Anonymous OPC UA sessions had no roles (`UserIdentity()`), so
`WriteAuthzPolicy.IsAllowed(SecurityClassification.Operate, [])`
rejected every write with `BadUserAccessDenied`. The reverse-write
stage of the Modbus e2e script surfaced this: stages 1-3 + 5 pass
forward-direction, stage 4 (OPC UA client → server → driver → PLC)
blew up with `0x801F0000` even with the factory + seed perfectly
wired.
Adds a single config knob:
"OpcUaServer": {
"AnonymousRoles": ["WriteOperate"]
}
Default empty preserves the pre-existing production-safe behaviour
(anonymous reads FreeAccess tags, rejected on everything else). When
non-empty, `OtOpcUaServer.OnImpersonateUser` wraps the anonymous token
in a `RoleBasedIdentity("(anonymous)", "Anonymous", AnonymousRoles)`
so the server-layer write guard sees the configured roles.
Wire-through:
- OpcUaServerOptions.AnonymousRoles (new)
- OpcUaApplicationHost passes it to OtOpcUaServer ctor
- OtOpcUaServer new anonymousRoles ctor param + OnImpersonateUser
branch
- Program.cs reads `OpcUaServer:AnonymousRoles` section from config
Env override syntax: `OpcUaServer__AnonymousRoles__0=WriteOperate`.
## Verified live
Booted server against `seed-modbus-smoke.sql` with
`OpcUaServer__AnonymousRoles__0=WriteOperate` + pymodbus fixture →
`test-modbus.ps1 -BridgeNodeId "ns=2;s=HR200"`:
=== Modbus e2e summary: 5/5 passed ===
[PASS] Probe
[PASS] Driver loopback
[PASS] Server bridge (driver → server → client)
[PASS] OPC UA write bridge (client → server → driver)
[PASS] Subscribe sees change
All five stages green end-to-end. Issue #219 closed by this PR; the
Modbus-seed update to set AnonymousRoles lives in the follow-up #220
live-boot PR (same AnonymousRoles value applies to every driver since
the classification is a driver-constant, not per-tag).
Full-solution build: 0 errors, only pre-existing xUnit1051 warnings.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Closes Stream C per docs/v2/implementation/phase-6-1-resilience-and-observability.md.
Core.Observability (new namespace):
- DriverHealthReport — pure-function aggregation over DriverHealthSnapshot list.
Empty fleet = Healthy. Any Faulted = Faulted. Any Unknown/Initializing (no
Faulted) = NotReady. Any Degraded or Reconnecting (no Faulted, no NotReady)
= Degraded. Else Healthy. HttpStatus(verdict) maps to the Stream C.1 state
matrix: Healthy/Degraded → 200, NotReady/Faulted → 503.
- LogContextEnricher — Serilog LogContext wrapper. Push(id, type, capability,
correlationId) returns an IDisposable scope; inner log calls carry
DriverInstanceId / DriverType / CapabilityName / CorrelationId structured
properties automatically. NewCorrelationId = 12-hex-char GUID slice for
cases where no OPC UA RequestHeader.RequestHandle is in flight.
CapabilityInvoker — now threads LogContextEnricher around every ExecuteAsync /
ExecuteWriteAsync call site. OtOpcUaServer passes driver.DriverType through
so logs correlate to the driver type too. Every capability call emits
structured fields per the Stream C.4 compliance check.
Server.Observability:
- HealthEndpointsHost — standalone HttpListener on http://localhost:4841/
(loopback avoids Windows URL-ACL elevation; remote probing via reverse
proxy or explicit netsh urlacl grant). Routes:
/healthz → 200 when (configDbReachable OR usingStaleConfig); 503 otherwise.
Body: status, uptimeSeconds, configDbReachable, usingStaleConfig.
/readyz → DriverHealthReport.Aggregate + HttpStatus mapping.
Body: verdict, drivers[], degradedDrivers[], uptimeSeconds.
anything else → 404.
Disposal cooperative with the HttpListener shutdown.
- OpcUaApplicationHost starts the health host after the OPC UA server comes up
and disposes it on shutdown. New OpcUaServerOptions knobs:
HealthEndpointsEnabled (default true), HealthEndpointsPrefix (default
http://localhost:4841/).
Program.cs:
- Serilog pipeline adds Enrich.FromLogContext + opt-in JSON file sink via
`Serilog:WriteJson = true` appsetting. Uses Serilog.Formatting.Compact's
CompactJsonFormatter (one JSON object per line — SIEMs like Splunk,
Datadog, Graylog ingest without a regex parser).
Server.Tests:
- Existing 3 OpcUaApplicationHost integration tests now set
HealthEndpointsEnabled=false to avoid port :4841 collisions under parallel
execution.
- New HealthEndpointsHostTests (9): /healthz healthy empty fleet; stale-config
returns 200 with flag; unreachable+no-cache returns 503; /readyz empty/
Healthy/Faulted/Degraded/Initializing drivers return correct status and
bodies; unknown path → 404. Uses ephemeral ports via Interlocked counter.
Core.Tests:
- DriverHealthReportTests (8): empty fleet, all-healthy, any-Faulted trumps,
any-NotReady without Faulted, Degraded without Faulted/NotReady, HttpStatus
per-verdict theory.
- LogContextEnricherTests (8): all 4 properties attach; scope disposes cleanly;
NewCorrelationId shape; null/whitespace driverInstanceId throws.
- CapabilityInvokerEnrichmentTests (2): inner logs carry structured
properties; no context leak outside the call site.
Full solution dotnet test: 1016 passing (baseline 906, +110 for Phase 6.1 so
far across Streams A+B+C). Pre-existing Client.CLI Subscribe flake unchanged.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>