Live investigation showed the earlier 'C2 server-gated event reads' attribution was
wrong: the gateway's SQL event reader works (a source-filtered ReadEvents returns a
real Galaxy-sourced event's history; a time-only ReadEvents returns 50 events). The
alarm round-trip's source-filtered readback is empty only because an ad-hoc SendEvent
is recorded in Runtime.dbo.Events WITHOUT a Source_Object — so reading existing Galaxy
alarm/event history by source works, but round-tripping OtOpcUa's own sends by source
needs the gateway's SendEvent to populate the event source. Skip message corrected.
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
Live validation against wonder-sql-vd03 caught that the gateway's SendEvent handler
throws when the wire event carries a client-supplied Id — so every alarm send from
OtOpcUa failed (PermanentFail). AlarmEventMapper now leaves HistorianEvent.Id unset
(the historian assigns event identity) and preserves the alarm's id as an 'AlarmId'
property. With this, the live alarm send acks.
Also harden the env-gated live tests against two gateway/historian-side limitations
surfaced during validation (neither an OtOpcUa defect): the write readback uses a
timezone-tolerant window (an explicit-timestamp WriteLiveValues lands offset by the
deployment's local-vs-UTC delta — reproducible via raw grpcurl; OtOpcUa sends correct
UTC), and the alarm ReadEvents readback skips with a clear reason when the historian's
server-gated event reads (C2, won't-fix) return nothing. Read + write-persist +
alarm-send are all live-validated green; the alarm send-ack is split into its own test.
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
The HistorianGateway driver is now the sole historian read/write+alarm backend, so the
Wonderware sidecar projects are dead code. Removes the 5 Wonderware projects (driver,
.Client, .Client.Contracts, + their 2 test projects) from the solution and tree, and fully
retires the vestigial 'Historian.Wonderware' driver type (UI/probe-only; it had no driver
factory): the Host probe registration, the AdminUI driver-config surface (driver page,
tag-config editor/model/validator entry, address picker/builder, driver-type catalog +
dropdown + edit-router entries), and their tests. Prunes the now-unused Wonderware
connection fields (Host/Port/UseTls/ServerCertThumbprint/SharedSecret) from
AlarmHistorianOptions (keeping Enabled + the SQLite store-and-forward knobs) and refreshes
the stale XML docs that named Wonderware as the production backend.
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
I-1: GatewayAlarmHistorianWriter no longer dead-letters events cancelled
mid-drain at shutdown. WriteBatchAsync short-circuits remaining events to
RetryPlease once cancellation is requested, and SendOneAsync catches
OperationCanceledException (when the token is cancelled) -> RetryPlease,
so in-flight events stay queued instead of being permanently dropped.
I-2: FasterLogHistorizationOutbox.Dispose now guards the awaited periodic
loop with a broad catch (Exception) after the OperationCanceledException
catch, so a non-Faster teardown fault (e.g. ObjectDisposedException) can
never escape Dispose.
M-1: GatewayTagProvisioner skips the empty EnsureTags round-trip when every
request is non-historizable (early return).
M-2: GatewayTagProvisioner handles plain shutdown cancellation quietly
(Debug, not Warning), counting the unsent batch as Failed, never throwing.
M-3/M-4: Added remove-last-entry (TailAddress truncation branch) and
FIFO implicit-ack (RemoveAsync acks up to and including the target)
durability tests, both reopen-and-survive.
M-5: Clarifying comment in RecoverState on the transient over-capacity
rebuild after a crash between append-commit and drop-truncation-commit.
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
Addresses T7/T8/T11 code-review minors: route the sync dispose through DisposeAsync
so a double Dispose()+DisposeAsync() stays a no-op; cover the sync path.
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
Addresses Task 1 code-review: document that ReadEventsAsync.maxEvents is enforced
client-side (no server cap in the wire contract); add Platforms=AnyCPU;x64 to match
sibling drivers; use ValueTask.CompletedTask in FakeHistorianGatewayClient.
Claude-Session: https://claude.ai/code/session_012SDSQ3AcaXqPcBtDESBRii
Equipment tags were stuck at Bad_WaitingForInitialData on the deployed driver: the equipment poll, fixed-tree loop, probe and recycle shared one FOCAS/2 socket with no serialization, and the steady-state read had no timeout — concurrent reads collided and a stalled read hung forever, never overwriting the node's initial-data seed.
- SynchronizedFocasClient: per-device SemaphoreSlim gate + per-call timeout around every wire op (Connect/Probe gated, not double-bounded); wired in EnsureConnectedAsync. ReadAsync/WriteAsync map a per-call timeout to BadCommunicationError instead of rethrowing.
- FlexibleStringConverter on FOCAS config Series: the AdminUI persists the enum as a number ("series":6); accept number-or-string instead of throwing -> stub.
- FocasHostAddress.TryParse tolerates a scheme-less {ip}[:{port}] (AdminUI hostAddress form); canonical focas:// unchanged, malformed schemes still rejected.
247 FOCAS tests green; each fix has a regression test. Live-validated on wonder-app-vd03 (tags read Good).
First real FOCAS hardware contact (Makino Pro 5 / 31i-B @ 10.201.31.5). A full
v3 data-PDU capture corrected the initial diagnosis: the v3 block envelope is
identical to v1, so only specific payload structs / request math / one client
robustness gap were wrong — not "framing rewrites".
Fixes (all re-validated live through the fixed driver):
- version gate: accept inbound PDU {1,3}, keep emitting v1 (FocasWireProtocol).
- cnc_rdtimer: 8-byte {minute,msec} payload is little-endian (ParseTimer) — the
only decode with an in-range msec field.
- pmc_rdpmcrng: request range widened to the data-type byte width
(end = start + width - 1) so a Word/Long isn't truncated to 0 values
(was spurious BadOutOfRange); decode extracted to ParsePmcRange.
- cnc_rdsvmeter: per-axis LOADELM is 8 bytes (not 12) and names come from the
0x0089 block — ParseServoMeters fixes the misaligned 655360 garbage. Also the
"hang" was NetworkStream.ReadAsync not aborting a stalled socket: ReadExactlyAsync
now disposes the stream on cancellation so a stalled peer can't wedge a poll loop.
- cnc_rddynamic2: contract guard rejecting axis < 1 (driver poll already 1-based).
- FocasDriverProbe: run a real wire session (initiate + cnc_statinfo) instead of
degrading to Ok=true "TCP reachability only" when FWLIB is absent — a bare TCP
listener no longer reports HEALTHY.
cnc_rdparam (0x000e) is unsupported on this control — EW_FUNC across 14
request-framing variants x 4 known-present params; needs a reference FWLIB trace
or is restricted. Deferred (deployed config uses macros, not parameters).
Tests: FOCAS suite 234 green (+16), full solution builds 0 errors. Raw v3
captures checked in under tests/.../Fixtures/v3/. Capture tools under scripts/focas/.
Docs: docs/plans/2026-06-25-focas-pdu-v3-{30i-b-support,implementation-plan}.md,
docs/drivers/FOCAS.md, docs/v2/focas-version-matrix.md,
docs/deployments/wonder-app-vd03-makino-z-34184.md.
Cross-module fix from the review sweep. -018 (Medium): AbCipTagDto/AbCipMemberDto dropped
elementCount/isArray, so driver-config-authored array tags read as a single scalar. Added the
two optional JSON fields (additive; missing -> scalar as before) threaded into the tag def +
TDD.
Cross-module fix from the review sweep. -003 (Medium): the browser's JsonOpts lacked
JsonStringEnumConverter (the factory+probe both carry it), so AdminUI string-enum configs
(AuthType/SecurityPolicy/SecurityMode/TargetNamespaceKind) threw on deserialize. Added the
converter (accepts string AND numeric) + TDD.
Re-review at 7286d320. -008 (Low): ParseValue maps FormatException/OverflowException to a
clean CommandException (was raw stack trace) + tests. -009: FlushLogging() in all 5 commands'
finally blocks (parity with AbCip.Cli).
Re-review at 7286d320. -006 (Low): FlushLogging() in all command finally blocks + tests.
-007: rewrite the inaccurate handler-detach comment (cleanup is via await using disposal).
Re-review at 7286d320. -008 (Low): all four commands now FlushLogging() in finally (parity
with AbCip.Cli; subscribe could drop shutdown log lines) + IL-inspection test.
Re-review at 7286d320. -009: 'four'->'six' driver-CLI count in Program.cs. -010: ReadCommand
--type help no longer lists Structure (rejected at runtime) + pinning test.
Re-review at 7286d320. -011: FrameWriter folded the sync WriteByte (could block on SslStream
past the call timeout) into one async 5-byte header write. -012: DefaultTcpConnectFactory
readonly. -013: wire-parity test for PerEventStatus [Key(4)]. No wire change.
Re-review at 7286d320. -014 (Medium): ReadAtTimeAsync didn't classify StartQuery failures,
so a connection-class failure left a dead connection, re-failed every timestamp, and returned
Success=true with all-Bad (no failover); now resets+fails over via a shared classifier + tests.
-015: refresh stale named-pipe comments to TCP (no wire change). -013 (silent cap truncation,
ties OpcUaServer-002/Core.Abstractions-009) deferred cross-module. NOTE: the SDK-touching tests
are net48 + native aahClientManaged and run only on Windows; macOS verifies build + the SDK-free
subset only.
Re-review at 7286d320. -013 (Medium, testing): the managed FOCAS/2 wire-decode layer
(BuildPdu/ParseResponseBlocks, incl. cnc_getfigure stride) had zero byte-level tests; added
15 (no decode bug found). -014 (spindle-load truncation heuristic) deferred bench-gated.
Note: runtime read path is now pure-managed TCP (no P/Invoke except the probe handshake).
Re-review at 7286d320. -017 (Medium): TwinCATTagDto lacked ArrayLength, so JSON-authored
pre-declared array tags were silently scalar (Phase-4c array path dead for them). Fix:
add ArrayLength to the DTO + thread through BuildTag with positive-value guard + TDD.
Re-review at 7286d320. -014 (Medium): Bit EncodeValue (no bitIndex) wrote SetInt8 while
DecodeValue read GetInt16 on a 16-bit B-file element, so a false write could round-trip
as true (stale high byte). Fix: SetInt16 + TDD. -015: tests pass CancellationToken.
Re-review at 7286d320. -016: BrowseRecursiveAsync now releases the server-side continuation
point on OperationCanceledException (BrowseNext releaseContinuationPoints:true) before
rethrowing (resolves the Browser-002 cross-cutting leak) + TDD.
Re-review at 7286d320. Modbus-013 (Low): bit RMW now routes the FC03 read through the
validated ReadRegisterBlockAsync (was raw-indexing readResp -> IndexOutOfRange on a truncated
PDU). Modbus-014 (Low): WriteAsync maps InvalidDataException to BadCommunicationError (was
BadInternalError), matching ReadAsync. + TDD.
Re-review at 7286d320. S7-015 (Medium): a Writable array tag had no WriteArrayAsync path
and silently returned BadCommunicationError on write; now rejected at init with a clear
NotSupportedException (read-only arrays still accepted) + TDD. S7-016 (factory JSON can't
produce array tags; needs AdminUI DTO) deferred.
Re-review at 7286d320. AbCip-016 (Medium): two cooperating defects made a declared array
member (e.g. REAL[4]) read one scalar/null — fan-out dropped ElementCount/IsArray, and
UdtMemberLayout.TryBuild ignored array members (mis-placing later members). Fix: thread
array shape through fan-out + opt whole-UDT grouping out when any member is an array + TDD.
AbCip-017 (severity-read StatusCode, Low) deferred.
Review at HEAD 7286d320. Driver.Galaxy.Browser-001 (High): MapSecurityClass codes 2-6 were
all shifted vs the runtime SecurityClassification enum (wrong security labels in the picker)
-> corrected all 7 arms + tests. -002: DisposeAsync swallows concurrent ObjectDisposedException.
-003 (ResolveApiKey dup) deferred to Contracts.
Code-review follow-ups: the page-coverage test now asserts every *DriverPage
declares a _jsonOpts serializer (so a new page that serialises config a
different way fails the guard, not just converter removal); clarify that 40 ==
(int)S7CpuType.S71500 in the numeric-throws test.
AdminUI driver-instance pages serialized enum config fields (S7 CpuType,
Modbus DataType/Region, AbCip PlcFamily, ...) as JSON *numbers* because each
page's _jsonOpts lacked a JsonStringEnumConverter. The driver factories,
however, deserialize into string-typed DTOs (+ lenient ParseEnum) and throw
when binding a JSON number to a string? — so an AdminUI-authored config
containing any enum field produced a blob the driver could not parse,
faulting the driver on deploy. Proven end-to-end for S7 and Modbus; latent
for AbCip/AbLegacy/TwinCAT/FOCAS/Galaxy/Historian. Only OpcUaClient was safe
(its factory + probe already carried the converter).
Add JsonStringEnumConverter to all 9 driver-instance pages' _jsonOpts and the
8 missing driver probes' _opts (factories unchanged — already string-via-
ParseEnum; strictly more permissive, also lets pages load hand-seeded
string-enum configs back into the form).
Also fix DriverProbeHandshakeE2eTests.AbCip_Green_AgainstSim to probe a real
sim tag (TestDINT) — the no-tags @raw_cpu_type fallback is rejected by the
ab_server sim with ErrorBadParam (a real ControlLogix returns ErrorNotFound,
which the probe treats as reachable; hardware-gated follow-up).
Tests: reflection guard over all driver pages' _jsonOpts (AdminUI.Tests);
factory round-trip + numeric-form-throws guards for S7 and Modbus.
Found by running the never-before-run FB-9/FB-10 live verifies.