AdminUI driver-instance pages serialized enum config fields (S7 CpuType,
Modbus DataType/Region, AbCip PlcFamily, ...) as JSON *numbers* because each
page's _jsonOpts lacked a JsonStringEnumConverter. The driver factories,
however, deserialize into string-typed DTOs (+ lenient ParseEnum) and throw
when binding a JSON number to a string? — so an AdminUI-authored config
containing any enum field produced a blob the driver could not parse,
faulting the driver on deploy. Proven end-to-end for S7 and Modbus; latent
for AbCip/AbLegacy/TwinCAT/FOCAS/Galaxy/Historian. Only OpcUaClient was safe
(its factory + probe already carried the converter).
Add JsonStringEnumConverter to all 9 driver-instance pages' _jsonOpts and the
8 missing driver probes' _opts (factories unchanged — already string-via-
ParseEnum; strictly more permissive, also lets pages load hand-seeded
string-enum configs back into the form).
Also fix DriverProbeHandshakeE2eTests.AbCip_Green_AgainstSim to probe a real
sim tag (TestDINT) — the no-tags @raw_cpu_type fallback is rejected by the
ab_server sim with ErrorBadParam (a real ControlLogix returns ErrorNotFound,
which the probe treats as reachable; hardware-gated follow-up).
Tests: reflection guard over all driver pages' _jsonOpts (AdminUI.Tests);
factory round-trip + numeric-form-throws guards for S7 and Modbus.
Found by running the never-before-run FB-9/FB-10 live verifies.
Replace bare TCP-connect with a two-phase probe: Phase 1 keeps the
existing SocketException / timeout / generic preflight paths unchanged;
Phase 2 runs Plc.OpenAsync (COTP CR/CC + S7 setup-communication) so a
device that accepts TCP but is not an S7 PLC reads red instead of green.
A linked CTS distinguishes caller cancellation ("timed out") from the
S7netplus internal read-timeout OCE ("handshake failed: timed out").
Cheap-and-fast probe: open TCP socket to the configured endpoint,
close immediately. Surfaces SocketError on failure, latency on
success, "timed out" on caller cancel. Sufficient for the AdminUI
Test Connect "can we reach the host?" question. Richer protocol-
level probes (OPC UA session open, FOCAS handshake, gRPC ping)
are a documented follow-up. Each probe registered as
AddSingleton<IDriverProbe, X> in DriverFactoryBootstrap so they
flow through DI into AdminOperationsActor.
Historian.Wonderware returns a clean "TCP probe not applicable"
result because it communicates over a Windows named pipe, not TCP.
Also adds OpcUaClient + Historian.Wonderware.Client project
references to Host.csproj (both were missing from the driver
ItemGroup).