DriverHostActor built ScriptedAlarmEngine without a scriptTimeout, so every
production alarm predicate fell back to TimedScriptEvaluator.DefaultTimeout
(250 ms) while virtual tags and Calculation tags ran on 2 s. History shows no
decision behind it: 250 ms is the generic Phase-7 A.4 default, the VT
evaluator moved to 2 s in F8b (219d10a2) and the alarm engine was simply never
given a value.
- New node-wide Scripting:RunTimeout (default 2 s, clamped to (0, 60 s],
non-positive -> default, each clamp a startup Warning) on ScriptingOptions.
- The VT evaluator and the alarm engine default to it; DriverHostActor now
builds the engine through CreateScriptedAlarmEngine, which passes it
explicitly. Calculation keeps its per-driver runTimeoutMs.
- Docs: ScriptEditor (config table), ScriptedAlarms, VirtualTags.
Tests: ScriptedAlarmEngineBudgetTests (a 600 ms predicate now completes and
activates; default and configured budgets), ScriptedAlarmEngineBudgetWiringTests
(the host-built engine), ScriptingOptionsBindingTests (bind + clamps). The
engine and wiring tests fail with the old 250 ms default restored.
Claude-Session: https://claude.ai/code/session_01GT67AEHd2Acv1YPwGfXEoV
Review m-1. The bind moves from Program.cs into
Host.Configuration.ScriptingOptionsBinding.Bind, which binds the
section and clamps it. Program.cs calls it, and
ScriptingOptionsBindingTests drives it with in-memory configuration.
Every documented key takes a non-default value, so a misspelled
property or key goes red instead of silently falling back to the
defaults. The tests also cover a clamped bind (1e300 / 1024 / 0, three
adjustments), an absent section, and the sibling LogFilePath /
LogTopicMinLevel keys leaving the bind untouched.
Refs #731#734
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT