Owner decision 2026-11-13 on #872 item 1. StatusCodeMap.FromMxStatus now maps a
Pending or Warning row to Uncertain (0x40000000) for any detail, ahead of the
detail vocabulary, keeping the once-per-(detail, category) warning. MXAccess sets
success = -1 on Pending (accepted, in progress); neither category is a failure.
Detail 8001 (automation-object ConfigurationError, write rejected for type
conversion, live-captured on windev 2026-11-13) maps to BadTypeMismatch. 8018
stays BadUserAccessDenied via its SecurityError category, now pinned by a test.
Data change: the value is published Uncertain. Write reply: the result is
Uncertain, never Good, so the server (which commits only Good) reports the write
not committed and reverts the node; a later MXAccess commit arrives as a data
change. Host status is unchanged (probe decode treats Uncertain and Bad alike,
quality < 192 -> Unknown); no alarm path calls the map.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
The gateway fills Statuses on every data change (live OnDataChange, value-cache
replay and session snapshot all carry Quality too), and EventPump used the status
row whenever one was present, so Quality was never read: an off-scan, Bad or
Uncertain attribute with an OK status row was published Good. A failure status
row still wins; otherwise the quality byte grades the value (legacy parity:
quality >= 192 Good).
Live, read-only on VD03 (DEV): healthy ScanState and _TestArea attributes stay
Good (0x00000000) via quality 192; the stopped JoePlatform/JoeAppEngine ScanState
now publish BadCommunicationError (0x80050000) instead of generic Bad, with no
"unrecognised quality byte" warning.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk