Driver.Cli.Common-007 + Driver.Cli.Common-008 resolution.
Driver.Cli.Common-007 (High, Correctness):
0x80550000 is the canonical OPC UA spec value for BadSecurityPolicyRejected,
not BadDeviceFailure. The correct spec value for BadDeviceFailure is
0x808B0000 (verified against OPC Foundation Opc.Ua.StatusCodes;
corroborated locally by Driver.Galaxy.Runtime.StatusCodeMap and both
Wonderware historian quality mappers which all hand-pin the correct
value).
The bug was duplicated across six driver modules:
- FocasStatusMapper.BadDeviceFailure
- AbCipStatusMapper.BadDeviceFailure
- AbLegacyStatusMapper.BadDeviceFailure
- TwinCATStatusMapper.BadDeviceFailure
- ModbusDriver.StatusBadDeviceFailure
- S7Driver.StatusBadDeviceFailure
Plus the SnapshotFormatter shortlist that named 0x80550000 as
BadDeviceFailure, and three downstream Modbus tests that asserted
against the wrong value (so CI was blind).
This commit fixes all six native-mapper constants, the formatter
shortlist, and the three Modbus tests in one pass. Added a regression
guard to FormatStatus_does_not_apply_pre_fix_wrong_names that pins
0x80550000 never renders as BadDeviceFailure (mirroring the existing
-001 wrong-name guards).
Behavior change: OPC UA clients consuming the native drivers now see
the canonical BadDeviceFailure (0x808B0000) on device-fault paths
instead of the misnamed BadSecurityPolicyRejected (0x80550000). Wire-
level status semantics now match operator-facing CLI labels.
Driver.Cli.Common-008 (Low, Testing):
Deleted the redundant FormatStatus_names_native_driver_emitted_codes
Theory — its five InlineData rows were already covered by the
well-known Theory in the same commit (5a9c459), and used a weaker
ShouldContain vs the well-known Theory's ShouldBe (exact match).
Verification:
- Driver.Cli.Common.Tests: 43/43 pass (was 48 after the -008 deletion).
- Driver.Modbus.Tests: 263/263 pass.
- Driver.AbCip.Tests: 262/262.
- Driver.AbLegacy.Tests: 157/157.
- Driver.FOCAS.Tests: 178/178.
- Driver.S7.Tests: 112/112.
- Driver.TwinCAT.Tests: 131/131.
Total: 1146 tests across the affected modules, all green.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
The sibling mxaccessgw repo restructured: clients/dotnet/MxGateway.Client
no longer exists, and the proto contracts moved to a new namespace
(ZB.MOM.WW.MxGateway.Contracts.Proto, was MxGateway.Contracts.Proto). The
driver's source still expects the pre-restructure namespace, so the
broken ProjectReference produced 86 build errors in src/ + 1 in tests/
on master.
Resolution: vendor the last known-good build of MxGateway.Client.dll
(99 KB, May 22) and MxGateway.Contracts.dll (490 KB, May 23) under
src/Drivers/.../Driver.Galaxy/libs/, reference them via <Reference
HintPath=...> in both the driver and its test csproj, and declare the
NuGet packages the dropped ProjectReference was supplying transitively
(Google.Protobuf, Grpc.Core.Api, Grpc.Net.Client,
Microsoft.Extensions.Logging.Abstractions, Polly) at versions matching
the sibling repo's ZB.MOM.WW.MxGateway.Contracts.csproj so binary
compatibility is preserved.
Why this over a source migration:
Source migration would require namespace renames across ~19 driver
files PLUS reimplementing MxGatewayClient / MxGatewaySession /
GalaxyRepositoryClient (~2,200 LoC) — the sibling repo dropped the
client library entirely, keeping only the proto contracts. Vendoring
the last known-good binaries unblocks the build in minutes, freezes
the gateway contract surface at a known-good version, and preserves
the option to migrate properly once the sibling repo decides whether
to restore a client library or hand the work back to us.
libs/README.md documents the unwinding plan (either path closes the
debt: sibling restores a client library, or driver migrates to the new
contracts namespace + reimplements the client wrapper).
Verification:
- dotnet build ZB.MOM.WW.OtOpcUa.slnx: 0 errors (was 87).
- Driver.Galaxy unit tests: 245/245 pass.
- Integration tests not run here (require a live mxaccessgw gateway).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Driver.FOCAS.Cli-005 follow-up: extend the SnapshotFormatter.FormatStatus
shortlist with the five Bad* codes the native-protocol mappers (FOCAS,
AbCip, AbLegacy) emit but which the shortlist previously left unnamed,
so they rendered only as severity-class 'Bad' instead of the documented
'BadDeviceFailure' / 'BadNotWritable' / ... names operators are told to
read off probe/write output.
Added entries:
0x80020000 BadInternalError
0x803B0000 BadNotWritable
0x803C0000 BadOutOfRange
0x803D0000 BadNotSupported
0x80550000 BadDeviceFailure
(BadTimeout 0x800A0000 was already added under Driver.Cli.Common-001.)
Tests: SnapshotFormatterTests gains a new [Theory]
FormatStatus_names_native_driver_emitted_codes covering the five names,
and the existing well-known [Theory] is extended with the same entries
to enforce exact '0x... (Name)' rendering. Suite now 47 green (was 42).
Flips Driver.FOCAS.Cli-005 from Deferred to Resolved; README regenerated.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.Historian.Wonderware.Client-003: replaced the mixed Interlocked
+ healthLock counters with RecordOutcome that touches _totalQueries
and exactly one of _totalSuccesses / _totalFailures under one
acquisition.
- Driver.Historian.Wonderware.Client-004: InvokeAndClassifyAsync routes
transport + sidecar classification through a single RecordOutcome
call; the legacy ReclassifySuccessAsFailure two-step is gone.
- Driver.Historian.Wonderware.Client-006: removed the dead
ReconnectInitialBackoff / ReconnectMaxBackoff options and added a
doc <remarks> stating the channel performs a single in-place
reconnect; retry/backoff stays with the caller.
- Driver.Historian.Wonderware.Client-008: the audit-suppression comment
block now records advisory titles, why neither applies, and the
revisit trigger.
- Driver.Historian.Wonderware.Client-010: reworded Dispose() to claim
deadlock-safety and added a GetHealthSnapshot summary documenting the
single-channel collapse + counter invariant.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.Cli.Common-004: confirm the FormatTable empty-input guard
landed earlier (commit 1433a1c); flip status to Resolved with a
cross-reference.
- Driver.Cli.Common-006: reword the SnapshotFormatter source-time
column comment to describe the actual behaviour (right-most column,
unmeasured, '-' for null timestamps) and confirm the
DriverCommandBase summary now enumerates FOCAS.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.FOCAS.Cli-001: WriteCommand.ParseValue now wraps numeric
FormatException / OverflowException as CliFx CommandException with
the offending value.
- Driver.FOCAS.Cli-002: SubscribeCommand's OnDataChange handler and the
banner both take a writeLock so notification-callback and main-thread
writes can't interleave; handler exceptions are warn-and-swallow.
- Driver.FOCAS.Cli-003: FocasCommandBase.ValidateOptions rejects
--cnc-port outside 1..65535, non-positive --timeout-ms, and
non-positive --interval-ms; ExecuteAsync calls it first.
- Driver.FOCAS.Cli-004: 'await using var driver' is the sole driver
disposal path; dropped the redundant explicit await ShutdownAsync.
- Driver.FOCAS.Cli-005 (Deferred): the fix lives in
Driver.Cli.Common.SnapshotFormatter — explicitly naming the
status-code shortlist there benefits every driver CLI. Left as a
Driver.Cli.Common follow-up.
- Registered the new tests/Drivers/Cli/ZB.MOM.WW.OtOpcUa.Driver.FOCAS.Cli.Tests
project in ZB.MOM.WW.OtOpcUa.slnx.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.Modbus.Cli-003: ModbusCommandBase.ValidateEndpoint rejects
--port outside 1..65535, non-positive --timeout-ms, and --unit-id
outside 1..247.
- Driver.Modbus.Cli-004: wrapped SubscribeCommand's OnDataChange handler
body in a try/catch (warn-and-swallow) and serialised the console
write through a lock.
- Driver.Modbus.Cli-005: Probe / Read / Write now catch the
cancellation-during-init OperationCanceledException and print
'Cancelled.' instead of dumping a stack trace.
- Driver.Modbus.Cli-006: ProbeCommand.ComputeVerdict derives the headline
from BOTH the driver state and the probe snapshot's OPC UA quality
class so the headline can't disagree with the wire result.
- Driver.Modbus.Cli-007: docs/Driver.Modbus.Cli.md carries an explicit
'CLI scope' callout — the address-string grammar is a DriverConfig
JSON feature; the CLI takes the structured triple only.
- Driver.Modbus.Cli-008: pinned BuildOptions, ValidateEndpoint, the
region-validation guards, ComputeVerdict, and the cancellation-during-
initialize paths.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.TwinCAT.Cli-001: TwinCATCommandBase.Validate rejects
non-positive TimeoutMs / IntervalMs and AmsPort outside 1..65535;
ExecuteAsync calls it first.
- Driver.TwinCAT.Cli-002: SubscribeCommand serialises every WriteLine
through a writeLock to remove the notification-callback vs banner
interleave risk.
- Driver.TwinCAT.Cli-003: SubscribeCommand.DescribeMechanism derives
the banner label from the returned ISubscriptionHandle.DiagnosticId
so it can't disagree with what the driver actually did.
- Driver.TwinCAT.Cli-004: introduced TwinCATTagCommandBase carrying
--poll-only + BuildOptions; BrowseCommand stays on the slimmer
TwinCATCommandBase so --poll-only no longer surfaces in browse --help.
- Driver.TwinCAT.Cli-005: ProbeCommand --type now carries the 't' short
alias to match the other commands.
- Driver.TwinCAT.Cli-006: 35 new tests covering Gateway / AmsAddress
parse / BuildOptions / PollOnly / browse-helpers / probe-alias /
mechanism derivation.
- Driver.TwinCAT.Cli-007: replaced the empty-init <inheritdoc/> with an
explicit summary warning future maintainers about the no-op init.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.S7.Cli-004: 'await using var driver' is the sole driver
disposal path; dropped the redundant explicit await ShutdownAsync from
each command's finally.
- Driver.S7.Cli-005: deleted the stale empty
tests/ZB.MOM.WW.OtOpcUa.Driver.S7.Cli.Tests/ directory (the real test
project lives under tests/Drivers/Cli/).
- Driver.S7.Cli-006: S7CommandBaseBuildOptionsTests cover the probe
toggle, timeout mapping, host/port/CPU/rack/slot wiring, and tag list
passthrough.
- Driver.S7.Cli-007: re-added the SubscribeCommand handler comment
explaining the CliFx IConsole.Output usage and that the poll-thread
raises events.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.AbLegacy.Cli-002: WriteCommand.Value description lists the full
true/false, 1/0, on/off, yes/no alias set.
- Driver.AbLegacy.Cli-003: SubscribeCommand serialises every WriteLine
via a per-execution consoleGate lock so the poll-thread OnDataChange
handler can't interleave with the banner.
- Driver.AbLegacy.Cli-004: dropped 'await using var driver' in favour of
a plain 'var driver' + explicit await ShutdownAsync in finally; the
driver is no longer shut down twice.
- Driver.AbLegacy.Cli-005: SubscribeCommand.IntervalMs description
carries the PollGroupEngine 250ms-floor caveat; docs/Driver.AbLegacy.Cli.md
spells out the same.
- Driver.AbLegacy.Cli-006: ProbeCommand --type now carries the short
alias 't' to match the other commands.
- Driver.AbLegacy.Cli-007: BuildOptionsTests cover the probe-disabled,
device-shape, tag-passthrough, timeout-propagation, and empty-tag-list
paths.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.AbCip.Cli-003: SubscribeCommand prints the 'Subscribed' banner
BEFORE wiring OnDataChange so the main thread can't interleave its
write with the poll-thread handler.
- Driver.AbCip.Cli-004: AbCipCommandBase.Timeout and SubscribeCommand
validate TimeoutMs / IntervalMs and throw CommandException on
non-positive values.
- Driver.AbCip.Cli-005: every command now calls FlushLogging() in its
finally block.
- Driver.AbCip.Cli-006: Timeout init throws NotSupportedException with a
pointer at TimeoutMs instead of silently swallowing assignments.
- Driver.AbCip.Cli-007: added AbCipCommandBaseTests covering BuildOptions
shape, probe / controller-browse / alarm toggles, host address, family
selection, tag list passthrough.
- Driver.AbCip.Cli-008: rewrote the opening paragraph in
docs/Driver.AbCip.Cli.md to credit the six-CLI roster with a pointer
at docs/DriverClis.md.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.Modbus.Addressing-006: broaden the catch in TryParseFamilyNative
so a future helper throwing a non-Argument/Overflow type still satisfies
the try-parse contract.
- Driver.Modbus.Addressing-007: document that the address grammar does
not carry ModbusStringByteOrder (the structured-tag path does);
add a 'Grammar scope' bullet to docs/v2/dl205.md.
- Driver.Modbus.Addressing-009: reword the ModbusModiconAddress comments
so they don't imply a leading-digit invariant the parser doesn't
enforce.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.Historian.Wonderware-004: ToHistorianEvent synthesises a fresh
Guid when the upstream EventId is unparseable and logs the substitution
instead of writing the historian with Guid.Empty.
- Driver.Historian.Wonderware-005: GetHealthSnapshot derives the
connection-open booleans from the active-node fields so the snapshot
is self-consistent without depending on the secondary lock.
- Driver.Historian.Wonderware-007: SID-mismatch branch in PipeServer now
sends a HelloAck { Accepted=false, RejectReason } so the client sees a
symmetric rejection.
- Driver.Historian.Wonderware-008: classify StartQuery failures —
connection-class codes drop the connection, query-class codes throw
QueryClassStartQueryException so the IPC layer surfaces Success=false.
- Driver.Historian.Wonderware-010: RequestTimeoutSeconds now enforced
via BuildRequestCts linked to the caller's CancellationToken.
- Driver.Historian.Wonderware-011: refreshed XML docs to describe the
current sidecar / named-pipe architecture (Galaxy.Host / Proxy
references reframed as historical context).
- Driver.Historian.Wonderware-012: pinned the previously-uncovered
HistorianDataSource behaviours with five new test files; also removed
the stale empty tests/ZB.MOM.WW.OtOpcUa.Driver.Historian.Wonderware.Tests
directory.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.OpcUaClient-011: rewrote the ValueRank comment with the OPC UA
Part 3 constants and an explicit scalar/array boundary at
valueRank >= 0.
- Driver.OpcUaClient-014: track every MonitoredItem.Notification handler
in a MonitoredItemNotificationHandle record; UnsubscribeAsync /
UnsubscribeAlarmsAsync / ShutdownAsync detach the handler before
Subscription.DeleteAsync so the SDK's invocation list no longer keeps
the driver alive.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.Modbus-003: route every _health access through ReadHealth /
WriteHealth helpers backed by Volatile.Read / Volatile.Write so a
burst of concurrent ReadAsync callers always sees a complete snapshot.
- Driver.Modbus-007: promoted the Int64 / UInt64 → Int32 surfacing
caveat to a full <remarks> block; rewrote DisableFC23's doc to flag it
as reserved / no-op.
- Driver.Modbus-008: deleted stale duplicate doc, rewrote the
prohibition-block summaries to credit the shipped re-probe loop, and
removed the unused 'status' local in the ModbusException catch arm.
- Driver.Modbus-009: bind-time validation rejects StringLength < 1 for
String tags; ModbusTcpTransport clamps keep-alive intervals to whole
seconds (>=1).
- Driver.Modbus-010: documented WriteOnChangeOnly's cache-invalidation
policy (reads-only) and the write-only-tag caveat.
- Driver.Modbus-011: collected the scattered instance fields into a
single contiguous block at the top of ModbusDriver.
- Driver.Modbus-012: covered the previously-uncovered Reinitialize
state-hygiene, malformed/truncated/empty-bitmap response, and
DisposeAsync teardown paths.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.TwinCAT-004: corrected the IEC time-type inline comments;
documented that the driver currently surfaces them as raw UInt32
counters.
- Driver.TwinCAT-006: ResolveHost returns a documented UnresolvedHost
sentinel when no devices are configured instead of returning the
logical DriverInstanceId (which never matches GetHostStatuses).
- Driver.TwinCAT-014: wired Probe.Timeout into the probe-loop call and
added a NotificationMaxDelayMs config knob threaded through
AddNotificationAsync.
- Driver.TwinCAT-015: Dispose() runs a genuinely synchronous teardown
with bounded waits (no sync-over-async deadlock pattern).
- Driver.TwinCAT-016: pinned the Structure-tag rejection and the
probe-loop vs read disposal race with regression tests.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.S7-003: ArgumentNullException.ThrowIfNull on the references
argument at the top of ReadAsync / WriteAsync (was reaching .Count
before any null check).
- Driver.S7-005: drop the redundant global::S7.Net.Plc qualifiers in
ReadOneAsync / WriteOneAsync — using S7.Net already covers Plc.
- Driver.S7-009: PollLoopAsync degrades _health to Degraded after
sustained failure and backs off exponentially up to PollBackoffCap;
resets on a healthy tick so an operator can see the loop wedge.
- Driver.S7-010: Dispose runs the synchronous teardown directly with a
bounded WhenAll Wait drain instead of bridging via DisposeAsync().
- Driver.S7-013: reject unsupported S7DataType values (Int64 / UInt64 /
Float64 / String / DateTime) at InitializeAsync so half-implemented
types no longer leak BadNotSupported live nodes into the address space.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.FOCAS-007: optional ILogger<FocasDriver> + alarm-projection
logger; log Debug around every formerly-empty catch (probe / shutdown
/ fixed-tree / recycle / alarms-read / projection).
- Driver.FOCAS-008: cache the parsed FocasAddress per tag at
InitializeAsync; Read/WriteAsync look it up instead of re-parsing on
every call.
- Driver.FOCAS-009: ProbeLoopAsync now wraps client.ProbeAsync in a
linked CTS honouring Probe.Timeout so a hung CNC socket can't block
past the configured limit.
- Driver.FOCAS-010: FocasOperationModeExtensions.ToText delegates to
FocasOpMode.ToText — single canonical op-mode label surface.
- Driver.FOCAS-011: FocasAlarmType constants are typed short to match
the cnc_rdalmmsg2 wire field and the projection switch arms.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.AbLegacy-005: optional ILogger<AbLegacyDriver> ctor parameter,
logged init failure / probe transitions / first non-zero libplctag
status per device.
- Driver.AbLegacy-011: Dispose() runs the synchronous teardown directly
instead of bridging via DisposeAsync().AsTask().GetAwaiter().GetResult()
to remove the documented sync-over-async deadlock pattern.
- Driver.AbLegacy-013: documented the ResolveHost three-tier fallback
chain in XML and pointed DiscoverAsync's IsArray=false comment at the
Modbus ArrayCount pattern for the eventual multi-element follow-up.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.AbCip-007: inject an optional ILogger<AbCipDriver> /
ILogger<AbCipAlarmProjection> (default NullLogger) and log around
every read / write / template-fetch / probe / alarm-poll failure path.
- Driver.AbCip-011: LogWarning when InitializeAsync is configured with
Probe.Enabled=true but ProbeTagPath is blank — operators now see why
GetHostStatuses keeps reporting Unknown.
- Driver.AbCip-012: documented the LibplctagTemplateReader per-call
Tag cost as accepted given libplctag's own connection pool and the
low-frequency discovery use-case.
- Driver.AbCip-013: per-device AllowPacking + ConnectionSize overrides
on AbCipDeviceOptions, threaded through AbCipTagCreateParams; central
BuildCreateParams helper replaces five ad-hoc clones; AllowPacking
now reaches Tag.AllowPacking at runtime.
- Driver.AbCip-015: stale-comment sweep — every PR-N forward-reference
is rewritten to describe present behaviour.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
- Driver.Galaxy-005: rewrite the EventPump BoundedChannelOptions comment
to honestly describe the Wait+TryWrite pattern.
- Driver.Galaxy-010: ResolveApiKey now warns when a literal API key is
used in production wiring; added an explicit dev: prefix for known
cleartext-in-dev cases and rewrote the GalaxyGatewayOptions doc.
- Driver.Galaxy-012: O(1) reverse-lookup for SubscriptionRegistry
dispatch via per-entry FullRefByItemHandle map; immutable hash-set for
the cross-binding reverse map; SubscribeAsync / ReadViaSubscribeOnce
use BuildResultIndex for per-reference correlation.
- Driver.Galaxy-013: ReinitializeAsync now validates the incoming JSON
against the running options; ReplayOnSessionLost honoured by the
Replay path; class summary rewritten to describe the shipped surface.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
GetMemoryFootprint now returns tagsByName * 256 + nativeSubs * 512 bytes
instead of a hard-coded 0; document that the stream-and-discard symbol
browse leaves no flushable cache so FlushOptionalCachesAsync is a
deliberate no-op.
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
Confirm AdsErrorCode values from Beckhoff.TwinCAT.Ads 7.0.172 and rewrite
MapAdsError with 20 explicit cases. Fix critical bug: AdsSymbolVersionChanged
was 0x0702 (DeviceInvalidGroup) but DeviceSymbolVersionInvalid is 1809
(0x0711); correct constant and all comments. Add BadOutOfService for
DeviceNotReady and BadInvalidState for DeviceInvalidState/PLC-in-Config.
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
Replace yield break with cancellationToken.ThrowIfCancellationRequested()
in BrowseSymbolsAsync so a cancelled browse propagates as
OperationCanceledException instead of silently completing with a partial
symbol set.
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
Swap _devices and _tagsByName to ConcurrentDictionary so ShutdownAsync
Clear() no longer races concurrent TryGetValue calls; store ProbeTask
on DeviceState and await it in ShutdownAsync before disposing the client
and gate, eliminating the probe-disposal race.
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
Reject Structure-typed pre-declared tags in BuildTag at config-parse time
with a clear InvalidOperationException; replaces the previous silent
garbage read (MapToClrType fell through to typeof(int)) and late
NotSupportedException on writes.
Co-Authored-By: Claude Sonnet 4.6 <noreply@anthropic.com>
Route all Session mutations through _probeLock so OnReconnectComplete, ShutdownAsync,
and OnKeepAlive cannot race each other when swapping or clearing the active session.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Wrap the InitializeAsync + ReadAsync body in a try/catch so an unreachable PLC
(refused TCP connect, wrong slot) still prints the structured Host:/CPU:/Health:/
Last error: report from driver.GetHealth() instead of crashing with a stack trace.
OperationCanceledException re-throws so Ctrl+C during connect exits cleanly.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Trim the --type help text on read and subscribe to the implemented set
(Bool/Byte/Int16/UInt16/Int32/UInt32/Float32) and append a one-line caveat that
Int64, UInt64, Float64, String, and DateTime are not yet implemented and will
return BadNotSupported — so the CLI does not advertise options that cannot succeed.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Wrap all numeric/DateTime BCL parses in ParseValue with try/catch(FormatException)
and try/catch(OverflowException) that re-throw as CommandException, matching the
existing Bool path. Update ParseValue_non_numeric_for_numeric_types_throws to assert
CommandException (not FormatException), and add an overflow-edge test (Byte value 256).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
S7-002: add inline comment documenting the UInt32→Int32 lossiness in MapDataType,
consistent with the Int64/UInt64 note. Tracked for a follow-up that adds unsigned
DriverDataType members.
S7-004: inject ILogger<S7Driver> (optional, defaults to NullLogger); add structured
log calls for connect success/failure, probe Running/Stopped transitions, and
swallowed poll-loop exceptions, so operators have an event trail via Serilog.
S7-008: restructure WriteAsync catch ladder to mirror ReadAsync — OperationCanceledException
re-throws, NotSupportedException → BadNotSupported, PUT/GET-disabled PlcException →
BadNotSupported/Faulted, genuine PlcException → BadDeviceFailure/Degraded, all
others → BadCommunicationError/Degraded. Health is now updated on every write failure.
Also factor ReadOneAsync reinterpret into internal ReinterpretRawValue and
WriteOneAsync boxing into internal BoxValueForWrite for testability (Driver.S7-014).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Remove the dead ProbeAddress config surface from S7ProbeOptions and the factory
DTO. ProbeLoopAsync uses Plc.ReadStatusAsync (CPU-status PDU), not a tag-address
read — ProbeAddress was never consumed. The XML doc on Probe is corrected to
describe the ReadStatusAsync-based probe. Existing configs that set probeAddress
are silently ignored by the JSON deserializer.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Complete the incomplete Addressing-003 fix: TryParseByteOrder now produces a
diagnostic mentioning "field 2" when a known type-code token (e.g. BOOL) is
supplied in the byte-order slot, so the user is guided to the correct field.
The previous fix only wired the message in the else-branch, which was unreachable
because LooksLikeByteOrderToken(BOOL) returned true first.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Reject --region Coils combined with any non-boolean --type with a CommandException
that names the constraint: coils carry a single bit, so only --type Bool is valid.
Without this check a write like "--region Coils --type UInt16 --value 42" would
silently coerce to a coil ON with no diagnostic.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Add --bit-index, --string-length, and --string-byte-order options to
SubscribeCommand, mirroring ReadCommand, and pass them into ModbusTagDefinition
so that BitInRegister and String type subscriptions use the correct bit index and
string length rather than silently defaulting to bit-0 / zero-length.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Reject an empty 3rd field in the address parser by checking parts[2].Length > 0
before the All(char.IsDigit) guard, so a trailing-colon typo like "40001:F:"
produces a diagnostic instead of silently parsing as a scalar.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
StatusCode is not a .NET type reference in this assembly — replace the unresolvable
<see cref="StatusCode"/> with prose text so TreatWarningsAsErrors does not fail the
build on the CS1574 unresolved-cref warning.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
GetMemoryFootprint() returned a constant 0 with a stale "PR 4.4 sets this" comment
even though PR 4.4 shipped the SubscriptionRegistry. Replace with a live estimate:
64 bytes × TrackedItemHandleCount + 256 bytes × TrackedSubscriptionCount. A 50k-tag
set now registers ~3 MB with the server's cache-flush heuristic instead of being
invisible. Returns 0 when no subscriptions are active.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Clear _tagsByName, _lastPublishedByRef, and _lastWrittenByRef in ShutdownAsync
(via the new shared TeardownAsync helper) so a ReinitializeAsync cycle starts
from a clean state, consistent with the existing _autoProhibited.Clear().
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Fix two resource-management bugs in StartDeployWatcher / BuildDefaultHierarchySource:
(a) Replace the discarded `_ = StartAsync(...)` with an explicit task variable that
surfaces any synchronous InvalidOperationException (called-twice guard) rather than
silently swallowing it.
(b) Change both StartDeployWatcher and BuildDefaultHierarchySource to use ??= on
_ownedRepositoryClient so the first client created (by whichever path runs first)
is reused by the second path, preventing a second GalaxyRepositoryClient from being
created and the first from leaking past the driver's lifetime.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Implement IAsyncDisposable on GalaxyDriver so async sub-component disposals
(EventPump, AlarmFeed, MxSession, MxClient, RepositoryClient) are awaited rather
than blocked on GetAwaiter().GetResult(). DisposeAsync is now the primary path;
Dispose() delegates to it for using-statement compatibility. Each async component's
shutdown is awaited individually with a best-effort catch so a single slow shutdown
cannot prevent the rest of the cleanup sequence from running.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
HashSet<T>.First() enumeration order is unspecified and unstable across mutations, so
the "owner" handle attached to alarm events was non-deterministic when multiple alarm
subscriptions were active. Change _alarmSubscriptions from HashSet to List (preserving
insertion order) and pick [0] — the earliest-registered handle — as the deterministic
owner. The server routes transitions by SourceNodeId, not by handle, so the choice of
handle does not affect delivery to active subscribers.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Add StatusCodeMap.ToQualityCategoryByte(uint) so the StatusCode → quality-byte
mapping lives in one place next to its inverse (FromQualityByte). GalaxyDriver
OnPumpDataChange now delegates to the helper instead of duplicating the shift+switch
inline; a future edit to the OPC UA bit layout cannot silently desync the probe-health
decode. Unit tests in StatusCodeMapTests pin all three category buckets and the
round-trip invariant.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
StatusCodeMap.FromMxStatus checked `success != 0` to determine success, but the
mxaccessgw proto contract explicitly documents that `success` is not a boolean and
that clients must branch on `category` (MX_STATUS_CATEGORY_OK), not on `success`
alone. Replace the raw field check with `status.IsSuccess()` from
MxStatusProxyExtensions, which requires both `success != 0` AND `category == Ok`.
A worker reporting success=1 with a non-OK category was previously misreported as
Good. Updated StatusCodeMapTests with a regression case covering the inverted scenario.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
EffectiveCipPath now references ParsedAddress/Profile properties instead
of the captured primary-constructor parameters to avoid CS9124 (param
captured into enclosing type AND used to init a member).
NonZero_libplctag_status_maps_via_AbLegacyStatusMapper updated to pass
(int)Status.ErrorNotFound rather than the stale magic integer -14 that
the old mapper happened to handle but the new enum-based mapper does not.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>