realm through every method (the forwarding trap). - DeferredSinkForwardingReflectionTests: existing exhaustive-forwarding guard auto-covers the new signatures; added an explicit guard that every node-naming sink method carries an AddressSpaceRealm parameter (RebuildAddressSpace exempt). - OtOpcUaNodeManager: register RawNamespaceUri + UnsNamespaceUri; realm->namespace index via NamespaceIndexForRealm; all node maps (_variables/_folders/ _alarmConditions/_nativeAlarmNodeIds/_historizedTagnames/_eventNotifierSources) re-keyed by the full ns-qualified NodeId string so Raw and UNS nodes sharing a bare id stay distinct; _notifierFolders already NodeId-keyed. A historized UNS reference node registers the SAME historian tagname as its backing raw node (both NodeIds -> one tagname). Inbound-write hook routes the full ns-qualified NodeId to the write gateway (realm-aware) and reverts by bare id + realm. HistoryRead seams resolve via NodeId directly. DefaultNamespaceUri kept as a transitional alias to UnsNamespaceUri for the SubscriptionSurvivalTests. - Test doubles across Commons.Tests / OpcUaServer.Tests / Runtime.Tests updated to the new interface signatures; SdkAddressSpaceSinkTests asserts the UNS namespace index for default-realm nodes. Build: dotnet build ZB.MOM.WW.OtOpcUa.slnx = 0 errors. Tests: Commons.Tests 310/310; OpcUaServer.Tests 335 passed / 4 pre-existing skips. Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox |
||
|
|
2c7fc65bae |
test(v3): migrate OpcUaServer.Tests + Host.IntegrationTests to v3 dark address space
Migrate the server composer/applier + 2-node harness tests off the retired
Namespace/NamespaceKind + equipment→driver/device binding schema onto the v3
greenfield shape (raw-only Tag; DriverInstance-RawFolderId; equipment via UnsLine).
OpcUaServer.Tests (134 build errors -> green, 335 pass / 4 skip):
- LIVE (migrated, passing): VirtualTag-historize + ScriptedAlarm composition,
composer purity/hierarchy, applier MaterialiseHierarchy + MaterialiseEquipmentTags
idempotency (hand-fed applier, not dark).
- SKIP dark-until-Batch-4: {{equip}} token expansion, applier equipment-namespace
E2E (equipment-tag variable materialization).
- RETIRE-with-comment / skip: alias-tag (Tag.EquipmentId binding gone) + device-host
equipment binding (architecturally removed).
- Add local DarkAddressSpaceReasons Skip-reason constants (mirrors Runtime.Tests).
Host.IntegrationTests (green, in-memory): drop deleted-Namespace seeds from
MultiClusterScoping + DriverReconnect; reshape EquipmentNamespaceMaterialization to
assert the DARK contract (folder nodes decode, EquipmentTags empty despite a seeded
v3 raw tag) with the full raw-tag->EquipmentTag materialization kept as a
Batch-4-pending Skip.
Tests-only; no src/ changes.
|
||
|
|
598cdfad5a | feat(otopcua): applier pass to materialise discovered nodes idempotently | ||
|
|
23b42b424d |
fix(code-review): resolve OpcUaServer-001 — UNS Area/Line rename refreshes folder DisplayName
A rename-only deploy produced an IsEmpty plan that short-circuited before MaterialiseHierarchy, leaving the OPC UA folder DisplayName stale. AddressSpacePlanner now diffs UnsAreas/UnsLines by stable id into a RenamedFolders set (counted in IsEmpty); the applier refreshes the folder in place via a new UpdateFolderDisplayName on ISurgicalAddressSpaceSink (forwarded through DeferredAddressSpaceSink so it is NOT inert on driver hosts; falls back to rebuild when the sink is non-surgical). DeploymentArtifact byte-parity untouched (rename rides the existing Name round-trip). No EF migration, no serialized wire/proto contract change. +13 OpcUaServer tests, Runtime rebuild test. |
||
|
|
40e8a23e7c |
refactor(opcuaserver): rename Phase7* address-space pipeline to AddressSpace*
v2-ci / build (push) Failing after 37s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (push) Has been skipped
The OPC UA address-space build pipeline was named after a v2-roadmap milestone number rather than its domain. Rename the family to describe what it does (build/diff/apply the OPC UA address space): Phase7Composer -> AddressSpaceComposer Phase7CompositionResult -> AddressSpaceComposition Phase7Planner -> AddressSpacePlanner Phase7Plan -> AddressSpacePlan Phase7Applier -> AddressSpaceApplier Phase7ApplyOutcome -> AddressSpaceApplyOutcome The 9 Phase7*Tests suites follow suit; Phase7ScriptingEntitiesTests -> ScriptingEntitiesTests (it tests the scripting migration, not the pipeline). Log-message prefixes move to the new class names. Pure mechanical rename, no behavioral change. EF migration classes/IDs (AddPhase7ScriptingTables, ExtendComputeGenerationDiffWithPhase7) are immutable and left untouched, as are historical design docs. Build clean; OpcUaServer 261/261, Runtime 272/272, ScriptingEntities 12/12 green. |