Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good
so every native + scripted condition reported Good unconditionally — a
comms-lost device still showed a healthy, inactive, Good condition (a
wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs
bucketing on IsGood) could not tell "genuinely inactive" from "lost contact".
Layer 1 — make Quality a real, plumbed field:
- AlarmConditionSnapshot gains OpcUaQuality Quality (default Good).
- MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good).
- WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality
member so a quality-bucket change fires a Part 9 event.
Layer 2 — drive native quality from driver connectivity (a comms-lost driver
emits no alarm transitions, and an alarm-bearing raw tag has no value variable,
so quality can't come from either existing channel):
- DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting.
- DriverHostActor fans it to every native condition the driver owns as
OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect).
- New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and
fires only on a bucket change — never touches Active/Acked/Retain (an active
alarm that loses comms stays active). Not a full-snapshot re-projection, so it
can't clobber severity/message and works for a never-fired condition.
Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the
reflection forwarding guard). Ungated by redundancy role; no /alerts row.
Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3).
Tests: node-level (materialise/project/no-clobber/unknown-node no-op),
NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor
fan-out, OpcUaPublishActor routing, and the wire-level guard
(Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified
against a simulated pre-fix always-Good server. Existing DriverInstanceActor
parent probes ignore the new ConnectivityChanged.
Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)";
design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.
A DriverInstanceActor stuck Reconnecting/Connecting now adopts a config delivered via ApplyDelta and
re-initialises with it, instead of dead-lettering and retrying the stale config forever. A monotonic
init generation supersedes the in-flight init so the corrected config always wins.
Materialised SystemPlatform/Galaxy variables previously stayed
BadWaitingForInitialData because nothing told the driver to subscribe
(OpcUaPublishActor TODO 'on a future SubscribeBulk pass') and published
values were only forwarded to the VirtualTag mux, never the OPC UA sink.
DriverHostActor now, after each apply, groups the deployment's galaxy tag
MXAccess refs by driver and sends DriverInstanceActor.SetDesiredSubscriptions;
the actor retains the set and (re)subscribes on every Connected entry, so
values resume after reconnects/redeploys (closes the F8b/#113 gap). Published
values are also forwarded to OpcUaPublishActor as AttributeValueUpdate
(NodeId == galaxy MxAccessRef) so the materialised variable shows live data.
Verified live in docker-dev: galaxy TestMachine_001 tags go Good with a
changing TestChangingInt. +1 unit test.
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
Three pieces landed in one batch, closing F7-residual + Host DI #106:
Runtime/DriverInstanceActor:
- Subscribe / Unsubscribe message contracts; the Connected state
handles them via IDriver.ISubscribable. On every OnDataChange
event the actor publishes AttributeValuePublished to its parent
(DriverHostActor → OpcUaPublishActor). OPC UA StatusCode is
mapped to the 3-state OpcUaQuality enum via severity bits
(00=Good, 01=Uncertain, 10/11=Bad).
- DetachSubscription tears the handler off the driver on
DisconnectObserved, Unsubscribe, and PostStop so a stale handler
never pushes to a dead actor.
- WriteAttribute now dispatches IWritable.WriteAsync (batch of one)
with a 5s CancellationTokenSource; status-code propagated to
WriteAttributeResult on non-Good results.
Host:
- New ProjectReferences to Core + every cross-platform driver
assembly (AbCip/AbLegacy/FOCAS/Galaxy/Modbus/S7/TwinCAT).
Galaxy is net10 (gRPC client to mxaccessgw); the COM-bound net48
Wonderware Historian driver stays out of the Host's reference
closure — its .Client gRPC wrapper is what binds for historian
needs.
- New DriverFactoryBootstrap.AddOtOpcUaDriverFactories() registers
a singleton DriverFactoryRegistry, invokes each driver's
Register(registry, loggerFactory), and binds IDriverFactory to
DriverFactoryRegistryAdapter. Replaces the F7 NullDriverFactory
default so deploys actually materialise real IDriver instances
on driver-role nodes. ShouldStub() still gates per-platform
behaviour at spawn time.
- Program.cs wires AddOtOpcUaDriverFactories() before AddAkka so
the runtime extension can resolve IDriverFactory from DI.
Tests: Runtime 46 -> 52 (+6):
- Write returns success when StatusCode = Good
- Write propagates non-Good status code in failure Reason
- Subscribe forwards OnDataChange to parent as AttributeValuePublished
- Quality translation: Uncertain (0x40...) and Bad (0x80...)
- Subscribe against non-ISubscribable returns failure
- DisconnectObserved detaches handler so late events are dropped
All 6 v2 test suites green: 152 tests passing.
Closes F7. F7-residual sub-tasks #110 (subscribe) and #111 (write)
both shipped. Host DI binding #106 shipped.