GalaxyAlarmPriority, the one table live Galaxy alarms (MxAccessSeverityMapper)
and AVEVA A&E history (EventMapper, #886) map the AVEVA priority through, ranked
a higher number as more severe. AVEVA ranks priority 1 as the most urgent, so a
priority-1 alarm read 250 and a priority-999 system event 1000.
It now uses AVEVA's default priority ranges, most urgent first:
AVEVA priority AVEVA severity bucket OPC UA Severity
1-250 1 Critical Critical 1000
251-500 2 High High 750
501-750 3 Medium Medium 500
751-999 4 Low Low 250
(history only) 0 not an alarm - 1
Out-of-range priorities clamp (<= 0 Critical, > 999 Low). Evidence, vd03
Runtime.dbo.Events read-only: priority 1/100 alarms carry AVEVA severity 1,
400/500 severity 2, 600/700 severity 3, and every priority-999 System.* /
User.* row severity 0 with IsAlarm 0.
- Live and history now use the same number. GalaxyDriver passes the table's
exact value as AlarmEventArgs.OpcUaSeverity. Before, it passed only the bucket,
which NativeAlarmProjector re-mapped through its generic 200/500/700/900
ladder, so live and history disagreed even before the direction fix.
- History: a row whose AVEVA severity is 0 (System.Start/Stop/Deploy,
User.Write...) is not an alarm and reads Severity 1, below every alarm band.
For alarms AVEVA's 1-4 severity is still never the value: the live feed
carries only the priority, so it cannot use it, and history must agree.
- Docs: docs/Historian.md gains "Galaxy alarm priority -> Severity
(lmxopcua#887)"; docs/AlarmTracking.md updated.
- Live re-run of the #801/#886 harness against vd03 HistorianGateway
ea9f21c (read-only, network-only): 224 of 233 cases identical to the #886
run, the 9 others differ only in Severity (priority-700 alarm rows 750 ->
500, 19 system/user events 1000 -> 1). Record: aveva-history-801.md
"#887 re-run", report aveva-gate-sdk2-887.json.gz.
Client-visible: every OPC UA client that ranks or filters Galaxy alarms by
Severity sees the order reversed (live and HistoryReadEvents). ScadaBridge has
no code that depends on the old values; its own mixed severity directions are
ScadaBridge#129.
Tests updated because they pinned the inverted table:
- Driver.Galaxy.Tests MxAccessSeverityMapperTests (rewritten: edges 1/250/251/
500/501/750/751/999, 0/-100/int.MinValue/1000/int.MaxValue clamps,
monotonic-decreasing sweep, equals GalaxyAlarmPriority for -2..1001)
- Driver.Galaxy.Tests GatewayGalaxyAlarmFeedTests (750 and 600 -> Medium)
- Driver.Historian.Gateway.Tests EventMapperTests (band table, priority 999
-> 250, 1 -> 1000; system events -> 1)
- OpcUaServer.IntegrationTests GalaxyEquipmentEventHistoryWireTests (700 ->
500, 100 -> 1000, System.Stop -> 1; the fake now stores AVEVA's real 0-4
severity)
New tests:
- Runtime.Tests NativeAlarmRestatementEndToEndTests
.Galaxy_live_condition_severity_is_the_AVEVA_priority_band (8 rows: the real
feed -> real GalaxyDriver -> host -> projector; the same rows EventMapperTests
pins on the history path)
- EventMapperTests.Aveva_severity_zero_marks_an_event_that_is_not_an_alarm
(5 rows, incl. the priority-999 alarm positive control)
- GalaxyDriverAlarmSourceTests: OpcUaSeverity passes through
Mutation check, 8 mutants, all killed: the pre-#887 inverted table; the
driver dropping OpcUaSeverity; no not-an-alarm rule; each of the three band
edges off by one; history ignoring priority; a missing AVEVA severity read
as 0.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
Group all 69 projects into category subfolders under src/ and tests/ so the
Rider Solution Explorer mirrors the module structure. Folders: Core, Server,
Drivers (with a nested Driver CLIs subfolder), Client, Tooling.
- Move every project folder on disk with git mv (history preserved as renames).
- Recompute relative paths in 57 .csproj files: cross-category ProjectReferences,
the lib/ HintPath+None refs in Driver.Historian.Wonderware, and the external
mxaccessgw refs in Driver.Galaxy and its test project.
- Rebuild ZB.MOM.WW.OtOpcUa.slnx with nested solution folders.
- Re-prefix project paths in functional scripts (e2e, compliance, smoke SQL,
integration, install).
Build green (0 errors); unit tests pass. Docs left for a separate pass.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>