Commit Graph

2 Commits

Author SHA1 Message Date
Joseph Doherty
5ea57d2d70 Task #138 — Modbus addressing grammar docs + e2e
Closes the docs/e2e end of the Modbus addressing line shipped across
#136-#145.

Docs:

- docs/v2/modbus-addressing.md (new) — full grammar reference.
  Region+offset (Modicon 5-digit / 6-digit / mnemonic), bit suffix,
  type codes (BOOL / I / UI / DI / UDI / LI / ULI / F / D / BCD / LBCD /
  STR<n>), all four byte-order mnemonics (ABCD / CDAB / BADC / DCBA),
  array-count semantics, family-native syntax (DL205 V/Y/C/X/SP and
  MELSEC D/M/X/Y with hex-vs-octal sub-family selection), driver-instance
  options (KeepAlive / Reconnect / IdleDisconnect, MaxCoilsPerRead and
  FC15/16 forcing, Deadband + WriteOnChangeOnly, MaxReadGap +
  CoalesceProhibited, multi-unit IPerCallHostResolver). Includes a worked
  JSON DTO example mixing AddressString + structured tag forms.

- docs/Driver.Modbus.Cli.md — appended a "v2 addressing grammar" section
  pointing users at the full reference, with quick-reference examples.

- Vendor-compatibility caveat documented: type codes and byte-order
  mnemonics were synthesised from training-era vendor docs (Wonderware
  DASMBTCP, Kepware KEPServerEX, Ignition, Matrikon, OAS) and should be
  verified against current vendor manuals before locking for production.

E2E tests (4 new AddressingGrammarTests in IntegrationTests):
- Modicon 5-digit and 6-digit forms map to identical wire offsets.
- Float32 + WordSwap (CDAB) round-trips end-to-end through the
  pymodbus simulator.
- Int16[5] array round-trips as a typed short[] surface.
- Block-read coalescing produces a wire-acceptable PDU when MaxReadGap=5
  bridges three nearby tags.

All tests skip gracefully when the pymodbus simulator at localhost:5020
is unreachable (matches the existing ModbusSimulatorFixture pattern).

Final test count across the Modbus addressing surface:
- 107 ModbusAddressing.Tests (parser + family + Modicon)
- 231 Driver.Modbus.Tests (driver, byte order, array, multi-unit, coalescing,
  protocol, subscribe, connection options)
- 110 Admin.Tests (incl. ModbusOptionsViewModel defaults pinning)
- 4 new AddressingGrammar integration tests (skip when sim down)
2026-04-25 00:32:27 -04:00
Joseph Doherty
5dac2e9375 Task #249 — Driver test-client CLIs: shared lib + Modbus CLI first
Mirrors the v1 otopcua-cli value prop (ad-hoc shell-level PLC validation) for
the Modbus-TCP driver, and lays down the shared scaffolding that AB CIP, AB
Legacy, S7, and TwinCAT CLIs will build on.

New projects:
  - src/ZB.MOM.WW.OtOpcUa.Driver.Cli.Common/ — DriverCommandBase (verbose
    flag + Serilog config) + SnapshotFormatter (single-tag + table +
    write-result renders with invariant-culture value formatting + OPC UA
    status-code shortnames + UTC-normalised timestamps).
  - src/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Cli/ — otopcua-modbus-cli executable.
    Commands: probe, read, write, subscribe. ModbusCommandBase carries the
    host/port/unit-id flags + builds ModbusDriverOptions with Probe.Enabled
    =false (CLI runs are one-shot; driver-internal keep-alive would race).

Commands + coverage:
  - probe              single FC03 + GetHealth() + pretty-print
  - read               region × address × type synth into one driver tag
  - write              same shape + --value parsed per --type
  - subscribe          polled-subscription stream until Ctrl+C

Tests (38 total):
  - 16 SnapshotFormatterTests covering: status-code shortnames, unknown
    codes fall back to hex, null value + timestamp placeholders, bool
    lowercase, float invariant culture, string quoting, write-result shape,
    aligned table columns, mismatched-length rejection, UTC normalisation.
  - 22 Modbus CLI tests:
      · ReadCommandTests.SynthesiseTagName (5 theory cases)
      · WriteCommandParseValueTests (17 cases: bool aliases, unknown rejected,
        Int16 bounds, UInt16/Bcd16 type, Float32/64 invariant culture,
        String passthrough, BitInRegister, Int32 MinValue, non-numeric reject)

Wiring:
  - ZB.MOM.WW.OtOpcUa.slnx grew 4 entries (2 src + 2 tests).
  - docs/Driver.Modbus.Cli.md — operator-facing runbook with examples per
    command + output format + typical workflows.

Regression: full-solution build clean; shared-lib tests 16/0, Modbus CLI tests
22/0.

Next up: repeat the pattern for AB CIP (shares ~40% more with Modbus via
libplctag), then AB Legacy, S7, TwinCAT. The shared base stays as-is unless
one of those exposes a gap the Modbus-first pass missed.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>